3.
tems: Wet, Dry, Deluge or Preaction. Care must exercised
that the orice size, temperature rating, deflector style and
sprinkler type are in accordance with the latest published
standards of the National Fire Protection Association or the
approving Authority Having Jurisdiction Installation.
Installation
Model F1S5 Series sprinklers are special response sprin-
klers intended for installation as specied in NFPA 13. They
must also be installed with the Model D Sprinkler Wrench
specically designed by Reliable for use with these sprin-
klers.
The Model F1S5-40, F1S5-56 and F1S5 LO Recessed
Sprinklers are to be installed with a maximum recess of ¾
inch (19mm). The Model F1, F2 & FP Escutcheons illus-
trated are the only recessed escutcheon to be used with
the Model F1S5-56 and F1S5 LO Pendent Sprinklers. The
use of any other recessed escutcheon will void all approvals
Fig. 1 Fig. 2
Model F1S5-56 F1/F2 Model F1S5-56 FP
Model F1S5 Large Orice Recessed Pendent Sprinkler
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal
Orice
Thread
Size
K Factor Sprinkler
Height Sprinkler Identication
(1)RTIc(fts1/2)
[ms1/2]
US Metric
½” (15mm) ½” NPT(R½) 5.6 80 2.25” (57mm) SP(2) (110-150)
[60-80]
Model F1S5 Large Orice Recessed Pendent Sprinklers(3) (90-150)
[50-80]
20mm R½ & R¾ 8.0 115 58mm SP
(1) c= 1.09 (ft/s)1/2 [0.60 (m/s)1/2]
(2) VdS Approval for 155°F (68°C), 175°F (79°C), and 200°F (93°C) only.
(3) Currently not VdS Approved.
Model F1S5-40, F1S5-56, F1S5 LO & F1S5-56, F1S5 LO Recessed Sprinklers
Application
Model F1S5-40, F1S5-56, F1S5 LO and F1S5-56, F1S5 LO Recessed sprinklers are used in xed re protection sys-
and negate all warranties. When installing Model F1S5-40,
F1S5-56 and F1S5 LO Recessed Pendent use the Model
GFR2 Sprinkler Wrench. Any other type of wrench may
damage these sprinklers.
Note: A leak tight sprinkler joint can be obtained with a torque of 8-18
ft-lbs (10,8 - 24,4 N-m). Do not tighten sprinklers over maximum
recommended torque. It may cause leakage or impairment of the
sprinklers.
Glass bulb sprinklers have orange covers to protect the
bulb during the installation process. REMOVE THIS PRO-
TECTION ONLY AFTER THE SYSTEM HAS BEEN HYDRO-
STATICALLY TESTED AND, WHEN APPLICABLE, THE ES-
CUTCHEONS HAVE BEEN INSTALLED. RASCO wrenches
are designed to install sprinklers when covers are in place.