manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. WaterLogic
  6. •
  7. Water Filtration System
  8. •
  9. WaterLogic WL100 Operating instructions

WaterLogic WL100 Operating instructions

WL100ManualPage50Revision:1‐14‐2019
DISPENSINGTROUBLESHOOTINGINDEX

1. Irregular/IntermittentDispensingfromOneSide

2. Dispensingwon'tstopwhennotholdingtheDispensingButton

3. SteadyDripoutofFaucet

4. HotWaterorSteamcomingoutofboththeFaucetandtheVentHole

5. HotWatercomingoutofFaucetVentHole

6. RestrictedFlowofHotWater

7. HotWaterDripoutofFaucet

8. DispensesHotandColdWateratthesametime

9. Nocoldwateravailable

10. Waterdoesnotdispensefromunit

11. ColdWaterdispensesfromFaucetandVentOutletSimultaneously

12. Smallamountofwaterperiodicallydispensesfromfaucetautomatically

13. DispenseButtonsStick

14. Run‐On‐Watercontinuestodispenseoutoffaucetafterreleasingthedispense
button


AlsoincludesrelatedinstructionforHotTankDescaling



WL100ManualPage51Revision:1‐14‐2019
DISPENSINGTROUBLESHOOTING

1. Irregular/IntermittentDispensingfromoneside


PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
theWL100WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawaterpressure
gauge.

Additionalmethodofverificationistoturnoffwatertounitand
pressthedispensebutton.DoestheSolenoidopenwithoutwater
pressuretotheunit?ListenforSolenoidtoactivate,notto
mistakenforthebutton“click”.

Adjustwaterpressureto40‐60psi.Thecorrectinputwater
pressureiscriticaltotheperformanceoftheunittoallow
Solenoidstoopen.

Looseorbadconnectionon
theFrontDispensingPCBor
SolenoidConnector
Checkthattheyareconnectedproperlyandtightened.
Solenoid
IfboththeWaterPressureandPCBhavebeenruledout,thenitis
theSolenoid.

ReplaceSolenoid.
Dispensingbuttonisbrokenon
PCB
CheckPCBforlooseordamagedbutton.ReplacePCBas
necessary.


WL100ManualPage52Revision:1‐14‐2019

2. DispensingWon’tStopWhenNotHoldingtheDispensingButton


PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
theWL100WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawaterpressure
gauge.

Additionalmethodofverificationistoturnoffwatertounitand
pressthedispensebutton.DoestheSolenoidopenwithoutwater
pressuretotheunit?ListenforSolenoidtoactivate,notto
mistakenforthebutton“click”.

Adjustwaterpressureto40‐60psi.Thecorrectinputwater
pressureiscriticaltotheperformanceoftheunittoallow
Solenoidstoopen.

Stemoftheswitchisbroken
onthePCB‐PrintedCircuit
Board.
RemoveDisplayPCandinspectswitches.

ReplaceDisplayPCBifswitchesappearbroken.

PartNumber20‐0040(FactoryPNEN‐6130)
DebrisintheSolenoid InspectSolenoidfordebrisandcleanoutasneeded.
DispensingButtonStuck
DirtorForeignmaterialisfillingthegaparoundthepush‐buttons.
Inspectthepushbuttonsandcleansurroundingarea.Inspect
faucetassemblyinsidetheunitandcleanasnecessary.

3. SteadyDripOutofFaucet


PossibleReason Solution
DebrisinSolenoid InspectSolenoidfordebrisandcleanoutasneeded.


WL100ManualPage53Revision:1‐14‐2019
4. HotWaterorSteamComingoutofboththeFaucetandVentHole


PossibleReason Solution
ImproperTubingattachment
fromtheHotTanktofaucetor
viceversa.
CheckthattheTubingisconnectedfromTankOutletstocorrect
Faucetattachments.ConnectTubingtoOutletsasneeded.

5. HotWaterComingoutofFaucetVentHole


PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
theWL100WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawaterpressure
gauge.

