WIKA air2guide A2G-70 User manual

DE
EN
Operating instructions
Betriebsanleitung
Ventilation duct sensor for relative humidity and
temperature, model A2G-70
Lüftungskanalfühler für relative Feuchte und Temperatur,
Typ A2G-70
Model A2G-70

2
40202801.04 10/2021 EN/DE
WIKA operating instructions model A2G-70
DE
EN
© 01/2010 WIKA Alexander Wiegand SE & Co. KG
All rights reserved. / Alle Rechte vorbehalten.
WIKA®is a registered trademark in various countries.
WIKA®ist eine geschützte Marke in verschiedenen Ländern.
Prior to starting any work, read the operating instructions!
Keep for later use!
Vor Beginn aller Arbeiten Betriebsanleitung lesen!
Zum späteren Gebrauch aufbewahren!
Operating instructions model A2G-70 Page 3 - 26
Betriebsanleitung Typ A2G-70 Seite 27 - 49

EN
3WIKA operating instructions model A2G-70
40202801.04 10/2021 EN/DE
Contents
Contents
Declarations of conformity can be found online at www.wika.com.
1. General information 4
2. Design and function 5
3. Safety 7
4. Transport, packaging and storage 11
5. Commissioning, operation 12
6. Menu navigation 16
7. Maintenance, cleaning and recalibration 20
8. Dismounting, return and disposal 21
9. Specications 24

EN
4
40202801.04 10/2021 EN/DE
WIKA operating instructions model A2G-70
1. General information
■
The ventilation duct sensor described in the operating instructions
has been manufactured using state-of-the-art technology. All
components are subject to stringent quality and environmental
criteria during production. Our management systems are certied to
ISO 9001 and ISO 14001.
■
These operating instructions contain important information on
handling the instrument. Working safely requires that all safety
instructions and work instructions are observed.
■
Observe the relevant local accident prevention regulations and
general safety regulations for the instrument's range of use.
■
The operating instructions are part of the product and must be kept
in the immediate vicinity of the instrument and readily accessible to
skilled personnel at any time. Pass the operating instructions on to the
next operator or owner of the instrument.
■
Skilled personnel must have carefully read and understood the
operating instructions prior to beginning any work.
■
The general terms and conditions contained in the sales
documentation shall apply.
■
Subject to technical modications.
■
Further information:
- Internet address: www.wika.de / www.wika.com
www.air2guide.com
- Relevant data sheet: TE 62.91
1. General information

EN
5WIKA operating instructions model A2G-70
40202801.04 10/2021 EN/DE
2. Design and function
2.1 Overview
Case
Mounting ange
Probe sleeve
2.2 Description
The model A2G-70 ventilation duct sensor is a humidity probe with an
integrated measurement of the relative humidity and temperature.
The measurement of relative humidity and the air temperature as
the basis of demand-orientated control/regulation is gaining ever
more importance in the ventilation and air-conditioning industry.The
A2G-70 registers the relative humidity and the temperature of the air
with a capacitive sensor. The sensor signals for both measurands are
transmitted to the control/regulation or building automation with analogue
output signals (0 … 10 V, 4 … 20 mA) or digital Modbus®protocol.
2. Design and function

EN
6
40202801.04 10/2021 EN/DE
WIKA operating instructions model A2G-70
2.3 Dimensions in mm
H
A
B
C
G
D
E
F
I
H
A
B
C
G
D
E
F
I
Adjustable 40 … 155 mm
Dimensions in mm [in]
A B C D E F Ø G H I
119 45 5.2 70 15 188 12 95.5 88.5
2.4 Scope of delivery
■
Digital ventilation duct temperature sensor for relative humidity and
temperature
■
Mounting ange
Cross-check scope of delivery with delivery note.
2. Design and function

EN
7WIKA operating instructions model A2G-70
40202801.04 10/2021 EN/DE
3. Safety
3.1 Explanation of symbols
WARNING!
... indicates a potentially dangerous situation that can result in
serious injury or death, if not avoided.
CAUTION!
... indicates a potentially dangerous situation that can result in
light injuries or damage to property or the environment, if not
avoided.
DANGER!
... identies hazards caused by electrical power. Should the
safety instructions not be observed, there is a risk of serious
or fatal injury.
WARNING!
... indicates a potentially dangerous situation that can result in
burns, caused by hot surfaces or liquids, if not avoided.
Information
... points out useful tips, recommendations and information for
ecient and trouble-free operation.
3.2 Intended use
The model A2G-70 ventilation duct sensor is used for the measurement
of the relative humidity and temperature, suitable for direct mounting on
circular ventilation pipes or rectangular ventilation ducts.
This instrument is not permitted to be used in hazardous areas!
3. Safety

