manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Siemens
  6. •
  7. Control Panel
  8. •
  9. Siemens SXL-EX Instruction Manual

Siemens SXL-EX Instruction Manual

Other manuals for SXL-EX

1

Other Siemens Control Panel manuals

Siemens SIMATIC HMI series User manual

Siemens

Siemens SIMATIC HMI series User manual

Siemens Synco RMZ792 User manual

Siemens

Siemens Synco RMZ792 User manual

Siemens SIMATIC WinCC flexible 2008 SP4 User guide

Siemens

Siemens SIMATIC WinCC flexible 2008 SP4 User guide

Siemens FC10 User manual

Siemens

Siemens FC10 User manual

Siemens FS720 Series User manual

Siemens

Siemens FS720 Series User manual

Siemens SIMATIC TD 200 User manual

Siemens

Siemens SIMATIC TD 200 User manual

Siemens SINAMICS S120 User manual

Siemens

Siemens SINAMICS S120 User manual

Siemens RRV912 User manual

Siemens

Siemens RRV912 User manual

Siemens SPC4000 Instruction sheet

Siemens

Siemens SPC4000 Instruction sheet

Siemens SIMATIC HMI KP300 Basic mono PN User manual

Siemens

Siemens SIMATIC HMI KP300 Basic mono PN User manual

Siemens MJ-X User manual

Siemens

Siemens MJ-X User manual

Siemens SPC 4300 User manual

Siemens

Siemens SPC 4300 User manual

Siemens FIREFINDER-XLS User manual

Siemens

Siemens FIREFINDER-XLS User manual

Siemens OP1S User manual

Siemens

Siemens OP1S User manual

Siemens OP5 Technical Document

Siemens

Siemens OP5 Technical Document

Siemens OP7 Technical Document

Siemens

Siemens OP7 Technical Document

Siemens SIMATIC HMI ITC1200 V3 PRO User manual

Siemens

Siemens SIMATIC HMI ITC1200 V3 PRO User manual

Siemens FireSeeker FS-250 Owner's manual

Siemens

Siemens FireSeeker FS-250 Owner's manual

Siemens FC721 User manual

Siemens

Siemens FC721 User manual

Siemens MKB-1 User manual

Siemens

Siemens MKB-1 User manual

Siemens SIMATIC S7-300 CPU Data: CPU 315-T-2 DP User manual

Siemens

Siemens SIMATIC S7-300 CPU Data: CPU 315-T-2 DP User manual

Siemens TRIANO 3 User manual

Siemens

Siemens TRIANO 3 User manual

Siemens SED2 Series User manual

Siemens

Siemens SED2 Series User manual

Siemens OP1S User manual

Siemens

Siemens OP1S User manual

Popular Control Panel manuals by other brands

GENEVO PRiMA 6 installation manual

GENEVO

GENEVO PRiMA 6 installation manual

NAPCO X 255 - Programming instructions

NAPCO

NAPCO X 255 - Programming instructions

Next Systems UNIR1 230 instruction manual

Next Systems

Next Systems UNIR1 230 instruction manual

HORNER HE-XPW1E0 user manual

HORNER

HORNER HE-XPW1E0 user manual

DSC CLASSIC PC1555 instruction manual

DSC

DSC CLASSIC PC1555 instruction manual

Bosch Solution 2000 installation guide

Bosch

Bosch Solution 2000 installation guide

VRinsight MS Panel user manual

VRinsight

VRinsight MS Panel user manual

Zeiss SYCOP 3 Quick reference guide

Zeiss

Zeiss SYCOP 3 Quick reference guide

HULTSTEINS ECOFRIDGE DISPLAY user manual

HULTSTEINS

HULTSTEINS ECOFRIDGE DISPLAY user manual

Elkron C420 Programming manual

Elkron

Elkron C420 Programming manual

GST GST200-2 Installation and operation manual

GST

GST GST200-2 Installation and operation manual

Efka Variocontrol V810 instruction manual

Efka

Efka Variocontrol V810 instruction manual

RDZ PC-HRX user manual

RDZ

RDZ PC-HRX user manual

STG-BEIKIRCH MZ3 operation instruction

STG-BEIKIRCH

STG-BEIKIRCH MZ3 operation instruction

AMX AutoPatch CP-15 instruction manual

AMX

AMX AutoPatch CP-15 instruction manual

Cebora 208-10 instruction manual

Cebora

Cebora 208-10 instruction manual

Satel CA-6 KLED-S user manual

Satel

Satel CA-6 KLED-S user manual

Evolution IQ plus 800 installation manual

Evolution

Evolution IQ plus 800 installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