Additionalmethodofverificationistoturnoffwatertounitand
pressthedispensebutton.DoestheSolenoidopenwithoutwater
pressuretotheunit?ListenforSolenoidtoactivate,notto
mistakenforthebutton“click”.

Adjustwaterpressureto40‐60psi.Thecorrectinputwater
pressureiscriticaltotheperformanceoftheunittoallow
Solenoidstoopen.

Impropertubingattachment
fromthetanktofaucetorvice
versa.
Verifytubingisconnectedproperlyfromtankoutletstocorrect
faucetattachments.
HotTankoutletholeisscaled
over.
InspectandDescaleTankasneeded.

SeeHotTankDescalingInstructionsthatareincludedfurther
belowinthisTroubleshootingSection.

Expansionchamberisnot
sealedproperly. ReplacetheHotTank.


WL100ManualPage54Revision:1‐14‐2019
6. RestrictedFlowofHotWater


PossibleReason Solution
PartiallyclosedWaterSupplyValve
totheunit. OpenWaterSupplyValve.
HotTankoutletholeisscaledover.
DescaleTank.

SeeHotTankDescalingInstructionsthatareincluded
furtherbelowinthisTroubleshootingSection.

Tubingiscreasedorhasa“kink”init. Inspectandreplacetubingasnecessary.
Faucetnipplescreenmeshhas
obstruction(s)
Unscrewfaucetnipplefromfaucetandremoveany
obstruction(s)fromscreenmesh.
ExhaustedFilter ReplacetheFilter
SolenoidconnectiontotheDisplay
PCB
Turnpoweroff;unplugtheunitandvisuallyinspect
SolenoidconnectionsintotheDisplayPCB.Verifythe
solderingpointsonconnectionsaresecureintotheboard.

RemovethePCBtoinspectthefrontoftheboard.
SolenoidValveisMalfunctioning Inspectvalvecomponentsforproperfunction.Replaceas
necessary.



WL100ManualPage55Revision:1‐14‐2019
7. HotWaterDripoutofFaucet


PossibleReason Solution
SmallOutletVentHolesusceptibletoscale
buildup.
DescaleTank.

SeeHotTankDescalingInstructionsthatareincluded
furtherbelowinthisTroubleshootingSection.


AllWaterlogicHotTankshaveabuiltinVentor
ExpansionChamberinthetopofthetankexceptfor
WL270(GF)units.

TheVentChamberallowsforexpansionofthewater
whenitisheated.

Thechambersareseparatedbyawelded‐intank
baffle.

Wateralwaysflowsintothebottomofthetankand
outthetoptothefaucet.

TheHotTankoutlettubehasarestrictorinitsbase.
Thisensuresthereservoirisalwaysfullbyallowing
morewaterinthanout.

Thereisasmallholeinthesideofthetankoutlettube
thatallowsairandwatertopassintothevent
chamberasitisheated.

Waterintheventchamberissuctionedbackthrough
theoutlettubeventholewhenwaterisdispensed.

Expansionofwaterasitisheatedinthereservoirwill
pushthewateroutthefaucetwhentheoutlettube
ventholebecomespluggedwithdebrisorscale.

ThesmallOutletVentHoleissusceptibletoscalebuild
upandisakeyindicatorthatdescalingisrequired.

ItiscriticaltodescaletheHotTankthroughthevent
lineandoutletlineonaregularbasistopreventthis
problem.

Descalingthroughtheinletand/oroutletlinesonly
willnotcleantheventchamberandoutletventhole
properly.

WL100ManualPage56Revision:1‐14‐2019
8. DispensesHotandColdWaterattheSameTime


PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
theWL100WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawater
pressuregauge.

Additionalmethodofverificationistoturnoffwatertounit
andpressthedispensebutton.DoestheSolenoidopen
withoutwaterpressuretotheunit?ListenforSolenoidto
activate,nottomistakenforthebutton“click”.

