LEC-GMJ2#-TF222-184EN
Page 1 of 2
Instruction Manual
Gateway (GW) unit
CC-Link compatible
Series LEC-GMJ2*
The intended use of the gateway unit is to connect to step motor
controllers which control the movement of an electric actuator, while
connected to the CC-Link network.
1 Safety Instructions
These safety instructions are intended to prevent hazardous situations
and/or equipment damage. These instructions indicate the level of
potential hazard with the labels of “Caution,” “Warning” or “Danger.”
They are all important notes for safety and must be followed in addition
to International Standards (ISO/IEC)
*1)
, and other safety regulations.
IEC 60204-1: Safety of machinery - Electrical equipment of machines.
(Part 1: General requirements)
ISO 10218-1: Robots and robotic devices - Safety requirements for
industrial robots - Part 1: Robots.
•Refer to product catalogue, Operation Manual and Handling
Precautions for SMC Products for additional information.
•Keep this manual in a safe place for future reference.
Caution
Caution indicates a hazard with a low level of risk which, if
not avoided, could result in minor or moderate injury.
Warning
Warning indicates a hazard with a medium level of risk
which, if not avoided, could result in death or serious injury.
Danger
Danger indicates a hazard with a high level of risk which, if
not avoided, will result in death or serious injury.
Warning
•Always ensure compliance with relevant safety laws and
standards.
•All work must be carried out in a safe manner by a qualified person in
compliance with applicable national regulations.
Refer to the operation manual or catalogue on the SMC website (URL:
https://www.smcworld.com) for further Safety Instructions.
2 Specifications
2.1 General specifications
Current consumption 200 mA max. (with no teaching box)
Electric actuator controller
Operating
0°C to 40°C (no freezing)
2
Insulation resistance 50 MΩ(500 VDC)
Weight 200 g (Direct mounting type)
0 g (DIN rail mounting type)
2 Specifications (continued)
2.2 CC-Link specifications
Item Specifications
Occupied number of stations
4 stations extended cyclic 8 times
(Input 896 points 108 word /
Communication speed 156 kbps / 625 kbps / 2.5 Mbps /
Frame synchronous communication
16
12
5
Applicable communication
CC-Link cable
Maximum
cable length
Comms.
156k 625k 2.5M 5M 10M
Total cable
1200 900 400 160 100
2.3 Controller I/F communication specifications
Serial
RS485 (Modbus protocol compatible)
Communication
115.2 kbps or 230.4 kbps (select 115.2 kbps
when the teaching box is connected
Cable length
The cable for the teaching box (3 m) and the
electric actuator controller (3 m x 12) = 39 m.
This is the maximum allowable cable length.
Warning
Special products (-X) might have specifications different from those
shown in this section. Contact SMC for specific drawings.
3 Name and function of parts
2 STATION NO. address
Switch to set address X1 and X10.
3 B RATE communication
Switch to set the communication
speed to the controller IF
4 CN2 SW communication
switch
To enable communication with
equipment on CN2 and disable
communication with controller IF.
7 CN2 TB / PC connector Connection for teaching box or PC
with controller setting software.
Connection for controller IF.
4 Installation
4.1 Installation
Warning
•Do not install the product unless the safety instructions have been read
and understood.
4.2 Mounting
•The gateway can be direct mounted (model LEC-GMJ2) using 2 x M4
screws or mounted on a DIN rail (model LEC-GMJ2D).
•When using DIN rail mounting, hook the gateway on the DIN rail and
press the lever in the direction of Arrow A to lock it.
Direct mounting DIN rail mounting
4.3 Environment
Warning
•Do not use in an environment where corrosive gases, chemicals, salt
water or steam are present.
•Do not use in an explosive atmosphere.
•Do not expose to direct sunlight. Use a suitable protective cover.
•Do not install in a location subject to vibration or impact in excess of
the product’s specifications.
•Do not mount in a location exposed to radiant heat that would result in
temperatures in excess of the product’s specifications.
•Avoid mounting the gateway near a vibration source, such as a large
electromagnetic contactor or circuit breaker on the same panel.
•Do not use in an environment with strong magnetic fields present.
5 Wiring
5.1 Wiring
Caution
•Do not perform wiring while the power is on.
•Confirm proper insulation of wiring.
•Do not route wires and cables together with power or high voltage
cables.
•Keep wiring as short as possible to prevent interference from
electromagnetic noise and surge voltage.
•Do not use an inrush current limited type of power supply for the
gateway.
•Do not connect multiple wires to one connector terminal.
5.2 Power Supply Connector (CN4)
Wire the power supply cable to the power supply plug connector, then
insert it into connector CN4 on the gateway.
•Use special screwdriver (Phoenix Contact
No. SZS0.4×2.0) to open / close the lever
and insert the wire into the connector
terminal.
•Applicable wire size:
20 AWG (0.5 mm
2
).
No. Terminal Description
5 Wiring (continued)
5.3 Ground connection
•Connect a ground wire to the FG terminal (pin 5) on the power supply
connector (CN4).
Caution
The M4 screw, cable with crimped terminal and shakeproof washer must
be prepared by the user.
The gateway must be connected to Ground to shield it from electrical
noise.
•A dedicated Ground connection must be used. Grounding should be
to a D-class ground specification (resistance of 100 Ωmaximum).
•The cross-sectional area of the ground cable shall be 2 mm
2
minimum.
•The Grounding point should be as near as possible to the gateway.
Keep the grounding cable as short as possible.
5.4 Bus connector (CN3)
No. Terminal Description
1 DA CC-Link communication
2 DB CC-Link communication
5.5 Terminating resistor
Caution
•Connect the terminating resistor to both ends of the CC-Link main
communication line.
•For the CC-Link system, the terminating resistor value depends upon
the type of cable used.
Type of cable Resistance
Communication cable for CC
CC-Link dedicated high-performance
130 ohms, 1/2 W
Not Recommended
Other
Recommended FG
Gateway
unit
Other
Gateway
3m 3m 3m 3m 3m
・・・
Screw direction
Screw direction
DIN rail
Lever
Wire entry
Lever
FG terminal
1
2
3
4
5