Installation – Commissioning – Maintenance 20151013 / Art. No. 1545217
Installation
All connections to the duct system should be done with a
straight duct of the same dimension as the box inlet and
with a length > 2 x ØD. If a flexible duct is used, it should be
stretched so it remains as straight as possible, see figure 1.
1. The commissioning box can be suspended from a ceiling
and connected to a duct system.The diffuser is secured
to the ceiling by connecting the M8 threaded rod (A)
into the popnut on the top of the diffuser, see figure 3.
2. Make sure that the orientation of the sensor module
aligns with the extension of the room, see figure 2. If
the connecting duct does not enter the room as in the
example in figure 4, the frontplate of the diffuser must
be dismantled and rotated in a direction with the sensor
module directed as shown in figure 2. Then fixate and
secure the diffuser with screws or pop rivets. Readjust
the hanger rods of the commissioning box if necessary.
3. The front plate is dismantled by pressing the fixing pins
of the bottom plate outward, which will loosen it from
the upper cone. Detach the safety cord that secures front
plate to the upper cone and disconnect the connector
(C, figure 3) from the top of the front plate. When reas-
sembling, press together the S-hook to prevent it from
coming loose.
A
B
C
Figure 3. ADAPT Free, installation.
Figure 2. The orientation of the sensor module in a room or in an
office module. The LED’s of the sensor should be aligned with
the extension of the room in a straight line, facing the short sides
of the room as shown by the arrow in the figure.
Figure 1. Using a flexible duct.
2Swegon reserves the right to alter specifications. 20151013 www.swegon.com
WISE
Maintenance
The exterior surface of the ADAPT air diffusers can be
cleaned whenever necessary using lukewarm water with
dishwashing detergent added.
The duct system is accessible through the air diffuser and
the commissioning box.
Commissioning
All the ADAPT Air diffusers are delivered preset into com-
missioning mode, which means that the air diffuser is set to
max. airflow by override control.
When the ADAPT air diffuser is in commissioning mode,
the light-emitting diode shines orange. The different LED
indications:
• Steady green LED: Normal operation, the air diffuser is
operating normally.
• Flashing green LED: The air diffuser has just been
powered on and calibration is in progress.
• Steady red LED: Function failure, see separate docu-
mentation inte the TUNE Adapt manual.
• Steady orange LED: The commissioning mode, max.
airflow
• Flashing orange LED: Other commissioning modes and
all the forced control situations of the feedback control
system.
More information about the commissioning process itself
can be read in the Project Manual for the Wise system and
the TUNE Adapt manual.
Figure 4. Lighting fixtures or similar objects must not be installed
beneath the diffuser as this disrupts the presence detection and
room temperature measurement.
3
Swegon reserves the right to alter specifications. 20151013 www.swegon.com
WISE
Electrical connections.
All the connections are wired to the CONNECT Adapt con-
nection box. From there, the Master air diffuser is connected
by means of the LINK Adapt (RJ45) cable included in the
delivery. The slave air diffusers, if required, are connected
by means of the same type of cable to their respective slave
contacts. If there are more than 2 slave air diffusers, a SPLIT
Link Adapt should be used for further connection to the last
slave air diffuser. See Figure 7. If SPLIT Link Adapt is used, the
maximum length of LINK Adapt from the connection box to
the last air diffuser is 15 meters. If ADAPT is to be connected
through Modbus communication, this should be done with
the LINK Modbus (RJ12) cable. The maximum length of
SPLIT Link Modbus is 10 meters from the connection box to
the last air diffuser. Use double CONNECT Adapts if longer
distances are required. All cables and contacts are different
so that they will not be confused or incorrectly connected.
Electrical data
ADAPT is supplied with power via the connection box. See
the wiring diagram in figure 7 or relevant diagram from the
Swegon Templates application, containing details for the
specific installation. It is important that cables with appro-
priate cross-sectional area, transformers of correct size and
power supply cables of correct length are selected. This
can for example be carried out with the dimensioning tool
“Cable and Transformer Design”, available for download
from www.swegon.com (the application is available in
english and swedish language versions).
Supply voltage 24 V AC ±10 %
Max. power consumption (controller only) 3 VA
Cable rating (controller only) 0,6 A
Ambient temperature 0 °C - +50 °C
Figure 5. Commissioning with TUNE Adapt.
2
3
1
24 V
Modbus
Figure 6. Air diffuser connections.
1. Connection for LINK Adapt cable (RJ45)
2. Connection for the LINK Modbus cable (RJ12).
3. Direct 24 V connection if a connection box is not used and the
air diffuser will be completely “stand alone”.
4Swegon reserves the right to alter specifications. 20151013 www.swegon.com
WISE
Figure 7. Wiring of Master/Slave air diffusers and accessories.
1. ADAPT Master air diffuser
2. ADAPT Slave air diffusers
3. CONNECT Adapt, connection box
4. 24 V AC Transformer
5. LINK Adapt (5 m long RJ45 cable)
6. LINK Modbus (5 m long RJ12 cable)
7a. TUNE Temp (1 VA)
7b. DETECT Quality (Room version with display - Q0: 1 VA.
Room version without display Q1 and duct version - Q2: 3 VA)
7c. DETECT RH, humidity sensor (1 VA)
8. ACTUATOR, radiator control (max 3 valves at 6 VA)
9. ADAPT Relay, relay for lighting
10. Connection to main control system (Modbus RTU)
11. SPLIT Link RJ45
12. SPLIT Modbus RJ12, max. stab length, 10 m.
*) Only one of the accessories in paragraph 7 can be connected at
any one time in a room installation.
20
Master
21
Slave
22
Slave
23
Modbus
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
65
4
3
9
55
10
- + C
A1 A2 1 3
1222
11
5
12
6
8
5
1
6
7a
7b
G
G0
OUT1
1
2
3
7c
66
12 12

