Care and
Maintenance
The Tyco®Rapid Response™, Series
LFII (TY2334) must be maintained and
servicedin accordancewiththe follow-
ing instructions:
NOTES
Absence of an Escutcheon Plate may
delay the sprinkler operation in a fire
situation.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
which it controls, permission to shut
down the affected fire protection sys-
tem must be obtained from the proper
authorities and all personnel who may
be affected by this action must be no-
tified.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed.Also,replaceanysprinklerthat
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
NOTE
The owner must assure that the sprin-
klers are not used for hanging of any
objects and that thesprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Automaticsprinkler systemsshouldbe
inspected, tested, and maintained by a
qualified Inspection Service in accord-
ance with local requirements and/or
national codes.
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
havebeensubjecttomisuse,improper
installation,corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP’s sole
option. TFBP neither assumes, nor
authorizesanypersontoassumeforit,
any other obligation in connection with
the sale of products or parts of prod-
ucts.TFBP shall not be responsiblefor
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer’s repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect,special or consequentialdam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP’s liability exceed an amount
equal to the sales price.
Theforegoingwarrantyismadeinlieu
of any and all other warranties, ex-
press or implied, including warranties
ofmerchantabilityandfitnessforapar-
ticular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Contact your local
distributor for availability..
Sprinkler Assembly:
Series LFII (TY2334), K=4.4, Residen-
tial Horizontal Sidewall Sprinkler with
(specify) temperature rating and
(specify) finish, P/N (specify).
155°F/68°C or
Chrome Plated . . . . . . . . . P/N 51-215-9-155
155°F/68°C
White Polyester. . . . . . . . . P/N 51-215-4-155
155°F/68°C
Natural Brass. . . . . . . . . . . P/N 51-215-1-155
175°F/79°C or
Chrome Plated . . . . . . . . . P/N 51-215-9-175
175°F/79°C
White Polyester. . . . . . . . . P/N 51-215-4-175
175°F/79°C
Natural Brass. . . . . . . . . . . P/N 51-215-1-175
Recessed Escutcheon:
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (spec-
ify*).
*Refer to Technical Data Sheet TFP770.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
Page6of6 TFP412
© 2007 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446