Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Bulletin 019 September 2018
Bulletin 019 September 2018
Model JL-17 (SIN RA1914)
K16.8 (240 metric)
Early Suppression
Fast Response Sprinkler
Features:
1. cULus, VdS, and LPCB listed as a nominal
K16.8 (240 metric) ESFR sprinkler.
2. FM Approved as a quick-response, storage
and non-storage, sprinkler.
3. Fusible link operating element.
4. Compact design allows piping to be in-
stalled farther from the ceiling and obstruc-
tions compared with larger sprinklers.
Listings and Approvals
1. Listed by Underwriters Laboratories Inc. and UL certified
for Canada (cULus) - Category Code VNWH.
2. FM Approved as a quick-response, storage and non-
storage, sprinkler.
3. VdS Schadenverhütung GmbH (VdS).
4. Loss Prevention Certification Board (LPCB).
5. CNBOP Technical Approval.
Product Description
The Reliable Model JL-17 Early Suppression Fast
Response (ESFR) Sprinkler with a nominal k-factor of
16.8 (240 metric). This sprinkler is designed to respond
quickly to growing fires and will deliver a heavy water
discharge to “suppress” rather than “control” fires. FM
Global classifies the Model JL-17 as a quick-response
sprinkler, storage and non-storage, when the sprinkler is
used in accordance with FM Global Property Loss Pre-
vention Data Sheets.
The Model JL-17 ESFR sprinkler utilizes a levered fus-
ible alloy solder link in either a 165°F (74°C) or a 212°F
(100°C) rating. Model JL-17 sprinklers are cULus Listed
for compliance with UL/ULC 1767, including the high
clearance test for rack storage.
The Model JL-17 ESFR sprinkler was designed to be
shorter and more compact than other ESFR sprinklers.
The shorter sprinkler allows piping to be installed farther
from the ceiling and obstructions. The JL-17 ESFR sprin-
kler is also less susceptible to damage due to smaller
deflector and frame design. The lighter JL-17 ESFR
passed rough use and abuse listing tests without plastic
protectors.
Model JL-17 ESFR Sprinkler
Application and Installation
The Model JL-17 ESFR sprinkler is intended for instal-
lation in accordance with NFPA 13 and FM Loss Pre-
vention Data Sheets 2-0 and 8-9, as well as the require-
ments of any Authorities Having Jurisdiction. See Table
B for information on NFPA and FM Global design criteria
for the Model JL-17 sprinkler.
Use only the Model J1 sprinkler wrench for removal
and installation. Any other type of wrench may damage
the sprinkler. A grooved wrench boss is provided on
the sprinkler to limit the potential for the wrench to slip
during installation.
Model J1
Sprinkler Wrench
Sprinklers not tightened to recommended torque may
cause leakage or impairment of the sprinkler. Damage
sprinklers must be replaced immediately.
When handling sprin-
klers, hold sprinklers
only on frame arms and
do not apply any force on
the link assembly. Sprin-
klers should be tight-
ened between 14 - 40 ft-
lbs (19 - 54 N-m) torque.
Temperature Ratings and Approvals
Temperature
Classification
Temperature
Rating Link
Color
Frame
Color
Maximum Ambient
Temperature Approvals
Sprinkler
Identification
Number
(SIN)
°F °C °F °C
Ordinary 165 74 Black Uncolored 100 38 cULus, FM, VdS, LPCB, CNBOP
RA1914
Intermediate 212 100 White White 150 66 cULus, FM, VdS, LPCB, CNBOP
Installation Data
Sprinkler Type Thread Size
Nominal K-
Factor Maximum
Working Pressure
Finish
US Metric
Pendent ¾” (R¾) 16.8 240 175 psi (12.1 bar) Bronze
Installation Criteria
See Table B on page 3 of this document.
Maintenance
The Model JL-17 ESFR Sprinkler should be inspected
and the sprinkler system maintained in accordance with
NFPA 25. Do not clean sprinkler with soap and water,
ammonia or any other cleaning fluid. Replace any sprin-
kler that has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated sprinklers. Prior to installation, sprinklers should
be maintained in the original cartons and packaging until
used, to minimize the potential for damage to sprinklers
that would cause improper operation or non-operation.
Once operated, automatic sprinklers cannot be reassem-
bled and reused. New sprinklers of the same size, type
and temperature rating must be installed. A cabinet of re-
placement sprinklers should be provided for this purpose.
2.
Model JL-17 ESFR Sprinkler Specification
Sprinklers shall be Early Suppression Fast Response
(ESFR) pendent sprinklers specifically tested and [cULus
Listed] [FM Approved] [VdS Approved] [LPCB Approved]
for commodity storage applications. Sprinkler frame and
deflector to be of bronze construction. Fusible link assem-
bly shall utilize the strut and lever principle of operation with
approved fast response black-painted or white-painted
beryllium-nickel thermal element. Water seal shall consist
of a PTFE coated Bellville spring washer and brass cap as-
sembly containing no plastic parts. ESFR sprinklers shall
have a nominal K-factor of 16.8 (240 metric) with [¾” NPT]
[ISO 7-R¾] threaded end connections. Sprinkler tempera-
ture rating shall be [Ordinary 165°F (74°C)] [Intermediate
212°F (100°C)]. ESFR pendent sprinklers shall be Reliable
Model JL-17 (Bulletin 019).
Ordering Information
Specify:
1. Sprinkler: Model JL-17
2. Temperature rating: [Ordinary 165°F (74°C)]
[Intermediate 212°F (100°C)]
3. Thread type: [3/4” NPT] [ISO 7-R3/4]
ITEM DESCRIPTION
Sprinkler Identification Number (SIN) RA1914
K Factor US (Metric) 16.8 (240)
Thread Size 3/4" (R3/4)
Sprinkler Orientation Pendent
Maximum Working Pressure, PSI (bar) 175 PSI (12 bar)
Model JL-17 Technical Data Table A
Storage Type NFPA FM GLOBAL
Sprinkler Type ESFR Storage
Response Type ESFR QR
System Type Wet Wet
Temperature Rating F (C) 165F, 212 (74, 100) 165F, 212 (74, 100)
Roof Construction See NFPA 13 See FM Global 2-0
Ceiling Slope See NFPA 13 See FM Global 2-0
Maximum Coverage Area See NFPA 13 See FM Global 2-0
Minimum Coverage Area See NFPA 13 See FM Global 2-0
Maximum Spacing See NFPA 13 See FM Global 2-0
Minimum Spacing See NFPA 13 See FM Global 2-0
Minimum Clearance to Commodity See NFPA 13 See FM Global 2-0
Sprinkler Distance to Ceiling See NFPA 13 See FM Global 2-0
Open Frame, Single, Double, Multi-
ple Row, or Portable Rack Storage of
Class I - IV, Cartoned Unexp Plastics
See NFPA 13 See FM 2-0 & 8-9
Solid Pile or Palletized Storage of
Class I - IV, Cartoned Unexp Plastics See NFPA 13 See FM 2-0 & 8-9
Idle Pallet Storage See NFPA 13 See FM 2-0,8-9 & 8-24
Rubber Tire Storage See NFPA 13 See FM 2-0 & 8-3
Rolled Paper Storage See NFPA 13 See FM 8-21
Flammable Liquid Storage See NFPA 30 See FM 7-29
Aerosol Storage See NFPA 30B See FM 7-31
Auto Components in Portable Racks N/A N/A
Model JL-17 Commodity Selection and Design Criteria Overview Table B
Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 09/18 P/N 9999970379
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years.

