Step 4 Controlling the motor speed with
a potentiometer
A potentiometer can be used to control the running
speed of the inverter. This is achieved by varying the
voltage applied to the analogue input. Connect the
potentiometer to the control terminals shown below.
Starting and stopping of the motor may be achieved
by connecting a switch to the digital input terminals
shown.
P006 Set to 1 to allow analogue input
P007 Set to 0 to enable control via digital input
The following parameter settings are required
To get the best performance from your drive,
you should enter information from your motor
ratings plate into certain parameters. The
following diagram indicates the location of the
information and the parameters which should
be entered.
Telling the drive about your motor
Commissioning MICROMASTER Basic
Display parameters Basic parameters
Select display
via P001
0 = output frequency
1 = frequency setpoint
2 = motor current
5 = Motor speed (RPM)
Display frequency,
motor current and motor
speed:
P001
Ramp-up time
P002 0-650 sec.
Ramp-down time
P003 0-650 sec.
0 = digital
1 = analog
2 = fixed frequency
Frequency setpoint
P006
Keypad control
P007
0 = disable 1 = enable
Parameter protection
P009
0 = only P001-P009 can be
altered
2, 3 = all can be altered.
Motor parameters Frequently used parameters
Nominal rating plate
frequency for motor
P081 0-400Hz
Nominal rating plate speed
for motor
P082 0-9999 RPM
Nominal rating plate
current for motor
P083 0.1-99.9A
Nominal rating plate
voltage for motor
P084 0-1000V
Nominal rating plate power
for motor
P085 0-100kW
Motor current limit
P086 0-250%
Minimum motor frequency
P012
0-400Hz.
Maximum motor frequency
P013
0-400Hz
Automatic restart after mains
failure
P015
0 = disable 1 = enable
Start on the fly
P016
0 = disable 2 = enable
Analogue input
P023
0 = 0-10V 1 = 2-10V
Fixed frequency operation
P041-048
0-400Hz
Input terminal function
P051-053
Selection relay output
P061
DC injection braking
P073 0-150%
Pulse frequency
P076
See Operator Manual
Control mode
P077
See Operator Manual
Continuous boost
P078
0-250%
See Operator Manual for other
parameters
Hints and Tips
The direction of rotation of the motor can be
reversed during commissioning by changing
over two of the output connections on the
inverter, or by pressing the Forward/Reverse
button.
Parameters P000 to P009 can always be read
or set. Access to all other parameters is
controlled by the contents of P009. The
factory default value is '0' which only allows
access to P000 to P009. Changing its value
to '3' allows all parameters to be accessed
permanently. See Operator Manual for the
function of other values of P009.
In case there are problems with the parameter
settings and wish to start again, change P944
to '1'. This will perform a reset to the default
values.
The value displayed in P000 is the output
frequency of the inverter, this is the default
setting but it can be changed by altering the
value in P001. For example, changing P001
to a value of '5' will cause the inverter to
display the RPM of the motor in P000. See
the Operator Manual for other settings of
P001.
The default value (0) of parameter P006
ensures that the drive runs at the frequency
set in P005. In order to control the output
frequency by an analogue input signal, the
value of P006 should be set to '1'. For other
methods of control using P006, see the
Operator Manual.
An F002 fault is often caused by either too
short a ramp up time or too much voltage
boost. An increase in the value in P002 will
increase the ramp time. Alternatively lower
the values in P078 and P079 to reduce the
voltage boost. Please note that if P078 falls
below '100' (default value) then the motor
may under-perform at low frequencies.
An F001 fault is often caused by attempting to
stop the motor too quickly increasing the
value in P003 (ramp-down time) will reduce
this possibility.
If the display flashes during operation, the
drive is registering a warning. Check P931
for the cause.