S&P PCLPD100XHP User manual

WARNING
READ AND SAVE THESE INSTRUCTIONS
Installer: Leave this manual with the homeowner.
CAUTION
CLEANING & MAINTENANCE
OPERATION
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING:
Model: PCLPD100XHP
1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2. This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up.
3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
4. Please read specification label on product for further information and requirements.
For quiet and efficient operation, long life, and attractive appearance - lower or remove grille and vacuum interior of unit with the dust brush attachment.
The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noises, replace the motor with the
exact service motor. The impeller should also be replaced.
VENTILATION FAN
a). Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
b). Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to
prevent power from being switching on accidentally. When the service disconnecting means cannot be locked, securely
fasten a prominent warning device, such as a tag, to the service panel.
c). Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction codes and standards.
d). Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning
equipment to prevent backdrafting.
Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire
Protection Association (NFPA),and the American Society for Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
e). When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
f). Ducted fans must always be vented to the outdoors.
g). Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupter) - protected
branch circuit (ceiling installation only).
h). This unit must be grounded.
i). Not for Use in Kitchens.
j). To reduce risk of fire and to properly exhaust air, be sure to duct air outside – Do not vent exhaust air into spaces
within walls or ceilings or into attics,crawl spaces, or garages.
k). WARNING: To Reduce The Risk Of Fire Or Electric Shock, Do Not Use This Fan With Any Solid-State Speed Control
Device.
l). The fan must not be installed in a ceiling thermally insulated to a value greater than R40.
Cod: 0060303007-A
Humidity sensor knob
50 80 100
1 21 2
1 2
Switch position
Duct diameter
Airflow(CFM)
4" Oval
Low airflow knobControl box
To change the pre-selected airflow, adjust
the control switches as per the table above.
is the position of switch
See “Connect Wiring” for details.
The control box, located inside the fan housing, has three separate adjustments:
(1) The low airflow knob adjusts the lower airflow from 30 CFM up to the air flow rate of the
high fan speed determined by the toggle switch setting.
The low speed is de-activated when set between OFF-30 CFM (factory set to OFF).
(2) The humidity sensor knob set user-adjustable setpoint. The humidity sensor is de-acti-
vated when set between OFF-30% (factory set to 80% (Ambient temperature of 25℃)).
(3) The toggle switch will adjust the upper fan speed setting from 50 to 100 CFM. (factory
set to 100CFM).
S
Max.
30
CFM
OFF
50%
70%
H (%)
80
45 60
OFF
30

ASSEMBLY INSTRUCTIONS
OPERATION
PLAN THE INSTALLATION
1. Before installation, you need to know:
ST4.2*13mm
Screw A
Screw B
Hanger bar
ST4.2*25mm
13 3/8 in. (340mm)
ROOF CAP*
(with built-in
damper)
ROUND
DUCT* WALL CAP*
(with built-in
damper)
*Purchase
separately
POWER
CABLE*
INSULATION*
(Place around and
over Fan Housing.)
Seal gaps
around
Housing.
FAN
HOUSING
ROUND
ELBOW(S) *
Seal duct
joints with
tape.
Keep duct
runs short
Hole A
Hole B
Hole A
Hole B
Channel
When installing contractor packs (if available), make sure to install any optional
such as lighted grille plugs with the fan housing to ensure wiring is completed
properly. Module and grille plugs come packaged with the optional accessory and
must be installed with the fan housing.
To Turn Fan ON
Turn the switch I (according to the following “CONNECT ELECTRICAL WIRING” ) ON.
• Fan will run at the certified airflow rate if the switch II is ON.
• Fan will run at the user-adjustable airflow rate if the switch II is OFF.
To Use Fan Time Delay Airflow Rate Change
1. Turn the switch I ON.
2. Turn the switch II ON - fan will run at the certified airflow rate.
3. When the switch II is turned OFF, fan will continue to run at the certified airflow rate until the time delay has elapsed (the delay time is 20 mins), and
then will automatically change to the user-adjustable airflow rate.
To Turn Fan OFF
Turn the switch I OFF
Fan runs continuously at a low speed (adjustable by low airflow knob) and automatically boost up to high speed when either of these conditions is
detected: a) Humidity above a user-adjustable setpoint (30%-80% relative humidity). b) rapid increases in humidity. After delay timer (20 minutes)
returns fan to the default low speed. Humidity sensor description according to “HUMIDITY SENSOR OPERATION” and “SENSITIVITY ADJUSTMENT”.
HUMIDITY SENSOR OPERATION
The humidity-sensing fan uses a sophisticated humidity sensor that responds to: (a) rapid increases in humidity or (b) humidity above a user-adjustable
set-point (30%-80% relative humidity). Fan runs continuously at a pre-set lower level (set by Low airflow knob) and automatically boosts up to the
certified airflow rate when environmental conditions change. If the fan continuously responds to changing environmental conditions, “H” (means
“humidity”) adjustment may- be required.
SENSITIVITY ADJUSTMENT
The “H” has been factory set for most shower applications. However, if the fan is in a tub area or is being used for dampness control, the “H” may need
to be increased toward maximum. If the control is responding too often to changing environmental conditions, movement toward maximum, “H” may be
required.
To adjust the “H”:
1. Disconnect power at service entrance.
2. Through the grille, locate the slot marked “H”.
3. Carefully rotate the “H” adjustment toward maximum or minimum.
4. Turn on power and check operation by turning on the shower or other humidity source until the fan turns on.
5. Repeat above steps if necessary.
When the temperature changes, humidity sensor values will have deviation.
1. Do not install fan above or inside a 45-degree angle projected outwards from the cooking equipment element closest to the fan.
See instruction sheet for clarification.
2. Two ways to connect ductwork to a factory-shipped unit.
2