EN
8
40202801.04 10/2021 EN/DE
WIKA operating instructions model A2G-70
The instrument has been designed and built solely for the intended use
described here, and may only be used accordingly.
The technical specications contained in these operating instructions
must be observed. Improper handling or operation of the instrument
outside of its technical specications requires the instrument to be taken
out of service immediately and inspected by an authorised WIKA service
engineer.
The manufacturer shall not be liable for claims of any type based on
operation contrary to the intended use.
3.3 Improper use
WARNING!
Injuries through improper use
Improper use of the instrument can lead to hazardous
situations and injuries.
▶Refrain from unauthorised modications to the instrument.
▶Do not use the instrument within hazardous areas.
▶Do not use the instrument with abrasive or viscous media.
Any use beyond or dierent to the intended use is considered as
improper use.
Do not use this instrument in safety or emergency shutdown devices.
3.4 Responsibility of the operator
The instrument is used in the industrial sector.The operator is therefore
responsible for legal obligations regarding safety at work.
The safety instructions within these operating instructions, as well as the
safety, accident prevention and environmental protection regulations for
the application area must be maintained.
The operator is obliged to maintain the product label in a legible
condition.
3. Safety

EN
9WIKA operating instructions model A2G-70
40202801.04 10/2021 EN/DE
To ensure safe working on the instrument, the operating company must
ensure
■
that the operating personnel are regularly instructed in all topics
regarding work safety, rst aid and environmental protection and know
the operating instructions and, in particular, the safety instructions
contained therein.
■
that the instrument is suitable for the particular application in
accordance with its intended use.
■
that personal protective equipment is available.
3.5 Personnelqualication
WARNING!
Riskofinjuryshouldqualicationbeinsucient
Improper handling can result in considerable injury and
damage to property.
▶The activities described in these operating instructions
may only be carried out by skilled personnel who have the
qualications described below.
Skilled electrical personnel
Skilled electrical personnel are understood to be personnel who, based
on their technical training, know-how and experience as well as their
knowledge of country-specic regulations, current standards and directives,
are capable of carrying out work on electrical systems and independently
recognising and avoiding potential hazards.The skilled electrical personnel
have been specically trained for the work environment they are working
in and know the relevant standards and regulations.The skilled electrical
personnel must comply with current legal accident prevention regulations.
Operating personnel
The personnel trained by the operator are understood to be personnel
who, based on their education, knowledge and experience, are capable
of carrying out the work described and independently recognising
potential hazards.
Special operating conditions require further appropriate knowledge, e.g.
of aggressive media.
3. Safety

EN
10
40202801.04 10/2021 EN/DE
WIKA operating instructions model A2G-70
3.6 Labelling, safety marks
Product label (example)
Type: A2G-50
Range: -250 ... +250 Pa
Output: 0 ... 10 V / 4 ... 20 mA
Supply: DC 24 V / AC 24 V ±10 % < 1 W
Made in EU E-Nr. 66209848
Model
Measuring range
Output signal
Supply voltage
Serial number
Before mounting and commissioning the instrument, ensure
you read the operating instructions!
3. Safety

EN
11WIKA operating instructions model A2G-70
40202801.04 10/2021 EN/DE
4. Transport, packaging and storage
4.1 Transport
Check the instrument for any damage that may have been caused by
transport.
Obvious damage must be reported immediately.
CAUTION!
Damage through improper transport
With improper transport, a high level of damage to property
can occur.
▶When unloading packed goods upon delivery as well as
during internal transport, proceed carefully and observe
the symbols on the packaging.
▶With internal transport, observe the instructions in chapter
4.2 “Packaging and storage”.
If the instrument is transported from a cold into a warm environment, the
formation of condensation may result in instrument malfunction. Before
putting it back into operation, wait for the instrument temperature and the
room temperature to equalise.
4.2 Packaging and storage
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport
(e.g. change in installation site, sending for repair).
Permissible conditions at the place of storage:
Storage temperature: -20 ... +70 °C
Avoid exposure to the following factors:
■
Direct sunlight or proximity to hot objects
■
Mechanical vibration, mechanical shock (putting it down hard)
■
Soot, vapour, humidity, dust and corrosive gases
■
Hazardous environments, ammable atmospheres
4. Transport, packaging and storage