Adjustwaterpressureto40‐60psi.Thecorrectinputwater
pressureiscriticaltotheperformanceoftheunittoallow
Solenoidstoopen.

HotorColdSolenoidisstuck
open.
RemoveTopCover.

CheckHotSolenoid:Dispensecoldwaterandvisuallyinspect
tubingforwaterflowfrombothtanks.

CheckColdSolenoid:Disconnectelbowfromoutletofcold
Solenoid.Selecthotwateranddispense(quicklyreleasing
dispensingbuttontoavoidmuchwatercomingoutofcold
Solenoid.

ReplaceSolenoidasnecessary.


WL100ManualPage57Revision:1‐14‐2019

9. NoColdWaterAvailable


PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
theWL100WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawater
pressuregauge.

Additionalmethodofverificationistoturnoffwatertounit
andpressthedispensebutton.DoestheSolenoidopen
withoutwaterpressuretotheunit?ListenforSolenoidto
activate,nottomistakenforthebutton“click”.

Adjustwaterpressureto40‐60psi.Thecorrectinputwater
pressureiscriticaltotheperformanceoftheunittoallow
Solenoidstoopen.

ClosedWaterSupplyValve OpentheWaterSupplyValve
ColdWaterSolenoidValve
malfunction Inspectthevalvecomponentsforproperfunctionality.
RedHeaterandCompressor
Switchonunitisoff.


TurnRedHeaterandCompressorSwitchon.
I=ON


Looseconnection(s)onthe
DisplayPCB
Turnpoweroff;unplugtheunitandvisuallyinspectSolenoid
connectionsintotheDisplayPCB.Verifythesolderingpoints
onconnectionsaresecureintotheboard.

RemovethePCBtoinspectthefrontoftheboard.
ExhaustedFilter Replacefiltersasneeded.


WL100ManualPage58Revision:1‐14‐2019
10. WaterdoesnotdispensefromUnit


PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
theWL100WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawater
pressuregauge.

Additionalmethodofverificationistoturnoffwatertounit
andpressthedispensebutton.DoestheSolenoidopen
withoutwaterpressuretotheunit?ListenforSolenoidto
activate,nottomistakenforthebutton“click”.

Adjustwaterpressureto40‐60psi.Thecorrectinputwater
pressureiscriticaltotheperformanceoftheunittoallow
Solenoidstoopen.

ClosedWaterSupplyValve OpentheWaterSupplyValve.
Theunitisnotproperly
pluggedintoelectricaloutlet
Checkelectricaloutletconnection,orforblowncircuit
breaker.
RedHeaterandCompressor
Switchonunitisintheoff
position


TurnRedHeaterandCompressorswitchon.
I=ON


15AmpFuseBlown Replacethe15AmpFuseasneeded.
HotandColdSolenoid
connectionsintotheDisplay
PCBareloose.
Turnpoweroff;unplugtheunitandvisuallyinspectSolenoid
connectionsintotheDisplayPCB.Verifythesolderingpoints
onconnectionsaresecureintotheboard.

RemovethePCBtoinspectthefrontoftheboard.
ExhaustedFilter Replacefiltersasneeded.


WL100ManualPage59Revision:1‐14‐2019

11. ColdWaterDispensesfromFaucetandVentOutletSimultaneously


PossibleReason Solution
Impropertubingattachment
fromthetanktofaucetorvice
versa
Verifytubingisconnectedproperlyfromtankoutletsto
correctfaucetattachments.
ScalehasformedinsideCold
Tankoutlettube.
RemoveColdWaterOutletTubefromColdTanktoFaucet,
cleanorreplaceasnecessary.
ExpansionchamberinCold
Tankisnotsealedproperly. ReplaceColdTank.

12. SmallAmountofWaterPeriodicallyDispensesfromFaucetAutomatically


PossibleReason Solution
Toomuchwaterpressure.
Recommend40to60psifor
theWL100WaterTreatment
Systemtooperateproperly.
Checkwaterpressureattheinletbulkheadwithawater
pressuregauge.