Slide one hanger bar into the channel on the housing and adjust as needed to fit
between framing. Hold housing in place so that the mounting flange contacts the
bottom of the joist, Screw the mounting flange to joist through the holes A and B.
Screw the hanger bar onto the other side of joist through its hole.
Screw hanger bar to housing with screw A.
3. Mount with mounting holes
ASSEMBLY INSTRUCTIONS
4. Mount to I-joist
Slide hanger bar into the channel on the housing and adjust as needed to fit I-joist.
Hold housing in place so that the mounting flange contacts the bottom of the joist.
Screw the mounting flange to the joist through holes A and B. Screw the hanger
bar onto the joist through its hole.
Screw the hanger bar to the housing with screw A.
6. INSTALL ROUND DUCTWORK
5. Wall installation
5a. When the product is installed on the wall, the adaptor shall be faced upward.
5b. Slide the hanger bar into the channel on the housing. Hold the housing in place
so that the mounting flange contacts the inner surface of the stud. Screw the
mounting flange to the stud stud through the holes A and B on the same side.
Screw the hanger bar onto the stud through its hole.
Screw the hanger bar to housing with screw A.
The minimum installation distance between studs is 13 3/8 in. (340mm)
Connect the round ductwork (not included) to the damper/duct connector, and run
the ductwork to a roof or wall cap (not included).
Using tape (not included), secure all the ductwork connections so that they are air
tight. The ducting from this fan to the outside of building has a strong effect on the
air flow, noise and energy use of the fan. Use the shortest, straightest duct routing
possible for best performance, and avoid installing the fan with smaller ducts than
recommended. Insulation around the ducts can reduce energy loss and inhibit mold
growth. Fans installed with existing ducts may not achieve their rated air flow.
Screw B
Screw A
Screw B
Screw B
Hanger
bar
Stud
Screw A
Screw B
Screw B
13 3/8 in. (340mm)
Screw A
2. Mount with mounting holes
Hold housing in place so that the mounting flange contacts the bottom of the joist,
Screw the mounting flange to the joists through the holes A and B.
Screw B Screw B
3