P/N 315-095997-6
Siemens Building Technologies, Inc.
8 ernwood Road
lorham Park, New Jersey 07932
SXL-EX CONTROL PANEL
(For SXL-EX Firmware Revision 2.0 and higher)
Operation, Installation, and Maintenance Manual
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 CN
Fire Safety
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
i
Table of Contents
1 INTRODUCTION .....................................................................................................................1
Firmware Revisions ............................................................................................................1
Standard Components .......................................................................................................2
MAIN BOARD ................................................................................................................................2
DISPLAY ........................................................................................................................................ 2
FRONT PANEL FUNCTIONS .......................................................................................................... 3
2 INSTALLATION.........................................................................................................................5
Unpackin the Equipment ..................................................................................................5
Installin the Control Panel ................................................................................................ 6
3 OPERATING MODES ...............................................................................................................9
Alarm .................................................................................................................................... 9
Supervisory.......................................................................................................................... 9
Zone Trouble ........................................................................................................................ 9
SYSTEM TROUBLE (FAULT) CODES .......................................................................................... 9
Normal .................................................................................................................................. 9
Pro ram/Test ....................................................................................................................... 9
Respondin to a Fire Alarm ...............................................................................................9
HOW THE SYSTEM ANNUNCIATES FIRE ALARMS ................................................................... 9
TO ACKNOWLEDGE ALARMS ................................................................................................... 10
TO SILENCE THE NOTIFICATION APPLIANCE CIRCUITS ....................................................... 10
TO RESET .................................................................................................................................. 10
Respondin to a Supervisory Condition ........................................................................ 10
HOW THE SYSTEM ANNUNCIATES SUPERVISORIES ............................................................ 10
TO ACKNOWLEDGE SUPERVISORIES .................................................................................... 10
TO RESET .................................................................................................................................. 10
Respondin to a Trouble Condition ................................................................................10
HOW THE SYSTEM ANNUNCIATES TROUBLES ...................................................................... 10
TO ACKNOWLEDGE TROUBLES .............................................................................................. 11
TO RESET .................................................................................................................................. 11
System Features ............................................................................................................... 11
INITIATING DEVICE CIRCUIT (ZONE) TYPES .......................................................................... 11
ALARM VERIFICATION ..............................................................................................................11
GENERIC ZONE ......................................................................................................................... 12
NOTIFICATION APPLIANCE CIRCUIT (NAC OR BELL CIRCUIT TYPE) ................................... 12
Simple Zone Code ................................................................................................................... 12
SET OUTPUT CONTROL MATRIX ............................................................................................. 13
BYPASS ZONES AND OUTPUTS ............................................................................................... 13
SET SYSTEM TIMING ................................................................................................................ 13
ALARM VERIFICATION RETARD/RESET TIMER SELECTION ................................................. 13
SET SYSTEM PASSWORD ........................................................................................................ 14
SET AC FAIL SIGNAL DELAY ..................................................................................................... 14
ENABLE SYSTEM OPTION CARDS ........................................................................................... 14
