Runxin 63504 User manual

Multi-functional Flow Control Valve for
Water Treatment Systems
63504,63504B (Old Model No.: F63C1,F63G1)
63604,63604B (Old Model No.: F63C3,F63G3)
73504,73504B (Old Model No.: F68C1,F68G1)
73604,73604B (Old Model No.: F68C3,F68G3)
User Manual
Please read this manual in details before using the valve
and keep it properly in order to consult in the future.
0WRX.466.501
International Patent Public No.:
WO 2006/007772
China Patent No.: ZL02220153.X,
ZL200420078956.5
USPatentNo.:7549446
IndiaPatentNo.:232582
Russia Patent No.:2349819
SouthKoreaPatentNo.:10-0914137
Mexico Patent No.: 268581
Australia Patent No.: 2005263257
Philippine Patent No.: 1-2006-502553
Taiwan Patent No.:M287896

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
Before the valve put into use, please fill in the below content so as to
help us to refer in the future.
The Program Type Setting (Operation by professional)
When all symbols light no, press and hold and buttons for 5
seconds to enter the menu of valve model selection. Please set the
program type in accordance with the product type. (Time clock type
by days or hours or Meter type);for example,F63C1 or F63G1 should be
set to F63B1; F63C3 or F63G3 should be set to F63B3. You couldn’t set
to other type.)
Softener System Configuration
Tank Size:Dia. mm,Height mm;
Resin Volume L;Brine Tank Capacity L;
Hardness of Raw water mmol/L;
Pressure of Inlet Water MPa;
Control Valve Model ;Number ;
The Specification of Drain Line Flow Control ;
Injector No. .
Water Source: Ground-water□ Filtered Ground-water □Tap Water □
Other .
Parameter Set
Parameter
Unit
Factory
Default
Actual Value
Control Mode A-01(02,03,
04)
/
A-01
Unit Mode HU01(02,03)
/
HU01
Water Treatment Capacity
(Meter type)
m3
80
Service Days(Time of clock
type, by days)
D.
03

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
Service Hours (Time clock
type, by hours)
H.
20
Regeneration Time
/
02∶00
Backwash Time
Min.
10
Brine & Slow Rinse Time
Min.
60
Brine Refill Time
Min.
05
Fast Rinse Time
Min.
10
Interval Regeneration Days
D.
30
Output Mode b-01(02)
/
b-01
If there is no special requirement when product purchase, we choose
5# drain line flow control and 9# injector for the standard configuration.

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
I
Catalogue
Notice ...........................................................................................................
1. Product Overview.....................................................................................
1.1. Main Application & Applicability .....................................................
1.2. Product Characteristics..................................................................
1.3. Service Condition...........................................................................
1.4. Product Structure and Technical Parameters................................
1.5. Installation......................................................................................
2. Basic Setting & Usage .............................................................................
2.1. The Function of PC Board.............................................................
2.2. Basic Setting & Usage...................................................................
3. Applications..............................................................................................
3.1. Softener Flow Chart.......................................................................
3.2. The Function and Connection of PC Board...................................
A. Signal Output Connector...........................................................
B. Interlock.....................................................................................
C. Pressure Relief Output..............................................................
D. Remote Handling Connector ....................................................
E. Interlock System........................................................................
F. Series System............................................................................
3.3. System Configuration and Flow Rate Curve.................................
3.4. Parameter settlement ....................................................................
3.5. Parameter Enquiry and Setting......................................................
3.7. Trouble-Shooting............................................................................
3.8. Assembly & Parts...........................................................................
4. Warranty Card..........................................................................................

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
1
Notice
To ensure normal operation of the valve, please consult with
professional installation or repairing personnel before use it.
If there are any of pipeline engineering and electric works, there must
be finished by professional at the time of installation.
Do not use the control valve with the water that is unsafe or unknown
quality.
Depending on the changing of working environment and water
requirement, each parameter of softener should be adjusted accordingly.
When the water treatment capacity is too low, please check the resin. If
the reason is shortage of resin, please add; if the resin is turn to reddish
brown or broken, please replace.
Test water periodically to verify that system is performing satisfactorily.
Sodium used in the water softening process should be considered as
part of your overall dietary salt intake. Contact doctor if you are on a low
sodium diet.
Ensure that there is solid salt all the time in the brine tank in the course
of using, when this valve is used for softening. The brine tank should be
added the clean water softening salts only, at least 99.5% pure,
forbidding use the small salt.
Do not put the valve near heat sources or surroundings with high
humidity, corrosive, intense magnetic field or intense librations
environment.And do not leave it outside.
Forbidden to carry the injector body. Avoid to use injector body as
support to carry the system.
Forbidden to use the brine tube or other connectors as support to carry
the system.
Please use this product under the water temperature between 5~

