Siemens 5WG1 372-5AR01 User manual

instabus EIB
Technical Product Information
September 2001
Time Switch 4 Channel REG 372 5WG1 372-5AR01
Siemens AG REG 372, 4 pages Technical Manual
Product and Applications Description
The time switch REG 372 is a DIN-rail mounted
device laterally attached to the bus coupling unit
REG 110 (to be ordered separately, order number:
5WG1 110-5AR01). During this it occupies 4 address-
ing locations of the bus coupling unit. Via the four
channels time controlled applications such as illumina-
tion, heating or shutters can be switched on or off. It
can be used as daily, weekly or yearly clock controller.
By connecting an aerial FA and a power unit NT DCF77
the clock controller itself automatically sets the up-to-
date daytime and date (MEZ).
With a reading button the set switching times, date
referenced inputs and 1x-switching commands can be
trialled.
The bus coupling unit REG 110, the power unit
NT DCF77 and the radio aerial FA are not contained in
the volume of delivery and must be ordered separately
Operational specifications
• 4 channels
• response margin
• radio interface DCF 77
• date referenced input
• single days and date ranges
• free weekday and channel block establishment
• yearly, weekly and daily program
• 322 memory locations
• no double tasks of the push-buttons
• automatic summer-/winter time conversion
• possibility of setting the program: every minute
• shortest switching time 1 minute
• rapid impulse
• preliminary selection (override)
• switching condition permanent ON, permanent OFF
Application Programs
11 S4 Time switch 4 Channel 241A01
• 4 inputs for time switch
• control start event
• control finishing event
• delayed on-switching
• delayed off-switching
• channel connection (AND/OR)
Note
Before programming the device has to be supplied with
voltage for at least 6 minutes (charge the accumulator).
Example of Operation
PEI bus
coupling
unit
REG 110
FA
aerial DCF77
Frankfurt / Main
signal
- +- +
time clock controller REG 372
instabus EIB
power unit
NT
DCF 77
Installation Instructions
• The device may be used for permanent interior
installations in dry locations within high voltage
distribution board or small casings.
VWARNING
• The device may be built into distribution boards
(230/400V) together only with appropriate VDE-
devices and must be mounted and commissioned by
an authorised electrician.
• Free DIN rail areas must be covered with covers,
order no. 5WG1 192-8AA01.
• The prevailing safety rules must be heeded.
• The device must not be opened. A device suspected
faulty should be returned to the local Siemens office.
Automation and Drives Group
Electrical Installation Technology Siemens AG 2001 Update: http://www.siemens.de/installationstechnik
P.O.Box 10 09 53, D-93009 Regensburg Subject to change without prior notice
2.18.2.2/1

instabus EIB
Technical Product Information
September 2001
Time Switch 4 Channel REG 372 5WG1 372-5AR01
Technical Specifications
Power supply
Via bus line
Control elements
Keyboard for setting respectively operating the time
switch
Display elements
LCD display unit
Connections
• 10 pin bar (PEI):
for connection with the bus coupling unit
• aerial FA: length of insulation removal approx. 5 mm
- 0,5 ... 2,5 mm² single core or flexible conductor,
8 mm ultrasonically compacted
- 0,5 ... 2,5 mm² flexible conductor with terminal pin,
crimped on gas tight
- 0,5 ... 1,5 mm² flexible conductor with connector
sleeve
- 1,0 and 1,5 mm² plain flexible conductor
Physical specifications
• housing: plastic
• dimensions (W x H x D): 45 x 107 x 68 mm
• mounting depth: 68 mm
• distributor section: 46 x 108 mm
• weight: approx. 175 g
• installation: rapid mounting on
DIN EN 50022-35 x 7,5 rail
Clock controller
• response accuracy: usually ±1 s/day at +20°C
• response margin: 72 h at +20°C
• duration of charge: 70 h accumulator
• shortest switching time: 1 s
• possibility of setting the program: every minute
• memory locations: 322
• control selection: yes
• manual switch: automatic operation/preliminary con-
trol selection FIX ON / FIX OFF
• switching condition display: yes
• block establishment: free weekdays and channel
block establishment
• summer- / wintertime conversion: automatically
• holiday program: yes
Electrical safety
• fouling class (according to IEC 664-1): 2
• protection (according to EN 60529): IP 20
• protection class (according to IEC 1140): II
• overvoltage class (according to IEC 664-1): III
• bus: safety extra low voltage SELV DC 24 V
• device complies with
EN 50 090-2-2 and IEC 664-1: 1992
Electromagnetic compatibility
complies with
EN 50081-1, EN 50082-2 and EN 50090-2-2
Environmental specifications
• climatic conditions: EN 50090-2-2
• ambient temperature operating: - 5 ... + 45 °C
• ambient temperature non-op.: - 25 ... + 70 °C
• relative humidity (non-condensing): 5 % to 93 %
Certification
EIB certificate
CE norm
complies with the EMC regulations (residential and
functional buildings), and low voltage regulations
Location and Function of the Display and
Operator Elements
Mo Tu We Th Fr Sa Su
Reset S/W
Prior. Year
CL R
1x N
1234
SMonthh-m-
h+ m+Day
I/O I/O I/O I/O
1
2
3
4
A1
A2
A3
A4
Figure 1: Location of the display and operator elements
A1 terminal connection blocks aerial FA
A2 Keyboard for setting respectively operating the
clock controller
A3 LCD display unit
A4 Physical external interface (PEI) for connection
with the bus coupling unit REG
Technical Manual REG 372, 4 pages Siemens AG
Automation and Drives Group
Update: http://www.siemens.de/installationstechnik Siemens AG 2001 Electrical Installation Technology
Subject to change without prior notice P.O.Box 10 09 53, D-93009 Regensburg
2.18.2.2/2