ONE PERSON SYSTEM TEST ................................................................................................... 14
LAST EVENT RECORD .............................................................................................................. 15
Pro ram Mode ................................................................................................................... 15
PROGRAM LEVEL DESCRIPTIONS ............................................................................................ 15
Section Page
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
ii
List of Illustrations
1. SXL-EX Control Panel ............................................................................................................ 1
2. SXL-EX Front Panel ............................................................................................................... 2
3. SXL-EX Enclosure.................................................................................................................. 5
4. Transformer ounting ............................................................................................................ 6
5. ounting the Standoffs and Spacers ...................................................................................... 6
6. ounting the SXL-X ain Board ........................................................................................... 7
7. Line Graph of Alarm Verification .......................................................................................... 12
8. SXL-EX Connection Diagram ..............................................................................................31
9. SXL-EX-INT Connection Diagram ....................................................................................... 32
Page
Figure
1. Program ode Levels ..........................................................................................................23
2. Test ode Levels ................................................................................................................. 24
3. System Fault Troubleshooting .............................................................................................. 25
4. Electrical Requirements for Battery Calculations and Power anagement .......................... 26
5. Field Wiring Checkout Procedure......................................................................................... 27
6. Default Configurations ......................................................................................................... 28
7. Programming Sheet ............................................................................................................. 29
List of Tables
ENABLING THE PROGRAM MODE ..............................................................................................16
Enter Password ......................................................................................................................... 16
Reading the SXL-EX Display .....................................................................................................16
To Select Program Mode ..........................................................................................................16
To E it Program Mode .............................................................................................................. 16
Test Mode .......................................................................................................................... 20
Reading the SXL-EX Display .................................................................................................... 20
TEST LEVEL DESCRIPTIONS ..................................................................................................... 20
ENABLING THE TEST MODE ...................................................................................................... 20
Enter Password ........................................................................................................................ 20
To Select Test Mode ................................................................................................................ 20
To E it Test Mode .................................................................................................................... 20
4 CHECKOUT PROCEDURE ....................................................................................................25
Maintenance ...................................................................................................................... 25
PERIODIC INSPECTION AND TESTING .................................................................................... 25
SERVICING ................................................................................................................................. 25
FIELD WIRING CHECKOUT PROCEDURE ............................................................................... 27
SXL-EX CONNECTION DIAGRAM ............................................................................................31
SXL-EX-INT CONNECTION DIAGRAM .....................................................................................32
Table of Contents (Cont.)
Section Page
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
1
SXL-EX Operation, Installation, and Maintenance Manual
INTRODUCTION
The SIEMENS SXL-EX is a microprocessor
based fire and life safety system with four
conventional initiating device circuits (up to 8
with the addition of the optional SZE- X or
SZE-8AX zone expander). All basic alarm and
trouble functions are annunciated and con-