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
2
50℃,water pressure 0.15~0.6MPa. Failure to use this product under
such conditions voids the warranty.
If the water pressure exceeds 0.6Mpa, a pressure reducing valve
must be installed before the water inlet. While, if the water pressure
under 0.15MPa, a booster pump must be installed before the water inlet.
It is suggested to install PPR pipe, corrugated pipe or UPVC pipe,
instead of TTLSG pipe.
Do not let children touch or play, because careless operating may
cause the procedure changed.
When the attached cables of this product and transformer are changed,
they must be changed to the one that is from our factory.

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
3
1. Product Overview
1.1. Main Application & Applicability
Used for softening or demineralization water treatment systems
Be suitable for
Residential softening system
Ion exchange equipment
Boiler softening water system
RO pretreatment softening system, etc.
1.2. Product Characteristics
Simple structure and reliable sealing
It adopts hermetic head faces with high degree pottery and
corrosion resistance for opening and closing. It combines with Service,
Backwash, Brine & Slow Rinse, Brine Refill and Fast Rinse.
No water pass the valve in regeneration in single tank type.
Manual function
Realize regeneration immediately by pushing manual button at any
time.
Long outage indicator
If outage overrides 3days, the time of day indicator “”will flash to
remind people to reset new time of day. The other set parameters do not
need to reset. The process will continue to work after power on.
LED dynamic screen display
The stripe on dynamic screen flash, it indicates the control valve is
in service, otherwise, it is in regeneration cycle.
Buttons lock

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
4
No operations to buttons on the controller within 1 minute, button
lock indicator light on which represent buttons are locked. Before
operation press and hold the “ ”and“ ” buttons for 5 seconds to
unlock. This function can avoid incorrect operation.
Interval backwash times (Suitable for F68)
It could set up interval backwash times for F68 up-flow regeneration
valve which means several times of services but one time of backwash.
The setting of interval backwash time depends on the local water
turbidity. (The lower the turbidity is , the longer of the interval backwash
time can be set)
It can choose time clock type or meter type by program
selection
When all symbols light no, press and hold and buttons for 5
seconds to enter the menu of valve model selection. Please set the
program type in accordance with the product type. (Tim clock type by
days or hours or meter type) (Notice: The meter type product has one
flow meter and flow meter cable, but the time clock type doesn’t have).
Four kinds of meter type can be selected ( Suite for F63C3,
F68C3)
Model
Name
Instruction
A-01
Meter
Delayed
Regenerate on the day although the available volume
of treated water drops to zero (0). Regeneration starts
at the regeneration time.
A-02
Meter
Immediate
Regenerate immediately when the available volume of
treated water drops to zero(0).
A-03
Intelligent
Meter
Delayed
Meter Delayed Regeneration type, but by setting Resin
Volume, Feed Water Hardness, Regeneration Factor,
the controller will calculate the System Capacity.
A-04
Intelligent
Meter
Immediate
Meter Immediately Regeneration Type, but by setting
Resin Volume, Feed Water Hardness, Regeneration
Factor, the controller will calculate the System Capacity.

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
5
There are two kinds of regeneration modes for time clock type
When the program is set as time clock type by days (such as F63C1,
F68C1, etc.) it can be changed to be by hours by dialing the red switch
on main control board to “1” (Refer to the Figure 13). Pointing to “ON”
means the time clock type service by days.(attention: After dialing the
switch, please restart the power)
Interlock function
It has a function of interlock to realize only one valve in regeneration
but the other valves are in service while several valves parallel in system.
In multi-steps treatment systems such as RO pre-treatment, when
several valves are in series, there is only one valve in regeneration or
washing to ensure pass water all the times while different valves in
regeneration or washing.(Application refer to Figure 3-9)
Signal output
There is a signal output connector on the main control board. It is for
controlling external wiring (Refer to Figure from Figure3-1 to Figure
3-8).
There are two kinds of output modes:
b-01 Mode: Turn on start of regeneration and shut off end of
regeneration; b-02 Mode: Signal available only at intervals of
regeneration cycles and In service.
b-01
b-02