instabus EIB
Technical Product Information
September 2001
Time Switch 4 Channel REG 372 5WG1 372-5AR01
Mounting and Wiring
General description
The N-system DIN-rail device can be installed to N-
system distribution boards, surface or flush mounted, or
to any available DIN-rail EN 50022-35 x 7,5.
During this the electric connection between the clock
controller and the bus coupling unit is established via
the lateral physical external interface (PEI).
The bus coupling unit is not contained in the volume of
delivery and must be ordered separately.
Mounting DIN-rail devices (Figure 2)
- Slide the device (B1) onto the DIN-rail (B2) and
- swivel back the device until the slide clicks into place
audibly.
- Remove the protection film of the adhesive tape (B4),
slip the device to the right and connect it with the bus
coupling unit (B3)
B1
B2
B1
B3
B4
Figure 2: Mounting of the DIN-rail device
Dismounting DIN-rail devices (Figure 3)
- Slip the bus coupling unit (C1) to the left until the
plug-in connection to the bus terminal unit (C2) is ex-
posed,
- press down the slide (C4) with a screw-driver and,
click it into place by a slight pressure and
- swivel the device (C1) from the DIN-rail (C3).
C2
C1 C1
C3
C4
Figure 3: Dismounting the DIN-rail device
Connecting terminal line aerial FA (Figure 4)
- Remove approx. 5mm of the insulation of the conduc-
tor (D1.1), plug it into the connection blocks (D1) and
tighten the screws (D1.2)
Connections
• aerial FA: strip insulation for 5mm
permissible conductor types/cross sections:
- 0,5 ... 2,5 mm² single core or flexible conductor,
8 mm ultrasonically compacted
- 0,5 ... 2,5 mm² flexible conductor with terminal pin,
crimped on gas tight
- 0,5 ... 1,5 mm² flexible conductor with connector
sleeve
- 1,0 and 1,5 mm² plain flexible conductor
Disconnecting terminal line aerial FA (figure 3)
- Detach the screws (E1.2) and plug the conductor
(E1.1) out of the connection block (E1).
D1.1 D1.2
ca. 5 mm
D1 E1.1E1.2
E1
Figure 4: connecting/disconnecting
terminal lines aerial FA
Dimension Diagram
Dimensions in mm
.
9,8
82
45
38
68
b
b = 6 SU
1 Spacer unit (SU) = 18mm
Siemens AG REG 372, 4 pages Technical Manual
Automation and Drives Group
Electrical Installation Technology Siemens AG 2001 Update: http://www.siemens.de/installationstechnik
P.O.Box 10 09 53, D-93009 Regensburg Subject to change without prior notice
2.18.2.2/3

instabus EIB
Technical Product Information
September 2001
Time Switch 4 Channel REG 372 5WG1 372-5AR01
Notes
Technical Manual REG 372, 4 pages Siemens AG
Automation and Drives Group
Update: http://www.siemens.de/installationstechnik Siemens AG 2001 Electrical Installation Technology
Subject to change without prior notice P.O.Box 10 09 53, D-93009 Regensburg
2.18.2.2/4
Table of contents
Other Siemens Timer manuals

Siemens
Siemens 7LF4 511-0 User manual

Siemens
Siemens 1. B. S. T. User manual

Siemens
Siemens LOGO! 8 User manual

Siemens
Siemens 7LF4 531-0 User manual

Siemens
Siemens RWB27Si User manual

Siemens
Siemens RWB1007 User manual

Siemens
Siemens RWB1007 User manual

Siemens
Siemens 7LF5 3001 User manual

Siemens
Siemens RWB30 User manual

Siemens
Siemens BUD 5241 User manual