Soyal AR-837-EA User manual

AR-837-EA
V230606
ACCESS & INDUSTRIAL CONTROL
- 1 -
B.
1
CN4
CN6 CN3 CN8 CN13
CN5
或
2
50~100cm
145 cm
60 mm
48.9 mm
25 mm 40.3 mm
29.6 mm
82.5 mm
108.7 mm
114 mm
56.3 mm 57.7 mm
35 mm
19.8 mm
4- 5.5
4- 6
60.3 mm
128 mm
64 mm
133.45 mm
66.7 mm
Contents
2Terminal Cables
1Products 3Tools
A-1.Surface Mounted: Use a screwdriver to screw the mounting plate to the wall.
A-2.Embedded: To dig a hole for 128mmx109mm; and then, use a screwdriver to screw the mounting plate
to the wall.
Pull cable ends through the access hole in the mounting plate.
Attach AR-837-EA to the mounting plate and install screws (supplied) into the holes at the bottom with the
allen key.
Apply power. LED (green) will light up with one beep.
Installation
AR-837-EA: Face recognition
Water proof Strip
Screws
Or
A-1.Surface Mounted A-2.Embedded
AR-MDL-721V
4Optional
Any Wiegand Output Module (CN10)
(Voice Module)
(TCP/IP Module included RJ45 Connector)
or
Ethernet : DMOD-NETMA10
DMOD-NETMA11
(TTL to RS-485 Converter)
AR-321L485-5V
(TCP/IP Module with POE function)
Installation Method
Dimension (mm) Installation Guide
(Digging depth)
Surface mounting hole(Front View) Surface mounting hole
(Side view)
Flush mounting hole
(Side view)
Flush mounting hole(Front View)

V230606
- 2 -
Surface / Flush-mounted Multifunctional
Face & RFID Recognition Controller
The communication wires and power line should NOT be bound in the same conduit or tubing.
Don’t equip reader and lock with the same power supply. The power for reader may be unstable when the lock is activating, that may cause a
malfunction in the reader.
The standard installation: Door relay and lock use the same power supply, and reader should use another independent power supply.
Use AWG 22-24 Shielded Twist Pair to avoid star wiring, CAT 5 cable for TCP/IP connection
1.Tubing:
2.Wire selection:
3.Power supply:
Connector Table (1)
Wire Application Wire Color Description
Lock Relay 1Blue White (N.O.)DC24V1Amp
2
Purple White
(N.C.)DC24V1Amp
Lock Relay COM 3White (COM)DC24V1Amp
Door Sensor 4Orange Negative Trigger Input
Exit Switch 5Purple Negative Trigger Input
Alarm Relay 6Gray N.O./N.C. Optional (by jumper)
Power 7Thick Red DC 12V
8Thick Black DC 0V
Cable:
Wire Application Wire Color Description
Anti-Tamper Switch 1Red N.C.
2Orange COM
3Yellow N.O.
Cable:
CN4
CN3
Wire Application Wire Color Description
RS-485 for Lift
Controller
1Thick Green RS-485(B-)
2Thick Blue RS-485(A+)
Cable: CN6
Notice
CN7
CN8
CN3
CN13
CN6
CN5
CN4
8
8
2
1
321
Connector Table (2): Optional
Wire Application Wire Color Description
HID RF Module 1Orange
ANT 1
2
Purple
ANT 2
3Black DC 0V
4Red DC 5V
5Blue Wiegand DAT: 1 Input
6Green Wiegand DAT: 0 Input
7White --
Wire Application Wire Color Description
Voice Module
(*Required speaker
8Ω / 1.5W (Max.
2W)
1Black DC 0V
2
Yellow
TX
3White TE
4Orange RX
5Red DC 5V
6Blue --
Cable: Cable:
Cable:
Wire Application Wire Color Description
1 --- ---
2 --- ---
TCP/IP Output
3
Orange White
Net - TX+
4Orange Net - TX-
5Green White Net - RX+
6Gerrn Net - RX-
7 --- ---
CN7 CN9 CN10
Wire Application Wire Color Description
Door Bell 1Black White Transistor Output Max. 12V/100mA
(Open Collector Active Low)
2Black DC 0V
Cable:
Wire Application Wire Color Description
Beeper 1Pink Beeper Output 5V/100mA, Low
LED 2Yellow Red LED Output 5V/20mA, Max
3Brown Green LED Output 5V/20mA, Max
Door Output 4Blue White Transistor Output Max. 12V/100mA
(Open Collector Active Low)
Wiegand 5Thin Green Wiegand DAT: 0 Input
6Thin Blue Wiegand DAT: 1 Input
WG Door Sensor
7Orange Negative Trigger Input
WG Exit Switch 8Purple Negative Trigger Input
Cable:
Wire Application Wire Color Description
Reserved 1 Red --
Security trigger signal
2Purple Security trigger signal Output
Arming 3 Red White Arming Output
Duress 4 Yellow White Duress Output
Cable: CN8
CN13
CN5
Connector Table (1)