Additionalmethodofverificationistoturnoffwatertounit
andpressthedispensebutton.DoestheSolenoidopen
withoutwaterpressuretotheunit?ListenforSolenoidto
activate,nottomistakenforthebutton“click”.

Adjustwaterpressureto40‐60psi.Thecorrectinputwater
pressureiscriticaltotheperformanceoftheunittoallow
Solenoidstoopen.

ColdorHotWaterSolenoid
valvemalfunction
Inspectvalvecomponentsforproperfunction.Replaceas
necessary.
ObstructioninSolenoid
housingispreventingproper
sealingofcomponent.
Pre‐determinewhetherwaterbeingdispensedishot/cold.
Isolatethewatersupply;pushtheDISPENSEbuttonto
releasethelinepressure,andremovethecoilaffixedtothe
Solenoidstem.

RemovethestemfromtheSolenoidhousingandallowwater
fromthetanktoflushoutthecontaminant(s).


WL100ManualPage60Revision:1‐14‐2019

13. DispenseButtonsStick


PossibleReason Solution
DirtorForeignmaterialis
fillingthegaparoundthe
push‐buttons.
Inspectthepushbuttonsandcleansurroundingarea.

Inspectfaucetassemblyinsidetheunitandcleanas
necessary.

14. RunOn–Watercontinuestodispenseoutoffaucetafterreleasingthe
dispensebutton
Reason
“RunOn”or“CarryOn”ispresentinallWaterlogicpressurefedunitswithoutoutlet
Solenoids.

“RunOn”isdefinedistheamountofwaterthatcontinuestodispenseoutofthefaucetafter
releasingthedispensebutton.

RunOnexistsbecausethetankspressurizeaswaterisbeingdispensed.EveryWaterlogictank
hasanoutletrestrictortoensurethetanksremainfullofwaterandwateriscontrolledasitis
releasedtothefaucet.TheinletSolenoidcontrolsflowintothetanks.Thetankswill
“depressurize”oncethedispensebuttonisreleasedtheinletSolenoidcloses.Asmallamount
ofwaterwill“RunOn”throughthefaucetasthetankdepressurizestoatmospheric
conditions.

Typical“RunOn”is2‐3seconds.

“RunOn”canbereducedbyinstallingapressurelimitingdevice.

Theamountofinletorsupplypressuredirectlyimpactstheamountof“RunOn”asquantified
below.

WLCPLabTestingofRnOn7‐31‐2013
Pressure Pressure Time FlowRate RunOn
StaticPSI DynamicPSI 4Liters I/min Seconds
68 40 61 2.9508197 3
50 30 72 2.5 2.5
32 20 92 1.956217 2
Pressuremeasuredatinletlinetounit.Staticwithunitclosed.Dynamicwithunit
dispensingcoldwater.
Nofilterswereinstalledinunit.




WL100ManualPage61Revision:1‐14‐2019
HOTTANKDESCALINGINSTRUCTIONS

TheHotTankrequiresremovalofmineraldeposits(descaling)onaregularbasis.Typically
descalingshouldtakeplaceevery6to12monthstopreservethelong‐termhealthofyourunit.

Usenon‐toxiccleanersuchasScaleKleen,DEZCAL,20%CitricAcidSolution,orUndilutedVinegar
Solutiontoremovemineraldepositsasdirectedbythemanufacturerdependinguponfiltration
andlocalwaterconditions.

Descalingisanimportantprocessthatremovescalciumdeposits,orscale,thatcanbuildup
insideatankovertime.Calciumandscaleisnon‐toxicbutleftunattendedwillhinderyourunit’s
performance.


WARNING!PERSONALPROTECTIVEEQUIPMENTREQUIRED.Alwaysensureproper
ventilationanduserubberornitrileglovesandeyeprotectionwhenusingchemicals.Referto
MaterialSafetyDataSheetforspecificrequirementsofeachproduct.

