manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Reliable
  6. •
  7. Irrigation System
  8. •
  9. Reliable F1 Series Manual

Reliable F1 Series Manual

This manual suits for next models

6

Other Reliable Irrigation System manuals

Reliable G4 User manual

Reliable

Reliable G4 User manual

Reliable DH80 Dry User manual

Reliable

Reliable DH80 Dry User manual

Reliable F1FR56-300 Series User manual

Reliable

Reliable F1FR56-300 Series User manual

Reliable F1FR-SS Series User manual

Reliable

Reliable F1FR-SS Series User manual

Reliable LT56 Series User manual

Reliable

Reliable LT56 Series User manual

Reliable KFR-CCS User manual

Reliable

Reliable KFR-CCS User manual

Reliable RFS42 Manual

Reliable

Reliable RFS42 Manual

Reliable F1FR56 Manual

Reliable

Reliable F1FR56 Manual

Reliable DH80 Manual

Reliable

Reliable DH80 Manual

Reliable DH80 Dry User manual

Reliable

Reliable DH80 Dry User manual

Reliable GFR User manual

Reliable

Reliable GFR User manual

Reliable F1FR-FS56 User manual

Reliable

Reliable F1FR-FS56 User manual

Reliable F4FR-NF Manual

Reliable

Reliable F4FR-NF Manual

Reliable DH56 Dry User manual

Reliable

Reliable DH56 Dry User manual

Reliable F3QR User manual

Reliable

Reliable F3QR User manual

Reliable G5-56 Dry User manual

Reliable

Reliable G5-56 Dry User manual

Reliable F3-80 Series User manual

Reliable

Reliable F3-80 Series User manual

Reliable JL-17 User guide

Reliable

Reliable JL-17 User guide

Reliable JL-17 User manual

Reliable

Reliable JL-17 User manual

Reliable J112SS Series Manual

Reliable

Reliable J112SS Series Manual

Reliable F1-SS Series Manual

Reliable

Reliable F1-SS Series Manual

Reliable G5-56 Dry User manual

Reliable

Reliable G5-56 Dry User manual

Reliable SWC Manual

Reliable

Reliable SWC Manual

Reliable G4 User manual

Reliable

Reliable G4 User manual

Popular Irrigation System manuals by other brands

Tyco TY-B Series manual

Tyco

Tyco TY-B Series manual

Toro ZSERIES 570Z brochure

Toro

Toro ZSERIES 570Z brochure

OpenSprinkler OSPi user manual

OpenSprinkler

OpenSprinkler OSPi user manual

EINHELL GE-WW 5537 E Original operating instructions

EINHELL

EINHELL GE-WW 5537 E Original operating instructions

Hunter Institutional Series instructions

Hunter

Hunter Institutional Series instructions

Cellfast 52-305 user manual

Cellfast

Cellfast 52-305 user manual

Tyco Fire Product Star Galaxy SGQR instruction manual

Tyco Fire Product

Tyco Fire Product Star Galaxy SGQR instruction manual

Tyco Fire Product CENTRAL A instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL A instruction manual

Oral Care Technologies Hydro Floss Instructions for use

Oral Care Technologies

Oral Care Technologies Hydro Floss Instructions for use

Tyco Fire Product Gem F892 instruction manual

Tyco Fire Product

Tyco Fire Product Gem F892 instruction manual

Irrigation-Mart KIT-GK100-RV-B quick start guide

Irrigation-Mart

Irrigation-Mart KIT-GK100-RV-B quick start guide

Tyco CC3 manual

Tyco

Tyco CC3 manual

Valley Bender160 owner's manual

Valley

Valley Bender160 owner's manual

Toro 730 Series Installation and service instructions

Toro

Toro 730 Series Installation and service instructions

Eden 97063-EDAMZ quick start guide

Eden

Eden 97063-EDAMZ quick start guide

Netafim NETBEAT user manual

Netafim

Netafim NETBEAT user manual

Tyco Fire Product CENTRAL ELO-231 instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO-231 instruction manual