AR-837-EA
V230606
ACCESS & INDUSTRIAL CONTROL
- 3 -
N.C.
COM
PB
12V
GND
CN4
1
2
3
5
6
7
8
4
CN5
WG Port
Main Port
N.O.
COM
N.C.
V+
V-
N.O.
P.T.Exit
GND
12V
EXIT
N.C.
COM
PB
12V
GND
CN4
1
2
3
5
6
7
8
4
CN5
WG Port
Main Port
N.O.
EXIT
+
–
E
GNDGND
EXIT
12V
GND
12V
GND
N.O.
12V
GND
CN4
N.C.
N.O.
COM
CTL
12V
GND
PB
AR-721RB
12V
GND
DDR
CN8
3
4
5
6
7
8
2
1
4
1 2 3
GND
GND
12V
N.C.
COM
PB
12V
GND
CN4
1
2
3
5
6
7
8
4
CN5
WG Port
Main Port
N.O.
EXIT
+
–
Sensor
12V
GND
CN4
1
2
3
5
6
7
8
4
CN5
WG
Port
Main Port
Sensor
CN3
P.T.Exit
GND
12V
+
–
+
–
E
COM
N.C.
N.O.
N.C.
N.O.
COM
ALM
N.C.
12V
GND
CN4
1
2
3
5
6
7
8
4
CN5
WG Port
Main Port
+
–
Sensor
N.C.
N.O.
COM
ALM
N.C.
COM
12V
ALM
GND
CN4
1
2
3
5
6
7
8
4
CN5
WG
Port
Main Port
CN3
P.T.Exit
GND
12V
SCADA
+
–
+
–
E
COM
N.C.
N.O.
DI
GND
Door Contact
Connect to Electric Bolt Connect to Magnetic Lock
Tamper-Switch Alarm Wiring Method Tamper-Switch Alarm Wiring Method
Wiring Diagram
Connect to Electric Strike
Controller
Controller
POWER
12VDC
POWER
12VDC
POWER
12VDC
POWER
12VDC
POWER
12VDC
POWER
12VDC
POWER
12VDC
POWER
12VDC
POWER
12VDC
RTE RTE RTE
Alarm
Alarm
Electric Bolt
AR-1207
Electric Bolt
AR-1207
Magnetic
Lock
Electric Strike
Universal I/O Module
AR-403-IO
Central
Monitoring
System
Built-in
Tamper Switch
Sensor
AR-MS-101-A
※ The Wiring of Enable "Share Door Relay" ( Set up via the parameterssetting Window of 701ServerSQL)
※ Enable WG Port option [Enable Force Alarm]
via Parameter Setting of 701Server Software
Door Open Too Long Alarm Wiring
Method (External Sensor) (Connect to Central Monitoring System through Modbus
via Universal I/O Module)
(WG Port Sensor Wiring Method)
Strengthen security with AR-721RB Connect to Reader
12V
GND
BZ
RLED
GLED
Door Output
WG 0
WG 1
WG-DS
WG-PB
N.C.
1
2
3
5
6
12V
GND
7
8
CN4
CN5
3
4
5
6
7
8
2
1
4
External lighting
(Connecting the external LED as backlight requires a special
rmware update and WG Slave Mode will be disabled.)
12V
CTL
COM
N.O.
POWER
12VDC
POWER
12VDC
Controller
E
Electric Bolt
AR-1207
Main Port
WG Port
CN5
※ The Wiring of Disable "Share Door Relay" ( Set up via the parameters
setting Window of 701ServerSQL
Strengthen security with AR-721RB
Controller
RTE
POWER
12VDC
POWER
12VDC
Electric Bolt
AR-1207
※This wiring method is not eligible for "Share Door Relay" function (set up via parameter
setting of 701ServerSQL). If there is external wiring to Wiegand reader, WG Port must
enabled Digital Relay Output to enable "Share Door Relay" function.
Controller
POWER
12VDC
Alarm
Electric Bolt
AR-1207
Built-in
Tamper Switch
※ Enable [Share Door Relay] & WG Port option
[Enable Force Alarm] via Parameter Setting of
701Server Software