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
6
Remote handling input
This connector can receive external signal, used together with PLC,
and computer etc. to control the valve. (Application refer to
Figure3-11)
Pressure relief output
The valve will cut off feeding water to drain line when it switches in
regeneration cycles(Same as signal output b-02). Thus in some water
treatment system, e.g. Deep Well, one booster pump was installed on
the inlet to increase the system water feeding pressure, this cut-off will
cause pressure on inlet rising too fast to damage the valve. Pressure
Relief Output can be used to avoid this problem. (Application refer to
Figure3-10)
Maximum interval regeneration days
Under the situation of service reaching the setting days and the
volume not yet, it could enter into regeneration process forcibly when
current time is the same as regeneration time.
All parameters can be modified
According to the water quality and usage, the parameters in the
process can be adjusted.

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
7
1.3. Service Condition
Runxin Valve should be used under the below conditions:
Items
Requirement
Working
conditions
Water pressure
0.15MPa~0.6MPa
Water temperature
5℃~50℃
Working
environment
Environment
temperature
5℃~50℃
Relative humidity
≤95% (When temperature is
25℃)
Electrical facility
AC100~240V/50~60Hz
Inlet water
quality
Water turbidity
Down-flow regeneration<5FTU;
Up-flow regeneration<2FTU
Water hardness
First Grade Na+<6.5mmol/L;
Second Grade Na+<10mmol/L
Free chlorine
<0.1mg/L
Iron2+
<0.3mg/L
CODMn
<2mg/L(O2)
In the above table, First Grade Na+ represents First Grade Na+
Exchanger. Second Grade Na+ represents Second Grade Na+
Exchanger.
When the water turbidity exceeds the conditions, a filter should be
installed on the inlet of control valve.
When the water hardness exceeds the conditions, the outlet water
hardness will hardly reach the requirement of boiler feed water(0.03
mmol/L). It is suggested to adopt second grade softener.

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
8
1.4. Product Structure and Technical Parameters
Product dimensions

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
9
Model
A(mm)
max
B(mm)
max
H(mm)
max
Flow Rate
m3/h
@0.3MPa
Regenerati
on
Mode
F63C3/F63C
1
282
198
177
4.0
Down-flow
F63G3/F63G
1
269
242
196
4.0
Down-flow
F68C3/F68C
1
282
198
176.5
4.0
Up-flow
F68G3/F68G
1
269
242
196
4.0
Up-flow
Attention:
1. The appearance is just for reference. It is subject to the real
product.
2. OD—Outer Diameters, 1.05OD=26.7mm
3. Transformer Output: DC12V/1.5A
1.5. Installation
A. Installation notice
Before installation, read all those instructions completely. Then
obtain all materials and tools needed for installation.
The installation of product, pipes and circuits should be
accomplished by professional to ensure the product can operate
normally.
Perform installation according to relevant pipeline regulations and
the specifications of Water Inlet, Water Outlet, Drain Outlet, Brine Line
Connector.
B. Device location
①The filter or softener should be located close to drain.

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
10
②Ensure the unit is installed in enough space for operating and
maintenance.
③Brine tank need to be close to softener.
④The unit should be kept away the heater, and not be exposed outdoor.
Sunshine or rain will cause the system damage.
⑤Please avoid to install the system in one Acid/Alkaline, Magnetic or
strong vibration circumstance, because above factors will cause the
system disorder.
⑥Do not install the filter or softener, drain pipeline in circumstance which
temperature may drop below 5℃, or above 50℃.
⑦One place is recommended to install the system which causes the
minimum loss in case of water leakage.
C. Pipeline installation

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
11
①Install control valve
a. As the Figure 1-1 shows, select the riser pipe with 26.7mm OD, glue
the riser pipe to the bottom strainer and put it into the mineral tank, cut
off the exceeding tube out of tank top opening. Plug the riser tube in case
of mineral entering.
b. Fill the mineral to the tank, and the height is accordance with the
design code.
c. Remove the tap covering on the central tube and check if the riser
tube is on the central of tank.
d. Install the top distributor to the valve and insert the riser tube into
control valve and screw tight control valve.
Note:
● The length of riser tube should be neither higher 2mm nor lower 5mm
tank top opening height, and its top end should be rounded to avoid
damage of O-ring inside the valve.
● Avoid floccules substance together with resin to fill in the mineral tank.
● Avoid O-ring inside control valve falling out while rotating it on the tank.
②Install animated connector
As Figure1-2 shows, put the sealing ring into nut of animated
connector, and screw in water inlet.
③Install flow meter
As Figure1-2 shows, put the sealing ring into nut of flow meter, screw
in water outlet; insert the sensor into flow meter.
④Pipeline connection
a.As Figure1-3 shows, install a pressure gauge in water inlet.
b.Install valve A, B, C and D in the intermediate pipeline, inlet and outlet
valve D is a sampling valve. (Or adopt F70A/F70C bypass valve).
c.Install a check valve in water outlet.
d.Inlet pipeline should be in parallel with outlet pipeline. Support inlet and
outlet pipeline with fixed holder.

