
EI Link - Three Phase
Quick Start Guide - TSS-3PS
Pg 2 of 3
1. Run the grid and load wires through the strain relief
into the EI Link.
2. Strip 12 mm off wire ends and crimp on 16mm2
ferrule.
3. Connect the wire ends into the appropriate GRID and
LOAD terminals. Torque to 1.5 NM.
4. Crimp the grounding cable with provided 16mm2
grounding terminal.
5. Connect grounding cable to ground bar and torque to
1.5 NM.
6. Terminate the opposite end of the grid and load cable
at the main service panel and backup panel with the
appropriate tools.
EI Link
EI Link
Grounding Cable
EI Inverter
TAP
3.1.2 GRID and Load
Load Grid
R (13) S (14) T (15) N (16) R (26) S (27) T (28) N (29) PE2
3.1.3 TS4
Scan here for the TS4 downloads
!
1. Install the TS4 module-level power electronics
(MLPE) on the back of the PV modules.
2. Connect the PV module to the TS4 input
conductors.
3. Connect the TS4 output conductors together to
form a string.
4. If using the TS4-A-F/TS4-A-2F, no additional steps
are necessary.
5. Remove each barcode sticker from the TS4-A-O
and place in the grid on the last page of this
document in the position and orientation of the
module as it is in the array. If using the TS4-A-F/
TS4-A-2F, this step is not necessary.
CAUTION - To prevent damage to the TS4, always connect PV modules to the TS4 input before connecting output
conductors in the string. Refer to the TS4 Installation Manuals for the TS4 installation requirements.
3.1.4 Connect PV Array
1. Run the PV wires through the strain relief into the EI
Link.
2. Strip 12 mm off wire ends and crimp them with the
provided 6mm2ferrules.
3. Press the wires into the appropriate PV + and PV -
terminals (Refer to the wiring diagram at the back of
the EI Link door.
PV
PV 1+ PV 1- PV 1+ PV 1- PV 2+ PV 2-
PV
3.1.6 Connect External Grounding
1. Connect the grounding cable from the
EI Inverter to the EI Link as shown.
2. Torque to 1.5 NM
3. Connect the grounding cable from the
EI BMS (when installed) to the EI Link
as shown.
4. Torque to 1.5 NM
3.1.5 TAP
1. Using CAT5/6, crimp the wires onto the RJ-45 male plug using the pin out diagram below.
2. Connect the other end of the wires to the corresponding terminals in the TAP as shown.
RJ45
Pin Wire color (T568B) Signal denition Function
1 White/Orange GND 12vDC- from CCA
2 Orange
3 White/Green VCC 12VDC + from CCA
4 Blue
5 White/Blue N/A Not in use
6 Green
7 White/Brown RS485B RS485 communication
with CCA
8 Brown RS485A
G1 G2 G2 G4
12345678
T568B
RJ-45 Male Plug
Load
Ethernet E-stop
COMTAP
AntennaMeter
Load Grid
PN: 002-00110-00 | REV 1.0 | Oct. 21, 2022