EN
12
40202801.04 10/2021 EN/DE
WIKA operating instructions model A2G-70
Store the instrument in its original packaging in a location that fulls the
conditions listed above. If the original packaging is not available, pack
and store the instrument as described below:
1. Wrap the instrument in an antistatic plastic lm.
2. Place the instrument, along with the shock-absorbent material, in the
packaging.
3. If stored for a prolonged period of time (more than 30 days), place a
bag containing a desiccant inside the packaging.
5. Commissioning, operation
Personnel: Skilled electrical personnel
Tools: Voltage tester, screwdriver
WARNING!
Physical injuries and damage to property and the
environment caused by hazardous media
Upon contact with hazardous media (e.g. oxygen, acetylene,
ammable or toxic substances), harmful media (e.g. corrosive,
toxic, carcinogenic, radioactive), and also with refrigeration
plants and compressors, there is a danger of physical injuries
and damage to property and the environment.
Should a failure occur, aggressive media with extremely high
temperature and under high pressure or vacuum may be
present at the instrument.
▶For these media, in addition to all standard regulations,
the appropriate existing codes or regulations must also be
followed.
CAUTION!
Damage to the instrument
When working on open electric circuits (PCBs) there is a
risk of damaging sensitive electronic components through
electrostatic discharge.
▶The correct use of grounded working surfaces and
personal armbands is required.
4. Transport ... / 5. Commissioning, operation

EN
13WIKA operating instructions model A2G-70
40202801.04 10/2021 EN/DE
DANGER!
Danger to life caused by electric current
Upon contact with live parts, there is a direct danger to life.
▶The instrument may only be installed and mounted by
skilled personnel.
▶Operation using a defective power supply unit (e.g. short-
circuit from the mains voltage to the output voltage) can
result in life-threatening voltages at the instrument.
▶Only switch the power supply on once the instrument has
been properly installed.
1. Mount the instrument in the desired location (see chapter 5.1
“Mechanical mounting”).
2. Open the instrument cover, lay the cable and connect in accordance
with the pin assignment (see chapter 5.2 “Electrical mounting”).
3. The instrument is now ready for conguration.
5.1 Mechanical mounting
■
Select a mounting location (at a duct).
■
Use the mounting ange as a template and mark the screw holes.
■
Mount the ange to the duct with the screws (screws are not included
in delivery).
Mount the ange
5. Commissioning, operation

EN
14
40202801.04 10/2021 EN/DE
WIKA operating instructions model A2G-70
■
Insert the probe to the desired depth.The end of the probe must
reach the middle of the duct.
■
Fasten the screws tightly to the ange in order that the probe is held in
position.
Tighten the
screw
Mount the probe into the ange
Tighten the
screws
Air flow direction Air flow direction
Air flow direction Air flow direction Air flow direction
Strain relief facing down
Air ow direction Air ow direction
Air ow direction Air ow direction Air ow direction
Strain relief directed downwards
5. Commissioning, operation

EN
15WIKA operating instructions model A2G-70
40202801.04 10/2021 EN/DE
5. Commissioning, operation
5.2 Electrical mounting
The ventilation duct sensor is designed to operate with safety extra-low
voltage (SELV). It must be operated at a constant operating voltage
(±0.2 V). Current/voltage spikes from switching the supply voltage on or
o must be prevented by the customer.
Unscrew the strain relief and connect the cable in accordance with the
connection diagram.Then screw the strain relief back tightly.
Connection diagram
rH
T
24 V
GND
Supply voltage UB
Output DC 0/2 … 5/10 V
Output DC 0/2 … 5/10 V
Output 4 … 20 mA
Output 4 … 20 mA
rH
T
Optional mA output
A
B
24 V
GND
Supply voltage UB
Modbus®B
Modbus®A
Modbus®output signal

EN
16
40202801.04 10/2021 EN/DE
WIKA operating instructions model A2G-70
6. Menu navigation
6.1 Standard version
1. Selecting the instrument menu
Keep the selection button “SELECT” pressed for at least 2 seconds to
access the menu.
▶MENU is displayed
2. Selecting and adjusting the parameters
Press the “DOWN” button once
▶Next menu item is displayed
Press the “SELECT” button once in order to
activate the selection of the parameter.
▶Selection ashes
Press “UP” or “DOWN” in order to dene the
desired value of the selection.
▶Selection is displayed
Press the “SELECT” button once in order to accept
the selection.
XXXXXXXX
XXXX
XXXXXXXX
XXXX
XXXXXXXX
XXXX
XXXXXXXX
XXXX
6. Menu navigation