Johnson Controls tyco ESFR-17 manual

Johnson Controls

Johnson Controls tyco ESFR-17 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Bulletin 117 December 2020
Bulletin 117 December 2020
Model F1 LO
K 8.0 (115 metric)
Standard Response
Sprinklers
Model F1 LO Sprinkler
Standard Spray Upright
Standard Spray Pendent
Model F1 LO Recessed Sprinkler
Recessed Standard Spray Pendent
Approval Organizations
1. Underwriters Laboratories Inc. (UL)
2. Underwriters’ Laboratories of Canada (ULC)
3. Factory Mutual Approvals (FM)
4. Loss Prevention Council (LPCB, UK)
5. VdS Schadenverhütung Gmbh
6. EC Certicate: 1438-CPR-0041 (R1712)
1438-CPR-0040 (R1722)
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Product Description
Model F1 LO series sprinklers are K8.0 (115) standard-
response sprinklers with a glass bulb operating element.
Model F1 LO sprinklers are available in a range of tempera-
ture ratings as indicated in the Temperature Ratings table in
this Bulletin, which may be modied by the Installation Data
for each specic model. Model F1 LO series sprinklers are
available in a variety of nishes as indicated in the Finishes
table in this Bulletin.
Standard spray Model F1 LO sprinklers are available in
pendent, recessed pendent, and upright congurations.
These sprinklers are listed and approved for installation in
all occupancies where standard spray, standard-response
sprinklers are permitted by the applicable installation stan-
dards.
Model F1 LO & F1 LO Recessed Sprinklers
Application
Model F1 LO and F1 LO Recessed sprinklers are used in xed
re protection systems: Wet, Dry, Deluge or Preaction. Care
must exercised that the orice size, temperature rating, deflec-
tor style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Association
or the approving Authority Having Jurisdiction.
Upright
Pendent
Recessed Pendent
Technical data:
Models Response Deflector
Orientation
Nominal
K-Factor
Thread
Size
Max.
Working
Pressure
Min.
Working
Pressure
Temperature
Rating Finish
F1 LO Standard Upright
Pendent
K 8.0
(115 metric)
¾” NPT
or ISO 7-1R¾ 175 psi (1) 7 psi
See
“Temperature
Ratings” Table
See
“Finish Table”
Material Data:
Frame Deflector Load Screw Cup Washer Bulb
DZR Brass
QM Brass CDA Alloy 510
CDA Alloy 210, 220, 314, 316, 360
or
CDA Alloy 544
CDA Alloy 314
or
CDA Alloy 353
Nickel Alloy 440 or Alloy 360
coated with PTFE Adhesive Tape Glass
See “Installation Data” tables for additional information on each sprinkler model.
(1) Model F1 LO Pendent, Recessed Pendent and Upright sprinklers (SIN R1712, R1722, R1742) are cULus Listed for 250
psi (17 bar).
2.
3.
Model F1 LO Upright and Pendent Sprinklers
Installation Wrench: Model W2 Sprinkler Wrench
Installation Data:
Nominal
Orice Thread Size Nominal K-Factor Sprinkler
Height
Approval
Organization
(Ref. Page 1)
Sprinkler Identication
Numbers (SIN)
US Metric Upright Pendent
Standard-Upright (SSU) and pendent Deflectors Marked to Indicate Position
17/32” (20mm) ¾” NPT (R3/4) 8.0 115 2.3” (58mm) 1,2,3,4 (1), 5, 6 R1722(3)(4)(5) R1712(4)(5)
(1) LPCB Approval up to 286°F (141°C)
(2) Not Used
(3) Polycoated upright UL and ULC listed corrosion resistant R1722.
(4) FM Approved for polycoated sprinklers R1722, R1712.
(5) Electroless Nickel PTFE Plated - cULus listed Corrosion Resistant.
Upright Pendent
Installation Data:
Nominal Orice Thread Size
Nominal K-Factor
Sprinkler Height
Approval
Organization
(Ref. Page 1)
Sprinkler Identication
Numbers (SIN)
US Metric
17/32” (20mm) ¾” NPT (R3/4) 8.0 115 2.3” (58mm) 1,2,3,4 R1712(1)(2)
(1) LPCB Approval is for 57°C through 93°C ratings.
(2) Electroless Nickel PTFE Plated - cULus listed Corrosion Resistant.
Recessed Pendent
(1) When installed directly into a tee, the escutcheon dimension’s adjustment will be reduced.
Model F1 LO Recessed Pendent Sprinkler