V230606
- 4 -
Surface / Flush-mounted Multifunctional
Face & RFID Recognition Controller
Programming
B. Entering and Exiting Programming Mode
Exiting
Press the repeatedly → Quit or Quit and Arming (Please refer to alarm / arming setting)
6
Changing the Master Code
Access programming mode → Tools → Master Code → Input the 6-digit new master code → Succeeded
5 2
A. Keyboard Lock/ Unlock
Lock/ Unlock
Press and simultaneously to lock keyboard. Press simultaneously again to unlock.
Entering
Input 123456 or PPPPPP
[e.g.] The Default Value= 123456. If already changed the Master Code= 876112, input 876112 → Access programming mode
P.S.If no instruction is entered within 30 sec., it will automatically leave the programming mode.
7
C. Initial setup
Node ID of Reader Setting
Access programming mode → Parameters[1] → Node ID → Input New Node ID : 1~254 (default value:001) → Main Door Number : 0~255
→ WG1 Door Number : 0~255 → Show UID (0=No, 1=WG, 2=ABA, 3=HEX) → Enable DHCP(0:No, 1:En, 2=Exit) → Succeeded
3 1
Language Setting
Access programming mode → Tools → Language → EN → Succeeded → Initial system...
5 1 0
POWER
12VDC
WG Mode / Controller Mode Setting Method
1. AR-837-EA can be set up as WG26/WG34/WG64 while the Controller is in WG Mode. These Controller can
also be paired with the Controller that has WG input function.
2. Networking Setting: Select E Series Controller Parameter Edit in 701Server,tick up the function “Ev5 WG
out/Hv3 Lift out”
3. Please restart the controller after pressing “Write to Controller”.
12V
GND
CN4CN4
CN8CN5
CN5
BZ
RLED
GLED
Door Output
WG 0
WG 1
DSS
PB
DSS
PB
Duress
ARM
PB
12V
GND
12V
GND
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
5
6
7
8
1
2
3
5
6
7
8
AR-837-EA AR-837-EA
4
4
211
2
3
4
WG Mode Controller Mode
701ServerSQL Parameter Setting
701ServerSQL Parameter Setting

AR-837-EA
V230606
ACCESS & INDUSTRIAL CONTROL
- 5 -
12
07
14 : 49 : 04
WED
Duty
:
0
14 : 49 : 04
WED
Duty : 0
12
/
07
Access programming mode → Add/Delete → Add -> RF-Learn → Input 5-digit user address
→ Input Tag Units(pcs) → Close Tag into RF Area
※If the batch of tags are Sequential, input Tag Units(pcs) in the quantity of the tags and present the tag with
the lowest number to the controller for adding all the tag data; otherwise, the tags must be presented to the controller individually
1 2
Adding Tag by RF Learn Function
Tag Information
SITE CODE
CARD CODE
SITE CODE
CARD CODE
※ User capacity: 16384 (00000~16383)
Access programming mode → Add/Delete → Add -> Card ID → Input 5-digit user address → Input Site Code → Input Card Code
1 1
Adding Tag by Tag ID
Access programming mode → Add/Delete → Delete -> Addr → Input Start address → Input End address
1 5
Deleting User Address
Access programming mode → Add/Delete → Suspend -> Addr → Input Start address → Input End address
1 3
Suspend User Address
Access programming mode → Add/Delete → Suspend -> ID # → Input Site Code → Input Card Code
1 4
Suspend Tag by Tag ID
Access programming mode → Add/Delete → Delete -> Addr → Input Start address → Input End address
1 7
Recover User Address
Access programming mode → Add/Delete → Delete -> ID # → Input Site Code → Input Card Code
1 8
Recover Tag by Tag ID
D. Adding and Deleting Tag
1. System will automatically exit Programming Mode when inactivating for 30
seconds.
2. LED status indicates controller’s mode and status.
OK (green) – blinking constantly when operating in Programming Mode
– or ashing an existed card in card learn mode, it comes 2 beeps
warning and LCD panel displays “Same Card: user address / card
number”
Error (red) – invalid card with 2 beeps warning and LCD panel displays “Card
Number Err!”
– or in anti-pass-back mode, when violates the access, it comes one
beep warning and LCD panel displays “Anti-pass Error!”
Arming (green) – arming on status
Alarm (red) – any abnormal condition occurs
3. Keypad will be locked up 30 sec. when incorrect pin code or master code is
constantly entered.
4. Maximum error input of pin code and master code can be changed via the
software 701Server (default: 5 times)
Power(Green)
Alarm(Red)
Arming(Green)
OK(Green)
Error(Red)
In processing(Green)
Networking : / and interactively ash between the Month and DAY.
[e.g.] 12/07←→12 07
Stand-alone : No ashing [e.g.] 12/07
(←Reference to picture)
Manu Tree
Function Description of Front Panel & Indicator
5. Tools
1. Language
2. Master Code
3. Master Range
4. Terminal RS-485
5. Ext.Comm CN11
6. Open Time Zone
7. Informations
8. Clock Setting
9. Daily Alarm
0. UART Port CN9
A. Event Logs
6. Quit
7. Quit & Arming
4. Parameters[2]
1. Auto Relock
2. Egress(R.T.E)
3. Miscellaneous
4. Force Open
5. Close & Stop
6. Anti-pass-back
7. Duress Code
8. Password Mode
9. Factory Reset
3. Parameters[1]
1. Node ID
2. OnO OpenZone
3. Door Relay Tm
4. Door Close Tm
5. Alarm Relay Tm
6. Alarm Delay Tm
7. Arming Delay Tm
8. Arming PWD
2. User Setting
1. Password
2. Access Mode
3. Extend Options
4. Single Floor
5. Multi Floor
6. Enroll Face
7. Delete Face
1. Add/ Delete
1. Add > Card ID
2. Add > RF Learn
3. Suspend > Address
4. Suspend > ID #
5. Delete > Address
6. Delete > ID #
7. Recover > Address
8. Recover > ID #
9. Antipass Group
※ The full screen menu setting is on page11 - Full Function Command Menu Table