Other Reliable Irrigation System manuals

Reliable RFS42 Manual

Reliable

Reliable RFS42 Manual

Reliable RFS42 User guide

Reliable

Reliable RFS42 User guide

Reliable N252 EC User manual

Reliable

Reliable N252 EC User manual

Reliable GFR User manual

Reliable

Reliable GFR User manual

Reliable F1 Series Manual

Reliable

Reliable F1 Series Manual

Reliable F156 Series User manual

Reliable

Reliable F156 Series User manual

Reliable F1FR56 User manual

Reliable

Reliable F1FR56 User manual

Reliable A4 User manual

Reliable

Reliable A4 User manual

Reliable F1FR56 Manual

Reliable

Reliable F1FR56 Manual

Reliable G4A-300 User manual

Reliable

Reliable G4A-300 User manual

Reliable DH80 Dry User manual

Reliable

Reliable DH80 Dry User manual

Reliable F1FR-SS Series Manual

Reliable

Reliable F1FR-SS Series Manual

Reliable RFC30 User manual

Reliable

Reliable RFC30 User manual

Reliable GFR VELO–ECOH Manual

Reliable

Reliable GFR VELO–ECOH Manual

Reliable F1FR User manual

Reliable

Reliable F1FR User manual

Reliable N25 ESFR User manual

Reliable

Reliable N25 ESFR User manual

Reliable RFC43 User manual

Reliable

Reliable RFC43 User manual

Reliable J168 User manual

Reliable

Reliable J168 User manual

Reliable F1-SS Series User manual

Reliable

Reliable F1-SS Series User manual

Reliable F1FR56 User manual

Reliable

Reliable F1FR56 User manual

Reliable G5 Series User manual

Reliable

Reliable G5 Series User manual

Reliable DH56 HSW-PL User manual

Reliable

Reliable DH56 HSW-PL User manual

Reliable F156 EC Series User manual

Reliable

Reliable F156 EC Series User manual

Reliable F3QR56 User manual

Reliable

Reliable F3QR56 User manual

Popular Irrigation System manuals by other brands

Viking VK206 Technical data

Viking

Viking VK206 Technical data

Komet KPS operating instructions

Komet

Komet KPS operating instructions

IrriGreen Irrigreen2 installation manual

IrriGreen

IrriGreen Irrigreen2 installation manual

Tyco Fire Product Gem RFII Series instruction manual

Tyco Fire Product

Tyco Fire Product Gem RFII Series instruction manual

K-Rain KRX6 manual

K-Rain

K-Rain KRX6 manual

Tyco EC-11 Series manual

Tyco

Tyco EC-11 Series manual

Underhill Mirage M-125 Operating and maintenance instructions

Underhill

Underhill Mirage M-125 Operating and maintenance instructions

Perrot Hydra M Maintenance and operating instructions

Perrot

Perrot Hydra M Maintenance and operating instructions

Tyco Fire Product CENTRAL ESLO instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL ESLO instruction manual

K-Line Irrigation G-Set Installation and user manual

K-Line Irrigation

K-Line Irrigation G-Set Installation and user manual

Autopot easy2grow 100 Set-up guidelines

Autopot

Autopot easy2grow 100 Set-up guidelines

Baccara G75 user manual

Baccara

Baccara G75 user manual

Toro MultiMatrix V-1550 Adjustment instructions

Toro

Toro MultiMatrix V-1550 Adjustment instructions

Green Blue RootRain Metro installation guide

Green Blue

Green Blue RootRain Metro installation guide

K-Rain K2Pro Setting instructions

K-Rain

K-Rain K2Pro Setting instructions

AQUAJOE AJ-OMS18-TRB user manual

AQUAJOE

AQUAJOE AJ-OMS18-TRB user manual

AQUAJOE AJ-IST72ZM user manual

AQUAJOE

AQUAJOE AJ-IST72ZM user manual

Viking C-1 Window Sprinkler Technical data

Viking

Viking C-1 Window Sprinkler Technical data

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.