10 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Product Overview
4.2 Environmental Conditions/Protection Class
Environmental conditions
Operating temperature (surrounding air temperature) -20…+60 °C (vertical installation)
Plug-in modules and USB devices may
limit max temperature to +50 °C
EN 60068-2-14
Storage temperature -20…+70 °C EN 60068-2-1
EN 60068-2-2
EN 60068-2-14
Operating and storage humidity 5…85 % RH non-condensing EN 60068-2-30
Vibrations 5…9 Hz, 7 mmp-p
9…150 Hz, 1 g
EN 60068-2-6
Shock ± 50 g, 11 ms, 3 pulses per axis EN 60068-2-27
Protection class
Front panel IP66 EN 60529
Rear IP20 EN 60529
4.3 Electromagnetic Compatibility (EMC)
Electromagnetic Compatibility (EMC)
Radiated disturbance test Class A CISPR 22, CISPR 16-2-3
Electrostatic discharge immunity test 8 kV (air electrostatic discharge)
4 kV (contact electrostatic discharge)
EN 61000-4-2
Radiated, radio-frequency,
electromagnetic field immunity test
80 MHz …1 GHz, 10 V/m
1,4 GHz … 2 GHz, 3 V/m
2 GHz … 2.7 GHz, 1 V/m
EN 61000-4-3
Burst immunity test ± 2 kV DC power port
± 1 kV signal line
EN 61000-4-4
Surge immunity test ± 0,5 kV DC power port (line to earth)
± 0,5 kV DC power port (line to line)
± 1 kV signal line (line to earth)
EN 61000-4-5
Immunity to conducted disturbances inducted by
radiofrequency field
0.15…80 MHz, 10 V EN 61000-4-6
Power frequency magnetic field
immunity test
Enclosure, 50/60Hz, 30A/m EN 61000-4-8
Voltage dips, short interruptions and
voltage variations immunity test
Port: AC mains; Level:
100 % duration: 1 cycle and 250 cycles (50 Hz);
40 % duration: 10 cycles (50 Hz);
70 % duration: 25 cycles (50 Hz);
Phase: 0°-180°
Test executed on the 230 VAC side of the power supply EN 61000-4-11
Port: DC mains; Level:
0% duration: 10ms 20 spaces by 1s
Test executed on the 24Vdc of the EUT EN 61000-4-29
Durability information
Backlight service life (LED type) 40.000 hours or more
(Time of continuos operation until the brightness of the backlight
reaches 50 % of the rated value when the surrounding air tempera-
ture is 25 °C).