trolled from the SXL-EX front panel (See
Figure 1) which consists of:
 Seven segment numeric display
 Four user-control switches
 Red and yellow LEDs for each of the
eight zones
 Six system status LEDs
Key features of the SXL-EX are:
 2 Class B (Style Y) +2 VDC notification
appliance circuits (NACs) rated at 1.5
amps each.
 Silenceable/Non-Silenceable notification
appliance circuits (NACs).
 Fully supervised initiating and notification
circuits.
 Initiating and notification circuits power
limited.
 Class B (Style B) 2 wire initiating
device circuits that are expandable to 8
circuits.
 Supports up to 30 non-shorting devices
per initiating device circuit.
 Selectable alarm verification option for
each initiating device circuit.
 One person system test with or without
audible confirmation.
 User-alterable factory installed configura-
tion.
 One Form C system Alarm relay.
 One Form C system Trouble relay.
 Seven segment numeric status display.
 Six LED status indicators.
 Easy-to-use front panel function keys.
1
 Standard 120 VAC operation with the
SXL-EX or 220/2 0 VAC operation with
the SXL-EX-INT.
 Alarm Coding (March Time, Temporal, or
Simplified Zone Code) and Non-
Silenceable output option.
 Easy-to-use built-in diagnostics.
 2 hour re-sound for Alarm and Trouble
conditions that are not restored to normal
after being acknowledged.
 Optional SZE-8AX module converts the
system to four Class A (Style D) Initiating
Device Circuits and two Class A (Style Z)
Notification Appliance Circuits and also
provides four additional Class A (Style D)
Initiating Device Circuits.
 Optional SRC-8 module provides eight
programmable Form C relays.
 Optional LED-3/ module provides
remote annunciation for eight zones with
16 LEDs. Up to two may be used.
 Optional SLT-1 module provides Leased
Line/Municipal Tie connection.
FIRMWARE REVISIONS
This manual references SXL-EX firmware 2.0.
Figure 1
SXL-EX Control Panel
SXL-EX
SIEMENS
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
2
SXL-EX Operation, Installation, and Maintenance Manual
Standard Components
A standard four zone SXL-EX has one
modulethe main board. An expander board
is added to provide four additional zones,
when needed.
MAIN BOARD
The Main board of the SXL-EX or SXL-EX-INT
contains the intelligence for the system and
performs all of the input/output processing as
listed below:
Two supervised Notification Appliance
Circuits provide 2 VDC at 1.5 amps.
Each circuit operates Class B (Style Y)
and can be independently programmed
to operate a number of different ways
(Non-Coded, March Time, Temporal, or
Simple Zone Code).
Two Form C relays rated at 30 VDC at 1
amp resistive, 30 VAC at 500mA resis-
tive. These relays are for Alarm and
Trouble operation.
 A dual mode battery charger that
provides float and constant current
Figure 2
SXL-EX Front Panel
modes of charging sealed lead acid
batteries (15 Amp-Hour maximum).
Nonvolatile storage of system con-
figuration so that configuration remains
intact during loss of system power.
Four supervised power limiting
Initiating Device Circuits Each circuit
operates Class B (Style B) and can be
independently programmed to operate as
an Automatic Alarm input, a Verified
Alarm input, a Supervisory input, or a
Generic input. Each initiating device
circuit can use an unlimited number of
manual shorting-type devices.
CPU Fail LED
DISPLAY
The SXL-EX display, shown in Figure 2,
provides the user with the necessary inter-
face to operate the fire detection system in
Normal, Test, and Program modes.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
3
SXL-EX Operation, Installation, and Maintenance Manual
CODE DESCRIPTION
1 AC power fail
2 NAC 1 trouble
3 NAC 2 trouble
4 Ground fault
5 Municipal tie fault
6 Battery fault
7 System Configuration fault
8 Auxiliary port fault
9 Outputs bypassed
0 Hardware failure
E Enter password
A Password accepted
F Password fail
P Program mode
tTest mode
L Leave Program/Test mode
The Function Keys
The ACK key is used to acknowledge alarms,
troubles, and supervisory conditions. In general
the LEDs change rom pulsing to steady to
indicate that the condition was acknowledged.
The SILENCE key silences the noti ication
appliance circuits that are con igured as
silenceable. Pressing the SILENCE key a
second time causes the NACs to re-sound.
The RESET key resets the SXL and all o the
smoke detectors.
The DRILL key activates all o the noti ication
appliance circuits.
The yellow zone status LEDs indicate
a trouble or supervisory condition existing on a
particular input. Pulsing indicates the condition
was not acknowledged; on steady indicates it
was acknowledged.
The red zone status LEDs provide an
indication o the status o a particular zone.
Pulsing indicates an alarm condition in that
zone. When the alarm is acknowledged, the LED
remains on steady until the panel is reset.
FRONT PANEL FUNCTIONS
The front panel of the SXL-EX is comprised of
a seven segment display, function keys, and
LEDs. Their functions are described below
(Refer to Figure 2):
The LEDs
The green Power LED remains on steady when
AC power is connected and pulses when the unit
is operating rom batteries.
The red Alar LED pulses when an alarm is
detected until it is acknowledged. Then it remains
on steady until the alarm condition is reset.
The yellow Supervisory LED pulses when a
supervisory condition is detected until it is ac-
knowledged. Then it remains on steady until the
supervisory condition is reset. Note that the
pulsing rates o the trouble and supervisory
conditions are di erent.
The yellow Trouble LED pulses when a trouble
condition is detected until it is acknowledged.