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
12
Note:
●If the water outlet or water tank is installed higher than control valve or
parallel interlock system with multi-outlets, a liquid level controller must
be installed in brine tank. Or else, the water in water outlet or water
tank will flow backwards into brine tank when backwash.
●If making a soldered copper installation, do all sweat soldering before
connecting pipes to the valve. Torch heat will damage plastic parts.
●When turning threaded pipe fittings onto plastic fitting, use care not to
cross thread or broken valve.
●If the valve belongs to time clock type, there are no step ②and ③

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
13
⑤Install drain pipeline
a.As the Figure 1-4 shows, slide the drain hose connector into drain
outlet.
b.Insert drain line flow control into drain outlet
c.Screw drain hose connector into drain outlet, and lock it.
d.Locate the drain hose well as the Figure1-4 show.
Note:
● Control valve should be higher than drain outlet, and be better not far
from the drain hose.
● Be sure not connect drain with sewer, and leave a certain space
between them, avoid wastewater be absorbing to the water treatment
equipment, such as showed in the Figure1-4.

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
14
⑥Connect brine tube
a.As Figure1-5 shows, slide 3/8″brine tube hose connector over end of
brine tube.
b.Insert tube bushing into the end of brine tube.
c.Insert the red brine line flow control into valve brine line
connector(Attention: cone side of control should face into valve)
d.Tighten brine draw hose connector onto brine line connector.
e.Connect the other end of brine tube with the brine tank. (The liquid
level controller and air-blocker should be installed in the brine tank.)
Remark: The brine tube and drain pipeline should not be bended or
plugged.

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
15
2. Basic Setting & Usage
2.1. The Function of PC Board
A. Time of day indicator
Light on,display the time of day.
“12:12” flash,remind you to reset the time of day if electrical service
interrupted 3 days more (If electrical service interrupted within 3 days,
it doesn’t need to reset the time. )
B. Button lock indicator
Light on, indicate the buttons are locked. At this moment, press any
single button will not work (No operation in one minute, will light on
and lock the buttons.)
Solution:Press and hold both and for 5 seconds until the
light off.
C. Program mode indicator
Light on,enter program display mode. Use or to view all
values.

MODEL 63504-F63C1/63604-F63C3/73504-F68C1/73604-F68C3
16
Flash, enter program set mode. Press or to adjust values.
D. Manu/Confirm button
Press , light on, enter program display mode and use or to
view all values.
In program display mode, press , flash, enter program set mode,
press or and adjust values.
Press after all program are set, and then the voice “Di” means all
setting are success and return program display mode.
E. Manual/Return button
Press in any status, it can proceed to next step.(Example: If outlet
water is unqualified, press in Service status, it will start
regeneration cycles instantly; Press while it is in Backwash
status, it will end backwash and go to Brine &Slow Rinse at once.)
Press in program display mode, and it will return in Service; Press
in program set mode, and it will return program display mode.
Press while adjusting the value, then it will return program display
mode directly without saving value.
F.Down▼ and Up▲
In program display mode, press ▲or▼ to view all values.
In program set mode, press ▲or▼ to adjust values.
Press and hold both ▲and ▼for 5 seconds to lift the Button Lock
status.
Other manuals for 63504
1
This manual suits for next models
15
Table of contents
Other Runxin Control Unit manuals

Runxin
Runxin 55504 User manual

Runxin
Runxin F104 A User manual

Runxin
Runxin 53515 User manual

Runxin
Runxin 51215 User manual

Runxin
Runxin F71B1 User manual

Runxin
Runxin 53520 User manual

Runxin
Runxin 73605 User manual

Runxin
Runxin 63504 User manual

Runxin
Runxin 17603 User manual

Runxin
Runxin 63518 User manual