V230606
- 6 -
Surface / Flush-mounted Multifunctional
Face & RFID Recognition Controller
H. Arming Password
K. Duress Code
L. Terminal Port
I. Arming Delay Time
Access programming mode → Parameters[1] → Arming PWD → Input 4-digit PIN (0001~9999; Default: 1234) → Succeeded
Or via 701Server and set it on AR-837-EA screen
38
Or via 701Server to set it on AR-837-EA screen
※Duress Code is only available in networking mode. It will substitute a personal pin code and send the message of Duress to computer as a warning signal.
※The Duress Code 0000 means that disable Duress Function and the default value is set as 0000 already.
Access programming mode → Parameters[2] → Duress Code → 4 sets (select one) → Input 4-digit PIN (0001~9999) → Succeeded
4 7
Access programming mode → Tools → Terminal Port → 0:Lift ; 1:Host ; 2:LED ; 3:PRN (default value:1) → Baud Selection
(default value:9600) → Succeeded
5 4
M. Setting up the alarm / arming
Conditions:
1. Arming enabled
2.Alarm system connected
Situations:
1. Door is open overtime: Door is open longer than door relay time plus door close time.
2. Force open (Opened without a valid user card): Access by force or illegal procedure.
3. Door position is abnormal: Happening when power is o and then on again, besides,
reader was on arming before power went o.
Access programming mode → Parameters[1] → ArmingDelayTm → Enter armed sta. Delay time(Sec), Range:000~255
;
Armed pulse out-put time (10ms) ,Range
:
000~255 → Succeeded
37
F. Enroll/Delete Face
Adding
Access programming mode → User Setting → Delete Face → Key in 5-digit user address →Follow the instruction on LCD Screen to enroll face
→Succeeded
2 6
Deleting
Access programming mode → User Setting → Delete FP → Key in 5-digit user address → Succeeded
P.S. If want to delete all users’ face data’ FP, key in 99999
2 7
#
G. Access Mode
E. PIN Code
Access programming mode → User Setting → Enroll Face → Input 5-digit user address → Input 4-digit PIN (0001~9999) → Succeeded
Or via 701Client set it on Users screen
21
Access programming mode → User Setting → Access Mode → Input User Address → 0: Invalid; 1: Card ; 2: Card or PIN; 3: Card & PIN
2 2
Setting up the access mode
Access programming mode → Add/Delete → Delete -> ID # → Input Site Code → Input Card Code
1 6
Deleting Tag by Tag ID
J. PIN & UID Length setting
Access programming mode → Parameters[1] → PIN & UID format → User PIN Length Range:4~8(4 is default value)
;
Card PIN Length Range:2~8(4 is default value)
39
※ If you select the access mode
with PIN, please ensure the
parameters in
Parameters
【2】 →
Miscellaneous →
Main Controller Skip PIN
Check, select 0 to disable WG1
Port Skip PIN Check, select
0 to disable; It will mistake
Controller and cannot get access
if you select dierent access
mode in Access mode and
Miscellaneous
4 3
3
2
Access programming mode →
User Setting → Access Mode
→ Key in 5-digit user address
(00000~08999)
→ 0: Invalid; 1:Card; 2: Card or
PIN; 3: Card and PIN
(837EA: → Finger Identify: 0:
Must ; 1: Ignore )→ Succeeded
2
2Access Mode Finger Identify
(837EF/EA Only) Result (837EF/EA Only)
Hardware 701Client Hardware 701Client
0:Invalid
0: Must Just card
Just Face / FP Invalid User
1: Ignore Just card
Just Face / FP
1:Card / Card only
0: Must Just card
Just Face / FP Finger+Card
0: Must Just card
Just Face / FP
Card rst, then ngerprint.
Special rmware version (For requirements, contact SOYAL).
APS837EF___V0405_230512 先卡片再按指紋.STM
1: Ignore Just card
Just Face / FP
1. Card Only
2. Finger Only
2:Card or PIN
0: Must Just card
Just Face / FP
1. Finger+Card 2. Finger+PIN 3. Card+Finger+PIN
4. Card+Finger+Card 5. PIN+Finger+PIN 6. PIN+Finger+Card
0: Must Just card
Just Face / FP
Card rst, then ngerprint.
Special rmware version (For requirements, contact SOYAL)
APS837EF___V0405_230512 先卡片再按指紋.STM
1: Ignore Just card
Just Face / FP 1. Card Only 2. PIN Only 3. Finger Only
3:Card and PIN
0: Must Just card
Just Face / FP Finger+Card+PIN
1: Ignore Just card
Just Face / FP 1. Card+PIN 2. Finger+PIN

