This manual describes how the ETHM-A module should be installed. For further information
related to the module, including its configuration and operation, please refer to the full version
of the manual, available at www.satel.eu.
1. ETHM-A module installation
The device is designed to be used only in the local area networks (LAN). It must
not be connected directly to the public computer network (MAN, WAN).
For establishing connection with public networks, use a router or xDSL modem.
Disconnect power before making any electrical connections.
The ETHM-A module should be installed indoors, in spaces with normal air humidity.
If the module is to comply with requirements of the EN50131 standard for Grade 2,
it must be installed in an additional enclosure that will enable it to meet requirements
of the tamper standards (e.g. in the SATEL OPU-3 or OPU-4 enclosure).
1.1 Preparing the cabling
To make electric connections between the module and other devices, use an unshielded
non-twisted cable. Do not lay the cables in immediate vicinity of the low-voltage electrical
network wires, especially those used for supplying the high-power equipment (such as
electric motors).
Connect the module to the Ethernet using a 100Base-TX standard compliant cable (identical
to that used for connecting computers to the network).
1.2 Installation of the module
The module enclosure base makes it possible to secure the module to the mounting surface
by using e.g. a cable tie or angle hooks.
Description of terminals
+12V –power input (12 VDC ±15%).
COM –common ground.
RING, TIP –terminals for connecting the control panel telephone communicator.
S1…S3 –1-Wire bus (1-Wire digital temperature sensors can be connected to the bus):
S1 –common ground,
S2 –data,
S3 –power supply.
I1…I8 –inputs. They can be programmed as digital (NC or NO type) or analog ones.
O1...O4 –programmable OC type outputs (disconnected from common ground / shorted
to common ground).
A RS B –terminals for future use (RS-485).
AC –input for supervision of AC voltage presence or for AC voltage frequency
measurement.