Then it remains on steady until the trouble condi-
tion is reset. Note that the pulsing rates o the
trouble and supervisory conditions are di erent.
The yellow Bypass/Alar Silence LED is on
steady when a zone in the system is bypassed
and it pulses when a noti ication circuit is silenced.
When an initiating device zone is bypassed, the
appropriate yellow zone trouble LED is on.
The Test/Progra LED is on steady when the
Test mode is selected and it pulses when the
Program mode is selected.
The Sounder
CONDITION RATE OF PULSATION
SYSTEM ALARM Sounds steady
TROUBLE Pulses at 50% duty cycle
SUPERVISORY Pulses at 25% duty cycle
CPU FAILURE Pulses once every 2 seconds
The seven seg ent display indicates
the various system troubles and the programming
and test modes. The numbers and symbols that
appear on this display are described in the
ollowing chart.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
4
SXL-EX Operation, Installation, and Maintenance Manual
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
5
SXL-EX Operation, Installation, and Maintenance Manual
INSTALLATION
Unpacking the Eq ipment
The SXL-EX is shipped in two cartons;
one of the cartons contains the SXL-EX
enclosure The other carton contains the
SXL-EX electronics, the transformer, and
the mounting hardware Follow the proce-
dure below to unpack the SXL-EX equipment.
1. Locate and open the shipping carton
containing the EN-SX enclosure. Remove
the packing material and inspect the
enclosure for damage.
Note: If the enclosure is damaged,
contact the shipping carrier
immediately to report the damage.
2. Locate and open the shipping carton
containing the SXL-EX electronics.
2
Figure 3
SXL-EX Enclosure
Remove the packing material, and inspect
the electronics for damage.
Note: If the PC board is damaged,
contact the shipping carrier
immediately to report the damage.
3. Check that the following items are inside
the carton:
 Mounting hardware for the SXL-X Main
Board and transformer
 Main board
 Power transformer
Note: If any of the above items are
missing, contact the distributor
from whom you ordered the unit.
SXL-EX
SIEMENS
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
6
SXL-EX Operation, Installation, and Maintenance Manual
Installing the Control Panel
Remove all system power before
installation, first battery and then AC
(To power up, connect the
AC first, then the battery.)
All wiring must comply with
national and local codes.
Install the SXL-EX control panel by following
the steps listed below.
1 Install the enclosure Fasten the
enclosure securely to a clean, dry, shock
and vibration free surface. Consider the
following placement factors when
mounting the enclosure: height as it
relates to the front panel, weight and size
of the enclosure, and local mounting
codes. Refer to the EN-SX Installation
and Power Limited Wiring Instructions,
P/N 315-09599 , for further information.
Figure
Transformer Mounting
2 Fasten the power transformer to the
inside of the enclosure Mount the
transformer on the four studs in the upper
left-hand corner of the EN-SX enclosure,
as shown in Figure , using the hardware
provided.
3 Pull all field wiring into the enclosure
Dress the wiring to the approximate
location to which it will go on the SXL-X
Main board.
4 Install the PC Board mounting metal
hex standoffs and plastic spacers
Mount the six PC Board metal hex stand-
offs and two plastic round spacers, as
shown in Figure 5.
5 Install the Main board Mount the Main
board to the standoffs in the center of the
enclosure (Refer to Figure 6).
a. Fasten two of the six screws provided
in the PC board mounting hardware in
the two bottom metal hex standoffs
Figure 5
Mounting the Standoffs and Spacers
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
7
SXL-EX Operation, Installation, and Maintenance Manual
labeled A in Figure 6, leaving a 1/4 inch
gap between the standoff and the
head of the screw.
b. Place the slots on the bottom of the
SXL-X Main board on the two screws.
c. Secure the board in place by fasten-
ing the remaining four screws labeled
B to the metal hex standoffs.
d. Tighten the bottom two screws.
6 Optional modules Refer to the specific
optional module Installation Instruction
sheet for the appropriate installation.
7 Before connecting any wire to its
screw terminal, refer to the Checkout
Procedure (page 27) and the SXL-EX
Connection Diagram (Figure 8, page 31)
or the SXL-EX-INT Connection
Diagram (Figure 9, page 32), as
applicable. Prior to connecting wiring to
the Main board, ensure compliance to
maximum resistance in accordance with
the Field Wiring Checkout procedure,
page 27. Make sure that all power is off
before connecting leads.
8 Install power wiring to the SXL-EX The
SXL-EX is designed to operate from a
120 VAC, 60 Hz power source.
Use a dedicated circuitbreaker. Wire in
accordance with local codes and/or
Article 760 of the National Electrical
Code, NFPA 72, latest edition.
a. Run Earth Ground from a suitable
source to the Earth Ground stud on
the chassis (See Figure 6 for the
location of the stud). Secure in place
using the two #8 nuts provided. Check
local requirements. Conduit is not an
acceptable ground
b. Connect the 120 VAC source and the
BLACK transformer wire leads
to TB1.
Figure 6
Mounting the SXL-X Main Board
c. Connect the BROWN transformer
wire leads to TB6.
9. Install power wiring to the SXL-EX-INT
The SXL-EX-INT is designed to operate
from a 220/2 0 VAC, 50/60 Hz power
source. See the SXL-EX 220/2 0 VAC
Transformer Wiring Installation
Instructions, P/N 315-0962 6 and the
SXL-EX-INT Connection Diagram (Figure
9, page 32).
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com