Other Swegon Fan manuals

Swegon ADAPT Extract d Guide

Swegon

Swegon ADAPT Extract d Guide

Swegon PELICAN Ceiling HF Guide

Swegon

Swegon PELICAN Ceiling HF Guide

Swegon LOCKZONE Wall a User manual

Swegon

Swegon LOCKZONE Wall a User manual

Swegon ADAPT Sphere b Guide

Swegon

Swegon ADAPT Sphere b Guide

Swegon PELICAN Ceiling Extract a Guide

Swegon

Swegon PELICAN Ceiling Extract a Guide

Swegon REACT V SKNXa User manual

Swegon

Swegon REACT V SKNXa User manual

Swegon COLIBRI Ceiling CR Guide

Swegon

Swegon COLIBRI Ceiling CR Guide

Swegon CASA W3 Smart User manual

Swegon

Swegon CASA W3 Smart User manual

Swegon ADAPT Parasol b-X User manual

Swegon

Swegon ADAPT Parasol b-X User manual

Swegon EXFa EXFT1 User manual

Swegon

Swegon EXFa EXFT1 User manual

Swegon ADAPT Parasol b User manual

Swegon

Swegon ADAPT Parasol b User manual

Swegon ADAPT Parasol EXb User manual

Swegon

Swegon ADAPT Parasol EXb User manual

Swegon PARAGONc User manual

Swegon

Swegon PARAGONc User manual

Swegon PARAGON Wall VAV Guide

Swegon

Swegon PARAGON Wall VAV Guide

Swegon EAGLE Wall b Guide

Swegon

Swegon EAGLE Wall b Guide

Swegon ADAPT Colibri d Guide

Swegon

Swegon ADAPT Colibri d Guide

Swegon CASA R7H Smart Guide

Swegon

Swegon CASA R7H Smart Guide

Swegon LOCKZONE Ceiling a Guide

Swegon

Swegon LOCKZONE Ceiling a Guide

Swegon GOLD RX User manual

Swegon

Swegon GOLD RX User manual

Swegon WISE Kite Ceiling a User manual

Swegon

Swegon WISE Kite Ceiling a User manual

Swegon ADAPT Parasol b 600 Guide

Swegon

Swegon ADAPT Parasol b 600 Guide

Swegon PARASOL EXc 690 MF Guide

Swegon

Swegon PARASOL EXc 690 MF Guide

Swegon GOLD series Quick start guide

Swegon

Swegon GOLD series Quick start guide

Swegon Adapt Sphere d User manual

Swegon

Swegon Adapt Sphere d User manual

Popular Fan manuals by other brands

Ayce 2F12 Operator's manual

Ayce

Ayce 2F12 Operator's manual

Faro Barcelona Ventyly KARUI Assembly manual

Faro Barcelona

Faro Barcelona Ventyly KARUI Assembly manual

Jefferson JEFFANDRM30-230 user manual

Jefferson

Jefferson JEFFANDRM30-230 user manual

aerauliqa QR400ABP installation manual

aerauliqa

aerauliqa QR400ABP installation manual

NSA TF-67RC instruction manual

NSA

NSA TF-67RC instruction manual

Eldom COLUMBIA VAC WGC40M instruction manual

Eldom

Eldom COLUMBIA VAC WGC40M instruction manual

LU-VE CHS-LHS Installation and maintenance  instruction

LU-VE

LU-VE CHS-LHS Installation and maintenance instruction

ClairiTech Innovations HumiFresh Hybrid 200 Installation & owner's manual

ClairiTech Innovations

ClairiTech Innovations HumiFresh Hybrid 200 Installation & owner's manual

Kogan ClearCool KA3FANTOWR instructions

Kogan

Kogan ClearCool KA3FANTOWR instructions

Hunter Builder Low Profile instruction manual

Hunter

Hunter Builder Low Profile instruction manual

Honeywell 50202 manual

Honeywell

Honeywell 50202 manual

Aprilaire ARNHPF Installation & operating instructions

Aprilaire

Aprilaire ARNHPF Installation & operating instructions

Hunter 28523 Parts guide

Hunter

Hunter 28523 Parts guide

Hinkley VAIL 52" instruction manual

Hinkley

Hinkley VAIL 52" instruction manual

Hunter 28839 Parts guide

Hunter

Hunter 28839 Parts guide

Exquisit VT 33056 we instruction manual

Exquisit

Exquisit VT 33056 we instruction manual

Sulion DIEHL manual

Sulion

Sulion DIEHL manual

Ruck Ventilatoren ISOR Assembly instruction

Ruck Ventilatoren

Ruck Ventilatoren ISOR Assembly instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.