corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed.Also,replaceanysprinklerthat
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommendedtobeinitiallyperformedfor
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify theintegrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
havebeensubject to misuse, improper
installation,corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP’s sole
option. TFBP neither assumes, nor
authorizesanypersontoassumeforit,
any other obligation in connection with
the sale of products or parts of prod-
ucts.TFBPshall notberesponsiblefor
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer’s repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect,specialor consequentialdam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP’s liability exceed an amount
equal to the sales price.
Theforegoingwarrantyismadeinlieu
of any and all other warranties, ex-
press or implied, including warranties
ofmerchantabilityand fitnessforapar-
ticular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Please specify the
Sprinkler Identification Number (SIN),
quantity, and temperature rating. Re-
fer to the Price List for complete listing
of Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: TY4232, (specify tempera-
ture rating), Extended Coverage Pen-
dentSprinklerwith(specifyfinish),P/N
(specify).
135°F/57°C
Natural Brass . . . . . . . . . . . . . PSN 50-801-1-135
White Coated . . . . . . . . . . . . . PSN 50-801-4-135
White (RAL9010)*. . . . . . . . . . PSN 50-801-3-135
Chrome Plated . . . . . . . . . . . . PSN 50-801-9-135
155°F/68°C
Natural Brass . . . . . . . . . . . . . PSN 50-801-1-155
White Coated . . . . . . . . . . . . . PSN 50-801-4-155
White (RAL9010)*. . . . . . . . . . PSN 50-801-3-155
Chrome Plated . . . . . . . . . . . . PSN 50-801-9-155
*Eastern Hemisphere sales only.
Recessed Escutcheon:
Specify: Style (30 or 40) Recessed
Escutcheon with (specify finish), P/N
(specify).
Style 30 Recessed Escutcheon
Chrome Plated . . . . . . . . . . . . PSN 56-705-9-011
White Color Coated . . . . . . . . PSN 56-705-4-011
White (RAL9010)*. . . . . . . . . . PSN 56-705-3-011
Brass Plated . . . . . . . . . . . . . . PSN 56-705-2-011
Style 40 Recessed Escutcheon
Chrome Plated . . . . . . . . . . . . PSN 56-700-9-010
White Color Coated . . . . . . . . PSN 56-700-4-010
White (RAL9010)*. . . . . . . . . . PSN 56-700-3-010
Brass Plated . . . . . . . . . . . . . . PSN 56-700-2-010
*Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 3 Sprinkler Wrench,
P/N 56-895-1-001.
Specify: W-Type 23 Recessed Sprin-
kler Wrench, P/N 56-000-6-838.
TFP223 Page 5 of 6