
TFP510
Page 8 of 10
Absence of the outer piece of an es-
cutcheon, which is used to cover a
clearance hole, can delay the time to
sprinkler operation in a re situation.
A Vent Hole is provided in the Bulb
Seat (Ref. Figures 1 and 2) to indicate
if the Dry-Type Sprinkler is remaining
dry. Evidence of leakage from the Vent
Hole indicates potential leakage past
the Inlet seal and the need to remove
the sprinkler to determine the cause of
leakage (e.g., an improper installation
or an ice plug). Close the re protec-
tion system control valve and drain the
system before removing the sprinkler.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro
-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers before, during, and
after installation. Sprinklers damaged
by dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any sprinkler that has a
cracked bulb or that has lost liquid from
its bulb. (Ref. Installation Section.)
The owner is responsible for the in-
spection, testing, and maintenance of
their re protection system and devices
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association
(e.g., NFPA 25), in addition to the stan-
dards of any other authorities having
jurisdiction. Contact the installing con-
tractor or product manufacturer with
any questions.
Automatic sprinkler systems are recom-
mended to be inspected, tested, and
maintained by a qualied Inspection
Service in accordance with local re-
quirements and/or national codes.
Limited
Warranty
For warranty terms and conditions,
visit www.tyco-re.com.
Step 1. Install pendent sprinklers only
in the pendent position, and install up-
right sprinklers only in the upright posi-
tion. The deector of a pendent or up-
right sprinkler must be parallel to the
ceiling.
Install horizontal sidewall sprinklers in
the horizontal position with their cen-
terline of waterway perpendicular to
the back wall and parallel to the ceil-
ing. Ensure the word “TOP” on the De-
ector faces the ceiling.
Step 2. With a non-hardening pipe-
thread sealant such as TEFLON tape
applied to the Inlet threads, hand-tight-
en the sprinkler into the sprinkler tting.
Step 3. Wrench-tighten the sprinkler
using either:
•
a pipe wrench on the Inlet Band or the
Casing (Ref. Figures 1 and 2)
•
the W-Type 7 Sprinkler Wrench on the
Wrench Flat (Ref. Figure 16)
Apply the Wrench Recess of the
W-Type 7 Sprinkler Wrench to the
Wrench Flat.
Note: If sprinkler removal becomes
necessary, remove the sprinkler us-
ing the same wrenching method not-
ed above. Sprinkler removal is easier
when a non-hardening sealant was
used and torque guidelines were fol-
lowed. After removal, inspect the sprin-
kler for damage.
Step 4. After installing the ceiling or
wall and applying a ceiling nish, slide
on the outer piece of the escutcheon
until it comes in contact with the ceil-
ing or wall. Do not lift the ceiling panel
out of its normal position.
When using the Deep Escutcheon,
hold the outer piece in contact with
the mounting surface (ceiling or wall).
Then rotate the inner piece approxi-
mately 1/4 turn with respect to the out-
er piece, to hold the Deep Escutcheon
rmly together.
Care and
Maintenance
The TYCO Series DS-1 Dry-Type
Sprinklers, 5.6K Pendent, Upright, and
Horizontal Sidewall, Quick Response (3
mm bulb) and Standard Coverage must
be maintained and serviced in accor-
dance with this section.
Before closing a re protection system
main control valve for maintenance
work on the re protection system that
it controls, obtain permission to shut
down the affected re protection sys-
tems from the proper authorities and
notify all personnel who may be affect-
ed by this action.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
DS-1 Dry-Type Sprinklers
When ordering TYCO Series DS-1
Dry-Type Sprinklers, 5.6K Pendent,
Upright, and Horizontal Sidewall, Quick
Response (3 mm bulb) and Standard
Coverage, specify the following
information:
• SIN:
Pendent – TY3935 or TY3235
Sidewall – TY3735 or TY3335
Upright – TY3135
• 5.6 K-factor
• Deector Style:
Upright, Pendent, or Horizontal Sidewall
•
Quick Response, Standard Coverage,
Dry-Type Sprinkler
• Order Length:
Dry-Type Sprinklers are furnished based
upon Order Length as measured per
Figures 3 through 10. After taking the
measurement, round it to the nearest
1/4 inch increment.
• Inlet Connections:
3/4 Inch NPT, 1 Inch NPT, or ISO 7-R 1
• Temperature Rating
• Sprinkler Finish
•
Escutcheon Style and Finish, as
applicable
• Part Number (P/N) from Table D
The Upright Sprinkler without an
Escutcheon (TY3135) is available in
1 Inch NPT only.
Part Numbers are for 3/4 inch and
1 inch NPT standard order sprin-
klers. Orders for all other sprinkler
assemblies must be accompanied
by a complete description. Refer to
the Price List for a complete listing of
Part Numbers.
Sprinkler Wrench
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
Sprinkler Boot
Specify: Model DSB-2 Dry Sprinkler
Boot, P/N 63-000-0-002
This Part Number includes one (1)
Boot, two (2) Strap Ties, and 1/3 oz. of
Adhesive (a sufcient quantity for in-
stalling one boot).