V230606
- 7 -
Surface / Flush-mounted Multifunctional
Face & RFID Recognition Controller
P. Alarm Clock (for Factory)
Hardware installation
M1
Board
Horn M2
1
2
3
4
5
6
7
8
N.C.
N.O.
COM
CTL
12V
ALM
12V
GND
GND
P1
Output to M1 and M2
Mike device
Mike device
Music Box
Music Box Mike's sound wire
Mike's sound wire
DC 12V Relay Board
Controller
POWER
12VDC
Access programming mode → Tools → Daily Alarm → Set (00~15) → Set Start Tm (24 Hours) ; Set Eect Sec.
(Seconds as the bell time, Range:1~255) → Set Weekday (0:disable, 1: enable) → Succeeded
5 9
O. Lift control
[e.g.] Connect with AR-401-IO-0016R to control which oor the user will be able to access. (BAUD9600)
Access programming mode → Tools → Terminal Port → 0
:
Lift Controller → Baud Selection 0
: 9600
5 4
Setting Lift control
Access programming mode → User Setting → Single Floor →
Input 5-digit user address → Input single oor number: 1~64
2 4
Single oor
Access programming mode → User Setting → Multi Floor → Input 5-digit user address → Select range: 1 or 2 or 3 or 4 → Input 16 digits
multi oors number [0:disable, 1: enable]
[e.g.] Set NO. 114, can use it through the 8 F and 16F:
Access programming mode → User Setting → Multi Floor → 114 → 1 → 0000000100000001
2
2
5
5
Multi oors
Set Floor/ Stop
1
0
17
0
33
0
49
0
9
0
25
0
41
0
57
0
1
2
3
4
3
0
19
0
35
0
51
0
11
0
27
0
43
0
59
0
2
0
18
0
34
0
50
0
10
0
26
0
42
0
58
0
4
0
20
0
36
0
52
0
12
0
28
0
44
0
60
0
5
0
21
0
37
0
53
0
13
0
29
0
45
0
61
0
6
0
22
0
38
0
54
0
14
0
30
0
46
0
62
0
7
0
23
0
39
0
55
0
15
0
31
0
47
0
63
0
8
1
24
0
40
0
56
0
16
1
32
0
48
0
64
0
Access programming mode → Tools → Terminal Port → 1
:
Lift Controller
(need to use AR-321L485-5V)
5 5
While connecting with AR-723-U(WG mode) and AR-661-U for anti-pass-back function, the access mode must be "Card" only.
N. Anti-pass-back
Device enable
Access programming mode → Parameters[2] → Anti-pass-back → master controller select [1: Yes] → WG select [1: Yes]
4 6
Card user enable
Access programming mode → Add/ Delete → Antipass Group → Input 5-digit starting user address → Input 5-digit ending user
address → must select [1: Yes]
1 9
Enable/Disable the arming status:
Standby Mode
Access Programming mode
Card only Card or PIN Card and PIN
Open the door
Present the tag to reader → Input
4-digit arming PWD →
Input user address → Input
4-digit individual PWD → →
Input 4-digit arming PWD →
Present the tag to reader → Input
4-digit individual PWD → →
Input 4-digit arming PWD →
Enable: Access programming mode → Quit & Arming
7Disable: Access programming mode → Quit
6
No open the door
→ Input 4-digit arming PWD
→ Present the tag to reader
※ [Use FP] can substitute for [Induct valid card].

