CONNECTING POWER
WARNING:
Risk of electric
shock. Can cause injury or death.
Open all local and remote electric
power disconnect switches and
verify with a voltmeter that power
is o before working within the unit
electric enclosures.
NOTE:
The vNSA requires
properly-grounded (earthed)
100–240VAC, single-phase
power, 50Hz or 60Hz. The ground
wire for the power lead must be
wired to the earth ground terminal
stud located next to the universal
power supply.
This equipment must be installed
by a qualified and certified
electrician who must review and
approve customer-supplied wiring
and circuit breakers and verify
correct input and grounded
(earthed) connections to ensure
compliance with technical
standards and national and local
electrical codes
The vNSA includes a power supply
with an adapter that must be wired
for the power connection.
NOTE:
Unplug the connector prior
to installation. You may use a field-
supplied power cord in place of the
provided hardwire adapter.
NOTE:
The maximum wire size is
16AWGstranded.
1. Connect the ground wire.
Locate the earth-ground
terminal inside the vNSA
enclosure and connect the
incoming electrical-service
ground wire to the ground
terminal.
2. Remove the adapter
cover.
Loosen the screw on the
adapter cover and remove the
cover.
3. Remove the wire clamp.
Loosen the screws in the wire
clamp and remove the clamp.
4. Secure wires in adapter.
Feed the wires through the
rubber grommet including the
ground wire from the earth-
ground terminal. Strip the
insulation from each wire to
expose 5/8 in. (16 mm), wrap
the wire around the appropriate
terminating screw, and tighten.
The screws are labeled as
follows:
• N = Neutral for 120-V
applications or Line for
220-V applications (white
wire)
• E = Earth ground, from the
earth-ground terminal
(green wire)
• L = Line (black wire)
5. Replace adapter cover.
Replace the wire clamp and
secure it with the 2 screws,
then replace the adapter cover
and tight the screw.
CONNECTING TO vNSA
To connect devices to vNSA, use
CAT5 (or better) with RJ45
connectors.
1
Wire clamp
Cover screw
2
34