CAUTION!STAINLESSSTEELTANKDESCALING.
TheHotTankismadefromstainlesssteel.Ensuredescalingsolutioniscompatiblewith
stainlessandalwaysflushtheunitcompletely.Disposeinanenvironmentallysafemanner.

MaterialsNeeded:
 PersonalProtectiveEquipment.RubberorNitrileSafetyGlovesandProtectiveEyewear
 PhillipsScrewdriver
 TemperatureGauge
 WaterPitcherorContainertocollectwaterfromthefaucet
 19Liter(5gallon)containerordrainbasin
 CitricAcidBasedCleaner
 ¼”PlasticTubing,atleast4feetinlength,andassorted¼”quickconnectfittings
 SanitizingCartridge–anemptyWaterlogicFilterwithcartridgeremoved
 FoodColoring

1. BypassFiltersbeforestartingtheDescalingProcedure.

2. Putdescalerperdirectionsand3dropsoffoodcoloringintothedescalingcartridge.

3. ConnectDescalingCartridgetotheinletwatersupplyandconnecttoInletBulkheadFittingonthe
backofWL100WaterTreatmentSystem.TurnonWaterSupply.

4. SelectHotWateranddepresstheMainDispensingButtonontheFrontControlPaneluntil
descalingsolution(coloredwater)comesoutoftheFaucet.Containeranddrainbasinwillbe
requiredtocatchwaterfromthefaucet.

5. TurnoffwatersupplyandremoveSanitizingCartridgefrominletwatersupply.Reconnectwater
supplytoInletFitting.

WL100ManualPage62Revision:1‐14‐2019

6. AllowdescalingsolutiontoremainintheHotTankfor15minutes(lengthoftimemayvary
dependingonwaterconditions).

7. Placeapitcher,catchbasinorothercontainerunderthefaucetoftheWL100WaterTreatment
System.

8. FlushtheHotTankuntilwaterrunsclear.

9. OnceclearWaterdispensesfromtheFaucet,theHotTankhasbeendescaled.Alwaysensure
unitisperformingtothecustomer’ssatisfaction.

10. ReplaceFilters.


WARNING!HOTWATER.UnitproducesHotWaterupto87
o
C(189
o
F).Waterabove52
o
C
(125
o
F)cancausesevereburnsorscalding.Hotwatershouldbedispensedcarefullyinto
insulatedcontainertoavoidinjury.

CAUTION!MUSTREPLACEHOTTANKEVERY3‐5YEARSDEPENDINGONUSAGE.TheHot
Tankanditscontrolsmustbereplacedaminimumofevery3‐5yearsdependingonusageto
ensureefficientanddependableoperation.


WARNING!REINSTALLALLPANELSANDCOVERS.AlwaysreinstallallPanels,Protective
Covers,andFastenersafterservicingequipment.Failuretodosocouldresultinsevere
personalinjuryandwillvoidthecertificationsandwarrantyoftheequipment.