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation
Model F1 LO sprinklers are standard response sprinklers in-
tended for installation as specied in NFPA 13. They must also
be installed with the Model W2 Sprinkler Wrench specically
designed by Reliable for use with these sprinklers.
The Model F1 LO Recessed Sprinklers are to be installed with
a maximum recess of ¾ inch (19mm). The Model F1 Escutch-
eon illustrated is the only recessed escutcheon to be used with
the Model F1 LO Pendent and EC Sprinklers. The use of any
other recessed escutcheon will void all approvals and negate
all warranties. When installing Model F1 LO Recessed Pendent
and EC Pendent Sprinklers, use the Model GFR2 Sprinkler
Wrench. Any other type of wrench may damage these sprin-
klers. Note: A leak tight 3/4” NPT (R/4) sprinkler joint can be
obtained with a torque of 14 - 20 ft-lbs (19 - 27 N-m). Do not
tighten sprinklers over maximum recommended torque. It may
cause leakage or impairment of the sprinklers.
Glass bulb sprinklers have orange covers to protect the bulb
during the installation process. REMOVE THIS PROTECTION
ONLY AFTER THE SYSTEM HAS BEEN HYDROSTATICALLY
TESTED AND, WHEN APPLICABLE, THE ESCUTCHEONS
HAVE BEEN INSTALLED. RASCO wrenches are designed to
install sprinklers when covers are in place.
Maintenance
The Models F1 LO sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25. Do
not clean sprinklers with soap and water, ammonia or any other
cleaning fluid. Remove any sprinkler which has been painted
(other than factory applied) or damaged in any way. A stock of
spare sprinklers should be maintained to allow quick replace-
ment of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
sprinklers that would cause improper operation or non-oper-
ation.
Ordering Information
Specify:
1. Sprinkler Model: F1 LO
2. Sprinkler Type
3. Temperature Rating
4. Sprinkler Finish
5. Thread Type: [¾” NPT] [ISO 7-1R¾]
6. Escutcheon Finish (where applicable)
Temperature Ratings
Classication
Sprinkler
Temperature
Maximum
Ambient
Temperature
Bulb
Color
°F °C °F °C
Ordinary 135 57 100 38 Orange
Ordinary 155 68 100 38 Red
Intermediate 175 79 150 66 Yellow
Intermediate 200 93 150 66 Green
High(1) 286 141 225 107 Blue
Extra High(1) 360 182 300 149 Mauve
(1) Not Available for F1 LO Recessed
Maximum Working Pressure
175 psi (12 bar)
SIN R1712, R1722 & R1742 cULus listed for 250 psi (17 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)
Finishes(1)
Standard Finishes
Sprinkler Escutcheon
Bronze
Chrome
Polyester Coated(6)(7)
Brass
Chrome
White Painted
Special Application Finishes
Sprinkler Escutcheon
Electroless Nickel PTFE(8)
Bright Brass(2)
Black Plated
Black Paint(3)(4)(7)
Off White(3)(7)
Chrome Dull
Lead Plated(3)(4)
Wax Coated(3)(4)(5)
Wax Over Lead(3)(4)
Electroless Nickel PTFE
Bright Brass
Black Plated
Black Paint
Off White
Chrome Dull
(1) Other colors and nishes are available on special order.
Consult factory for details. Custom color painted sprin-
klers may not retain their UL Corrosion resistance listing.
(2) 200°F (93°C) maximum.
(3) UL and ULC listed, and NYC approved only.
(4) 155°F to 200°F (68°C to 93°C) ratings only.
(5) 286°F (141°C) sprinklers may be coated for ambient
conditions not exceeding 150°F (66°C).
(6) UL listed corrosion resistant SIN number:
R1722 in standard Black or White. Corrosion resistance in
other polyester colors is available upon request.
(7) FM Approved for SIN R1722, R1712.
(8) cULus listed Corrosion Resistant SIN R1722, R1712 &
R1742 in Electroless Nickel PTFE Plated.
Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Ofces
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Ofces
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 12//20 P/N 9999970011
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years.