V230606
- 8 -
Surface / Flush-mounted Multifunctional
Face & RFID Recognition Controller
Access programming mode → Parameters[1] → OnO OpenZone → Main Controller Auto Open Zone (0:disable, 1:enable)→
Open Door lmm. During Open Zone (0:No, 1:Yes) → WG1 Port Auto Open Zone(0:disable,1:enable)→ Open Door Imm.During
Open Zone(0:No, 1:Yes) → Succeeded
3 2
Q. OpenZone
R. Open TimeZone
Access programming mode → Tools → Open TimeZone → Set (00~15)→ Time (24 Hours) → Main Port(0:disable,1:enable) ;
WG Port(0:disable,1:enable)→ Weekday(0:disable,1:enable) →Succeeded
56
Access programming mode → Parameters[1] → Node ID → Enter New Node ID → Main
Door Number Range → WG1 Door Number Range → Show WG Message → Enable DHCP
→ please enter IP Address(IPV4) → please enter Net Mask(IPV4) → please enter Gatewa(IPV4) →
Succeeded
IP Address Cong
31
Parameter Setting Menu
Set card display mode
I nput New NodeID
Range
: 001 ~ 254
Current Data
:
001
1. Add / Delete
2. User Setting
3. Parameters(1)
4. Parameters(2)
1. Node ID
2. Ono OpenZone
3. Door Relay Tm
4. Door Close Tm
001
Enable DHCP
0:
NO 1
:
En
192.168.001.127*
0
2
:
Exit
WG1 Door Number
Range
: 000 ~ 255
002
Show WG Message
0
:
NO
1
IP Address(I PV4)
192.168.001.127
192.xxx.xxx.xxx
Net Mask ( IPV4)
255.255.255.000
255.xxx.xxx.xxx
Gateway (I PV4)
192.168.001.254
192.xxx.xxx.xxx
6.
7.
8.
9.
Alarm DelayTm
ArmingDelayTm
Arming PWD
PIN&UID format
User PIN Length
Range
:4~ 8
4
Card UID Length
Range
:2~ 8
4
Show UID
1=WG 2=ABA 3=HEX
4=WG26 5=ABA8
Succeeded
0=N
Show UID
1=WG 2=ABA 3=HEX
4=WG26 5=ABA8
2
0=N
Main Door Number
Range
: 001 ~ 255
001
1
:
Enable
Access programming mode → Parameters[1] → PIN&UID format → User PIN Length
→ Card UID Length → Show UID → Succeeded
3 9
1. Add / Delete
2. User Setting
3. Parameters(1)
4. Parameters(2)

AR-837-EA
V230606
ACCESS & INDUSTRIAL CONTROL
- 9 -
Capture facial data and analyze Controller extract data Data Comparison Veried successfully
Face Enrollment Tips
When registering for facial recognition, it is recommended to place the face close to the camera and
try to ll the frame as much as possible by moving the face forward. This can increase the chances of a
successful registration.
After registering a face, if it is similar to other facial features, especially for twins, the following solutions
should be considered:
1.Re-register under sucient lighting conditions.
2.Exchange registration order with each other.
3.Repeat registration and capture feature points until successful registration
Face Enrollment Procedure

AR-837-EA
V230606
ACCESS & INDUSTRIAL CONTROL
- 10 -
Notes and Tips for Registration and Recognition of Wearing Face Mask
Detection Mode

AR-837-EA
V230606
ACCESS & INDUSTRIAL CONTROL
- 11 -
Entering
Input 123456 or PPPPPP
[e.g.] The Default Value= 123456. If already changed the Master Code= 876112, input 876112
→ Access programming mode
P.S.If no instruction is entered within 30 sec., it will automatically leave the programming mode.
Up
Down
Enter/OKEsc/Quit
1. Add/ Delete
2. User Setting
1-4. Suspend > ID #
2-4. Single Floor
1-9. Antipass Group
1-4-1
2-4-1
1-9-1
1-4-2
2-4-2
1-9-2
Set Site:
00000:XXXXX
Range: (0-65535)
User Address:
F3: Prev F4: Next
Range (0-016383)
Input Start Address
Range: (0-16383)
Set Code:
00000:XXXXX
Range: (0-65535)
Set Single Floor
(Range: 01~64)
Clear the Others
Input End Address
Range: (0-16383)
1-5. Delete > Address
2-6. Enroll Face
2-7. Delete Face
2-5. Multi Floors
1-5-1
2-6-1
2-7-1
2-5-1
1-5-2
2-6-22-5-2
Input Start Address
Range: (0-16383)
User Address:
F3: Prev F4: Next
Range: (0-002998)
User Address:
F3: Prev F4: Next
Range: (0-099999)
000000
User Address:
F3: Prev F4: Next
Range: (0-016383)
Input End Address
Range: (0-16383)
Closer: Rotating
Center Image Pls
Select Range:
1: 01-16 2: 17-32
3: 33-48 4: 49-64
1-3. Suspend -> Address
2-3. Extend Options
1-8. Recover > ID #
1-3-1
2-3-1
1-8-1
1-3-2
2-3-2
1-8-2
Input Start Address
Range: (0-16383)
User Address:
F3: Prev F4: Next
Range (0-16383)
Set Site:
00000:XXXXX
Range: (0-65535)
Input End Address
Range: (0-16383)
Is Guard User
0: NO 1: YES
Set Code:
00000:XXXXX
Range: (0-65535)
1-1. Add -> Card ID
2-1. Password
1-6. Delete > ID #
1-1-1
2-1-1
1- 6-1
1-1-2
2-1-2
1-6-2
1-1-3
User Address:
00000 XXXXX
Range: (0-16383)
User Address:
F3: PreV F4: Next
Range (0-016383)
Set Site:
00000:XXXXX
Range: (0-65535)
Set (User Address) Code:
00000 XXXXX
(1-10 Digital)
Input PIN Code
Rang: 0000~9999
Set Code:
00000:XXXXX
Range: (0-65535)
Set (User Address) Code:
00000:_XXXX
Range: (0-65535)
1-2. Add -> RF-learn
2-2. Access Mode
1-7. Recover > Address
1-2-1
2-2-1
1-7-1
1-2-2
2-2-2
2-2-3
1-7-2
1-2-3
2-3-3
2-5-3
1-9-3
User Address:
F3: Prev F4: Next
Range: (0-016383)
User Address:
F3: Prev F4: Next
Range (0-163833)
Input Start Address
Range: (0-16383)
Tag Uints (pcs)
Must be Sequence
Range: (1-016378)
0: Invalid 1: Card
2: Card or PIN
3: Card & Pin
Finger / Face
0: Must 1: Ignore
000000=0
Input End Address
Range: (0-16383)
Close Tag
Into RF Area
Enable Antipass
0: NO 1: YES
Data: 1
0->NO 1->YES
Current Setting:
1000000000000000
Enable Antipass
0: NO 1: YES
Data: 0
Full Function Command Menu Table