EN
17WIKA operating instructions model A2G-70
40202801.04 10/2021 EN/DE
6. Menu navigation
3. Select the lower limit of the humidity for the
output signal: 0 ... 90 % r. h.
Press the “DOWN” button once
▶“RH OUT MIN” menu item is displayed
4. Select the upper limit of the humidity for the
output signal: 10 ... 100 % r. h.
Press the “DOWN” button once
▶“RH OUT MAX” menu item is displayed
5. Select the lower temperature limit for the
output signal: 0 … 45 °C or 32 ... 112 °F
Press the “DOWN” button once
▶“TE OUT MIN” menu item is displayed
6. Select the upper temperature limit for the
output signal: 5 … 50 °C or 42 ... 122 °F
Press the “DOWN” button once
▶“TE OUT MAX” menu item is displayed
7. Select the upper value of the output signal:
5 V or 10 V
With mA outputs, “10 V” must be selected.
Press the “DOWN” button once
▶“MAX OUTPUT V” menu item is displayed
RH OUT MIN
0.0 % RH
RH OUT MAX
10.0 % RH
TE OUT MIN
0.0 °C
TE OUT MAX
50,0 °C
MAX OUTPUT V
10 V

EN
18
40202801.04 10/2021 EN/DE
WIKA operating instructions model A2G-70
6. Menu navigation
8. Select the lower value of the output signal:
0 V or 2 V
With mA outputs, “0 V” must be selected.
Press the “DOWN” button once
▶“MIN OUTPUT V” menu item is displayed
9. Selectthehumidityoset:±10%r.h.
The oset function enables a eld calibration. This
is necessary in demanding applications that require
annual calibration.
10. Selecttemperatureoset:±5°Cor±9°F
11. Press the “SELECT” button in order to exit the
menu.
6.2 Modbus®version
1. Selecting the instrument menu
Press the “SELECT” button for at least two seconds
to access the menu.
▶“MENU” is displayed
MIN OUTPUT V
0 V
RH OFFSET
0.0 % RH
TE OFFSET
0.0 °C
SELECT
EXIT MENU
MENU

EN
19WIKA operating instructions model A2G-70
40202801.04 10/2021 EN/DE
2. Selecting and adjusting the parameters
→ see chapter 6.1 “Standard version”
3. Select Modbus®address: 1 … 247
Press the “DOWN” button once
▶“ADDRESS” menu item is displayed
4. Select the baud rate: 9,600, 19,200, 38,400
Press the “DOWN” button once
▶“BAUD RATE” menu item is displayed
5. Select the parity bit: None, even, odd
Press the “DOWN” button once
▶“PARITY BIT” menu item is displayed
6. Press the “SELECT” button in order to exit the
menu.
ADDRESS
99
BAUD RATE
9600
PARITY BIT
NONE
SELECT
EXIT MENU
6. Menu navigation

EN
20
40202801.04 10/2021 EN/DE
WIKA operating instructions model A2G-70
6.3 Modbus®register
Function code 04 - Read input register
Register Parameter
description
Data
type
Value Range
3x0001 Program version 16 bit 0…1000 0.0 … 99.0
3x0003 Relative humidity
reading
0…1000 0.0 … 100.0 %
3x0004 Temperature reading 0…500 0.0 … 50.0 °C
7. Maintenance, cleaning and recalibration
Personnel: Skilled electrical personnel
Tools: Voltage tester, screwdriver
For contact details, see chapter 1 “General information” or the
back page of the operating instructions.
7.1 Maintenance
This instrument is maintenance-free and oers long service life provided
it is handled and operated properly.
Repairs must only be carried out by the manufacturer or appropriately
qualied skilled personnel.
7.2 Cleaning
CAUTION!
Physical injuries and damage to property and the
environment
Improper cleaning may lead to physical injuries and damage
to property and the environment. Residual media in the
dismounted instrument can result in a risk to persons, the
environment and equipment.
▶Carry out the cleaning process as described below.
6. Menu navigation / 7. Maintenance, cleaning...
Table of contents
Languages:
Other WIKA Accessories manuals
Popular Accessories manuals by other brands

LOXONE
LOXONE SMART SOCKET AIR manual

Nokia
Nokia MetroSite EDGE installation manual

Mitsubishi Electric
Mitsubishi Electric PZ-70CSW-E quick start guide

HOME DECÓ
HOME DECÓ 51967 quick start guide

Rice Lake
Rice Lake 880 Performance Series Technical and service manual

Huawei
Huawei TP48200A installation guide

Cooper Lighting
Cooper Lighting Halo HSA610 Specifications

Beurer
Beurer UB 90 Instructions for use

QUEST ELITE
QUEST ELITE Snowdon Full item instructions and extended details

Flexifoil
Flexifoil Camera Kite user manual

Cardinal
Cardinal 225D SmartCell Installation and technical manual

NuAire
NuAire NU-8600 Operation and maintenance manual