17
ENGLISH
Installation/Service mode
• 'NONE' will be displayed for the menu that setting modes don't support. In some cases, the setting may not be
possible or it may not be applied though it is set on the unit.
• If communication initialization is needed after saving the setting, the system will reset automatically and
communication will be initialized.
NOTE
Main
menu
Sub-
menu Function SEG
number Default Range Unit
1
1
Wired remote
controller's option
function set /
Check 1
Cooling support Y / N 1 1 0-Both cooling & heating
1-Heating only -
Selecting the standard
temperature of cooling
and heating
2 0
0-Water Outlet temperature
1-Indoor temperature -
Selecting a standard
sensor of indoor
temperature
3 0
0-Temperature sensor of wired
remote controller 1-External
temperature sensor -
Selecting Master/Slave 4 0 0-Master, 1-Slave -
2
Wired remote
controller's option
function set /
Check 2
Allow self-test entering
Y / N 1 0
0-Entering is not allowable
1-Entering is allowable -
3Room temperature
compensation of
a wired remote
controller set /
check
Checking current sensor
temperature value 123 0 -9~40˚C(15.8~104˚F) -
4Setting compensation
temperature value 123 0 -9.9~9.9˚C(14.18~49.82˚F) 0.1˚C
(32.18˚F)
5
Checking the
number of
connected devices
The number of
connected devices 12 - 0~16 1
6Setting desired temperature unit (Available
only when the temperature display is °C) 1 1 0-1˚C(33.8˚F), 1-0.5˚C(32.9˚F),
2-0.1˚C(32.18˚F) -
0Reset to option setting default value of wired
remote controller 1 0 0-Disuse, 1-Reset -
2
1Checking Micom code of wired remote
controller 1~6 - Micom code -
2Checking version information of wired remote
controller 1~6 - Revision date -
3
1
Checking Hydro Unit main address 12 -
Main address(0~63)
Display the main address
currently applied
Setting Hydro Unit main address 34 -
Main address(0~63)
(When the address setting
is set as manual address, the
corresponding address will be
set after the outdoor unit is reset
and tracking is completed.)
2 Hydro Unit group(RMC) address set/check 12 - Group address (00H~2FH)
3 Wireless remote controller option set/check - - Option code
4 Hydro Unit option(K1~K24) set / check - - Option code
0 Process initialization 1 0 0-Disuse, 1-Reset -
DVM Hydro Unit_MWR-WW00_IM_EN_03647A(1).indd 17 2013-01-09 오후 2:48:43