AR-837-EA
V230606
ACCESS & INDUSTRIAL CONTROL
- 12 -
Full Function Command Menu Table
3. Parameters [1]
4. Parameters [2]
3-3. Door Relay Tm
3-8. Arming PWD.
3-3-1
3-8-1
Main Door OpenTm
Range: 000~609
601~609=0.1~0.9
007
Input PIN Code
Range: 0000~9999
1234
3-4. Door Close Tm
3-9. PIN&UID format
3-7. Arming Delay Tm3-5. Alarm Relay Tm 3-6. Alarm Delay Tm
3-4-1
3-9-1 3-9-3 3-9-5 3-9-7
3-7-13-5-1 3-6-1
Main Door Close
delay time (Sec)
Range: 000~255
015
User PIN Length
Range: 4~8
4
Show UID :0=No
1=WG 2=ABA
3=HEX 4=WG26
5=ABA8
1
RFID 125KHz RF
0: Disable
1: Enable
1
User Capacity:
0: 16384 1: 32768
2: 65536 (0~2)
0
Enter armed sta.
Delay time (Sec)
Range: 000~255
001
Alarm Relay Time
Range: 000~609
601~609=0.1~0.9
015
Alarm Output
Delay time (Sec)
Range: 000~255
3-2. OnOff OpenZone
3-2-1
Main Controller
Auto Open Zone
Dis/Enable (0/1)
0
3-1. Node ID
4-1. Auto Relock 4-2. Egress(R.T.E) 4-3. Miscellaneous
3-1-1
4-1-1 4-2-1 4-3-1 4-3-4 4-3-7
3-1-2
4-1-2 4-2-2 4-3-2 4-3-5 4-3-8
4-3-3 4-3-6 4-3-9
3-1-6 3-2-2
3-3-2 3-4-2
3-9-2 3-9-4 3-9-6 3-9-8
3-7-2
3-1-3 3-1-5 3-1-7
3-1-4 3-1-8
Input New NodeID
Range: 001~254
Current Data: 001
Main Controller
Auto Relock Door
0: NO 1:YES
0
Main Controller
Request To Exit
0: Dis 1:Enable
0
Main Controller
TimeAttendance
0: YES 1: NO
0
WG1 Port
Skip PIN Check
0: NO 1: YES
0
WG1 Port
Share Main Relay
0: NO 1: YES
0
Main Door Number
Range: 000~255
WG Prot
Auto Relock Door
0: NO 1:YES
0
WG1 Port
Request To Exit
0: Dis 1:Enable
0
WG1 Port
TimeAttendance
0: YES 1: NO
0
Main Controller
Pass any Tags
0: NO 1: YES
0
Tag Second time
interval (10ms)
Range: 0000~9999
0100
Main Controller
Skip PIN Check
0: NO 1: YES
0
WG1 Port
Pass any Tags
0: NO 1: YES
0
Max error times
for lock keypad
Range: (0~9)
5
IP Address (IPv4)
192.168.001.127
192.xxx.xxx.xxx
WG1 Port Auto Open
Zone Dis/Enable (0/1)
0
WG1 Door OpenTm
Range: 000~609
601~609=0.1~0.9
007
WG1 Door Close
delay time (Sec)
Range: 000~255
015
Card UID Length
Range: 2~8
4
NFC 13.56MHz RF
0: Disable
1: Enable
1
'#' is Door Bell
0: Disable
1: Enable
0
Enable Buzzer
0: NO 1: YES
1
Armed Pulse out-
put time. (10ms)
Range:000~255
000
WG1 Door Number
Range: 000~255
Net Mask (IPv4)
255.255.255.000
255.xxx.xxx.xxx
Show WG Message
0: NO 1:Enable
1
Gateway (IPv4)
192.168.001. 254
192.xxx.xxx.xxx
Enable DHCP
0: No 1: En 2: Exit
192.168.001.127*
0
※User PIN Length Range:4~8(4 is default value)
;
Card PIN Length Range:2~8(4 is default value)