Run 120V AC house wiring to the location of the fan. Use only UL-approved connectors (not included) to attach the house wiring to the
wiring plate. Refer to the wiring diagram, and connect the wires as shown.
CONNECT ELECTRICAL WIRING
Install ceiling material to complete the ceiling construction. Then, cut around the fan housing.
To attach the grille assembly to the fan housing, pinch the grille springs on the sides of the grille
assembly, and position the grille into the housing with the grille springs in the appropriate slots.
Push the grille assembly towards the ceiling to secure.
INSTALL GRILLE
SERVICE PARTS
PART PART NAME Qty.
1
2
3
4
5
6
7
8
9
10
11
12
a
d
e
f
b
c
Housing
Screw
Screw
Screw
Screw
Screw
Screw
Blower
Motor
1
2
1
Power box 1
1
1
1
1
1
1
1
1
3
3
3
1
1
1
Grille Assembly (includes part 2)
Grille Spring
Hanger Bar
Blower Assembly includes part 3, 4, 5, 6, b, c.
*Replacement parts are shown for illustration purposes only and are not sold seperately
WARNING: Before replacing, be sure to turn off power at power source.
WARRANTY
1
2
3
4
a
b
f
e
d
8
9
10
11
12
6
7
c
5
Damper / Duct Connector
Wire Panel / Harness Assembly
Blower Wheel
Wiring plate
Motor plate
UNIT
BLACK (BLK)
SWITCH BOX
SWITCH I
POWER SUPPLY
120V AC
GROUND (GRD)
WHITE (WHT)
FAN
RECEPTACLE
WIRE
PANEL
SWITCH I
SWITCH II
SWITCH II
BROWN (BRN)
FAN
BRN
BLK
WHT
UNIT
SWITCH BOX
WHT
GRD GRD
LINE
IN
BLK
S&P USA Ventilation Systems, LLC. & S&P Canada Ventilation Products, Inc. warrants to the original end user of its products that our exhaust fans will be free from defects in
materials and workmanship for a period of Six (6) years from the date of original purchase. THERE ARE NO OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
BUT NOT LIMITED TO IMPLIED WARRANTIES OF SUITABILITY FOR A PARTICULAR PURPOSE.
During this six year period, S&P will, at its option, repair returned products or parts, or provide replacement products or parts, without charge, for any product or part which is
found to be defective under normal use.
This warranty does not cover normal maintenance and service or any parts that have been subject to misuse, negligence, accident, improper maintenance or repair, faulty
installation or installation contrary to recommended installation instructions.
S&P’s obligation to repair or replace, at S&P’s option, shall be the purchaser’s sole and exclusive remedy under this warranty. No labor or materials are covered by this
warranty. S&P shall not be liable for incidental damages arising out of or in connection with product use or performance.
This warranty gives you specific legal rights. You may also have other rights which vary from state to state.
To qualify for warranty service, you must notify S&P at the address or telephone number stated below, provide the model number and part identification, and describe the
nature of any defect in product or part. You may be required to ship a defective part to S&P. There will be no charge for shipping repaired or replacement parts from S&P to
you if your address is in the United States or Canada. At the time of requesting warranty service, you must present evidence of the original purchase date.
S&P USA Ventilation Systems, LLC.
6393 Powers Avenue Jacksonville, FL 32217
P. 904-731-4711
F. 800-961-7379
www.solerpalau-usa.com
S&P Canada Ventilation Products, Inc.
6710 Maritz Drive Unit #7 Mississauga, ON L5W 0A1 - Canada
T. 416-744-1217
F. 416-744-0887
www.solerpalaucanada.com
4
Table of contents
Other S&P Fan manuals

S&P
S&P RED User manual

S&P
S&P PCD110 User manual

S&P
S&P TD-1300/250 SILENT 3V User manual

S&P
S&P SILENT-300 DESIGN Manual

S&P
S&P DUOVENT COMPACT RV Series User manual

S&P
S&P PC50XP User manual

S&P
S&P Duovent Series User manual

S&P
S&P TH-MIXVENT Series User manual

S&P
S&P CADB-HE BASIC Series User manual

S&P
S&P VENT-160 N N8 User manual

S&P
S&P SILENTUB-100 Manual

S&P
S&P DECOR-200 S User manual

S&P
S&P ARTIC TOWER N User manual

S&P
S&P CK-35 User manual

S&P
S&P CK-25 Series User manual

S&P
S&P SILENT DUAL Series User manual

S&P
S&P ARTIC TOWER M Technical Document

S&P
S&P decor-100 DC User manual

S&P
S&P EBB-175 User manual

S&P
S&P TD-350/125 SILENT User manual