
Holding time (H) – lasts for
seconds
• At end of H, if internal pressure
transducer is above psi ( bar)
and external pressure transducer has
reached psi ( bar), pump begins
vent cycle.
• At end of H, if internal pressure
transducer is below psi ( bar)
or both internal pressure transducer is
below psi ( bar) and external
pressure transducer has not reached
psi ( bar), an H will appear on
display. Pump turns on again and pumps
until internal pressure transducer has
reached psi ( bar). When
internal pressure transducer is above
psi ( bar) and external
pressure transducer has reached
psi ( bar), vent cycle
takes place.
• If at end of H internal pressure
transducer is above psi ( bar)
but external pressure transducer has not
reached psi ( bar), pump turns
on for seconds and then stops and waits
until external pressure transducer reaches
psi ( bar). H appears on display.
When internal pressure transducer is
above psi ( bar) and external
pressure transducer has reached
psi ( bar) vent cycle takes place.
Holding time (H)
• Holding time H remains until
internal pressure transducer is above
psi ( bar) and external
pressure transducer has reached
psi ( bar), and then
vent cycle takes place. If both
pressure transducers do not reach
preset settings within allotted pumping
time of minutes, alarm will occur.
If internal pressure transducer drops
below psi ( bar) during H,
it repumps until internal pressure
transducer reaches psi ( bar).
Possible faults
• E Fault – failure to build pressure at
pump within allotted minutes of
pumping time.
• E Fault – failure to build pressure at
end of supply line.
• E Fault – failure to vent at pump. Internal
pressure transducer has seconds to
drop below psi ( bar) when
motor reverses to locate vent position.
• E Fault – failure to vent at end of supply
line. External pressure transducer has to
drop below psi ( bar) before next
lube cycle takes place.
Vent cycle
• After pump completes preset hold time
and pump maintains specified pressure,
controller initiates vent cycle. Vent cycle
lasts for ten seconds.
• Motor turns counter-clockwise to engage
and open internal vent valve.
Displays rotating segment is turning
counter-clockwise.
• Motor stops in position to hold
vent valve open. Hr will be displayed for
remainder of seconds.
• Cam () († Fig. , page ) engages vent
lever () depressing vent valve plunger ()
(† Fig. , page ).This opens valve
passage of supply line to reservoir.
• Lubricant is flowing back to reservoir
venting pressure from system. Valve
stays open during pause time.
Fill reservoir with
grease
Use grease fitting () († Fig. , page )
to fill reservoir. Filling reservoir for first time
is critical to proper pump operation. It is
recommended to run motor by initiating
lubrication cycle during first reservoir fill.
Stirring paddle () of running motor will
help to evenly spread grease, minimizing
air pockets.
Stirring paddle
Stirring paddle () († Fig. , page )
is attached to motor and rotates during
lubrication cycle. Paddle works grease in
reservoir to make it more pumpable and at
same time pushes grease down into housing
and pumping elements to prevent cavitation.
Low–level control
Pump model PS is equipped with
low–level grease control as standard feature.