AR-837-EA
V230606
ACCESS & INDUSTRIAL CONTROL
- 13 -
Full Function Command Menu Table
4. Parameters [2]
5. Tools
6. Quit
7. Quit & Arming
5-1. Language
5-2. Master Code
5-3. Master Range
5-6. Open Time Zone 5-9. Daily Alarm 5-0. UART Port CN9 5-A. Event Logs
5-8. Clock Setting
5-7. Informations
5-4. Terminal RS485 5-5. Ext.Comm CN11
4-7. Duress Code 4-8. Password Mode 4-9. Factory Reset
5-1-1
5-2-1
5-3-1
5- 6-1 5-9-1 5-0-1
5-8-1
5-7-1
5-4-1 5-5-1
4-7-1 4-8-1 4-9-1
5-3-2
5-6-2 5-9-2 5-0-2
5-8-2
5-6-3 5-9-3
5-A-1
5-4-2
0: English (USA)
1: Chinese (TW)
0
Input MasterCode
000001~999999
123456
Input Start Addr
Range: (0-16383)
000000
Set <F1~F4,#>: 01
00:00~00:00 ..
SuMoTuWeThFrSaHo
0 0 0 0 0 0 0 0
Set <F1~F4,#>: 01
00:00 Sec.=000
SuMoTuWeThFrSaHo
0 0 0 0 0 0 0 0
0: Lift9600 1: PRN
2: LED 3: Voice
0
YY: XXXX MM: XX
Day: XX Hour: XX
Min: XX Sec: XX
F/w Ver: 4.4T
Users: 00000
Messages: 00000
Press any Key ...
0: Lift 1: Host
2:LED 3: PRN
1
0: FP-Type 1: Lift
2: Vein2000 3:
FP9000 4:……..
2
Input PIN Code
Range: 0000~9999
Password Mode
0: Addr. & PIN(M4)
1: PIN(M8) 2:M6
1
0: System Param.
1: User Setting
2: System & User
2
Input End Addr
Range: (0-16383)
000000
Time=00:00~00:00
Main Port (0/1):0
WG Port (0/1):0
Start Tm=00:00
Effect Sec.=000
Elevator oor
button available
Range: (1~600)
015
Month/Day Format
0: DD/MM 1: MM/
DD
Weekday: (0/1)
SuMoTuWeThFrSaHo
X X X X X X X X
0 0 0 0 0 0 0 0
Weekday: (0/1)
SuMoTuWeThFrSaHo
X X X X X X X X
0 0 0 0 0 0 0 0
20'06/04 2359:26
(M24)Controller
Power On 00000
Baud Selection
0: 9600 1: 19200
2: 38400 3: 57600
※More Details:Introduction of New Function Commands for Enterprise E Controller and Home H Controller
4-3. Miscellaneous 4-4. Force Open .. 4-5. Close & Stop 4-6. Anti-passback
4-3-10 4-4-1 4-5-1 4-6-14-3-12 4-3-14 (837EF)
4-3-134-3 -11 4-4-2 4-5-2 4-6-2
Main Controller
On Egress Beeps
0: NO 1: Bi 2: Bibb
2
Main Controller
Force Open Alarm
0: NO 1: YES
0
Main Controller
Close Door Stop
Alarm 0: NO 1:YES
0
Main Controller
Anti-passback
0: NO 1: YES
0
Lock Door Relay
0: NO 1: YES
0
Main Controller
Free Tag Always
0:NO 1:YES
0
Interlock to WG ?
0:NO 1:YES
0
WG1 Port
On Egress Beeps
0: NO 1: Bi 2: Bibb
2
WG1 Port
Force Open Alarm
0: NO 1: YES
0
WG1 Port
Close Door Stop
Alarm 0: NO 1:YES
0
WG1 Port
Anti-passback
0: NO 1: YES
0
Other manuals for AR-837-EA
1
Table of contents
Other Soyal IP Access Controllers manuals

Soyal
Soyal AR-721KP User manual

Soyal
Soyal AR-331-E User manual

Soyal
Soyal AR-888-PBI-S User manual

Soyal
Soyal AR-888-PBI User manual

Soyal
Soyal AR-101-H User manual

Soyal
Soyal AR-821EF User manual

Soyal
Soyal AR-723-H User manual

Soyal
Soyal AR-721U User manual

Soyal
Soyal AR-837-E User manual

Soyal
Soyal AR-723 User manual

Soyal
Soyal AR-888H User manual

Soyal
Soyal AR-725E User manual

Soyal
Soyal AR-723 H User manual

Soyal
Soyal AR-327H User manual

Soyal
Soyal AR-363-E User manual

Soyal
Soyal AR-829E User manual

Soyal
Soyal AR-331-E User manual

Soyal
Soyal AR-837 E User manual

Soyal
Soyal AR-881-EF9DO User manual

Soyal
Soyal AR-837-EL User manual