Other manuals for WL100

7

Other WaterLogic Water Filtration System manuals

WaterLogic WL2FLT User manual

WaterLogic

WaterLogic WL2FLT User manual

WaterLogic WL100 Operating instructions

WaterLogic

WaterLogic WL100 Operating instructions

WaterLogic WL270 User manual

WaterLogic

WaterLogic WL270 User manual

WaterLogic WL380 User manual

WaterLogic

WaterLogic WL380 User manual

WaterLogic WL3 IT User manual

WaterLogic

WaterLogic WL3 IT User manual

WaterLogic WL380 Operating instructions

WaterLogic

WaterLogic WL380 Operating instructions

WaterLogic WL15-HCS User manual

WaterLogic

WaterLogic WL15-HCS User manual

WaterLogic WL500 - Sparkling User manual

WaterLogic

WaterLogic WL500 - Sparkling User manual

WaterLogic escowa Purus iQ3 User manual

WaterLogic

WaterLogic escowa Purus iQ3 User manual

WaterLogic WL100 Reference guide

WaterLogic

WaterLogic WL100 Reference guide

WaterLogic WL7 User manual

WaterLogic

WaterLogic WL7 User manual

WaterLogic WL3 FX User manual

WaterLogic

WaterLogic WL3 FX User manual

WaterLogic WL2FL FIREWALL User manual

WaterLogic

WaterLogic WL2FL FIREWALL User manual

WaterLogic WL7 User manual

WaterLogic

WaterLogic WL7 User manual

WaterLogic F-FWEG1-M-A-NT Series User manual

WaterLogic

WaterLogic F-FWEG1-M-A-NT Series User manual

WaterLogic PUREZZA WL2FL FIREWALL User manual

WaterLogic

WaterLogic PUREZZA WL2FL FIREWALL User manual

WaterLogic Countertop Pure K-FU-00S20-00C1L-13-0-XXX User manual

WaterLogic

WaterLogic Countertop Pure K-FU-00S20-00C1L-13-0-XXX User manual

WaterLogic WL100 Operating instructions

WaterLogic

WaterLogic WL100 Operating instructions

WaterLogic WL250 User manual

WaterLogic

WaterLogic WL250 User manual

WaterLogic Water Filtration Systems User manual

WaterLogic

WaterLogic Water Filtration Systems User manual

WaterLogic WL850HV User manual

WaterLogic

WaterLogic WL850HV User manual

WaterLogic WL500 - Sparkling User manual

WaterLogic

WaterLogic WL500 - Sparkling User manual

WaterLogic WL7 FW Reference guide

WaterLogic

WaterLogic WL7 FW Reference guide

WaterLogic WLH2 Classe Operating and maintenance manual

WaterLogic

WaterLogic WLH2 Classe Operating and maintenance manual

Popular Water Filtration System manuals by other brands

Neo-Pure TL3-A502 manual

Neo-Pure

Neo-Pure TL3-A502 manual

Bem Lora UF operation instruction

Bem

Bem Lora UF operation instruction

Master Water Conditioning FES-30T Installation and operation manual

Master Water Conditioning

Master Water Conditioning FES-30T Installation and operation manual

Ispring WF150K Installation instructions & user manual

Ispring

Ispring WF150K Installation instructions & user manual

Zip HydroTap G5 Touch-Free Wave Quick start installation guide

Zip

Zip HydroTap G5 Touch-Free Wave Quick start installation guide

Perfect Water Technologies Tap Master Jr Series Installation & service manual

Perfect Water Technologies

Perfect Water Technologies Tap Master Jr Series Installation & service manual

BWT BWT Multi HM Installation and operating manual

BWT

BWT BWT Multi HM Installation and operating manual

OptiPure OP350 Installation, operation & maintenance manual

OptiPure

OptiPure OP350 Installation, operation & maintenance manual

JRC NSVS1103 manual

JRC

JRC NSVS1103 manual

Ispring DF1 Series user manual

Ispring

Ispring DF1 Series user manual

Ecosoft SENSE Installer and user guide

Ecosoft

Ecosoft SENSE Installer and user guide

EcoWater ECR 3000R20 owner's manual

EcoWater

EcoWater ECR 3000R20 owner's manual

SY-KLONE RESPASC installation instructions

SY-KLONE

SY-KLONE RESPASC installation instructions

Evince ELITE EV-ELT-948-1.0 owner's manual

Evince

Evince ELITE EV-ELT-948-1.0 owner's manual

Canature 475 Pro Series Installation & operation manual

Canature

Canature 475 Pro Series Installation & operation manual

LG WCD56US2 owner's manual

LG

LG WCD56US2 owner's manual

Wisy Optima installation instructions

Wisy

Wisy Optima installation instructions

Watts E-Treat ETREATWCS Installation, operation and maintenance manual

Watts

Watts E-Treat ETREATWCS Installation, operation and maintenance manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.