Check if the DIN-Rail mounting kit is installed firmly.Step 1 Insert the bottom of DIN-Rail mounting kit (one sideStep 2 with spring support) into DIN-Rail, and then insert
the top into DIN-Rail.
Tips:
Insert a little to the bottom, lift upward and then insert
to the top.
Check and confirm the product is firmly installed onStep 3 DIN-Rail, then mounting ends.
【Disassembling DIN-Rail】
Power off the device.Step 1 After lift the device upward slightly, first shift out theStep 2 top of DIN-Rail mounting kit, then shift out the
bottom of DIN-Rail, disassembling ends.
Attention before powering on:
Power ON operation: first connect power line to the
connection terminal of device power supply, then power
on.
Power OFF operation: first unpin the power plug, then
remove the power line, please note the operation order
above.
【Power Supply Connection】
DC power supply
The series provide 4-pin power supply
input terminal blocks and two
independent DC power supply systems of
PWR1 and PWR2. The power supply
supports nonpolarity and anti-reverse
connection. It can normally operate after reverse connection.
Power supply range: 12~48VDC
【Relay Connection】
Relay terminals are a pair of normally open
contacts in the alarm relay of the device. They
are open circuit in normal non alarm state,
closed when any alarm information occurs. For example: it's
closed and sends out alarm when power off. This series
support 1 channel relay alarm information output, and DC
power alarm output. It can be connected to alarm indicator,
alarm buzzer, or other switching value collecting devices for
timely warning operator when alarm information occurs.
【DIP Switch Setting】
This series provide 4-pin DIP switch for function
settings, where "ON" is enable valid terminal.
Please power off and power on after changing
the status of DIP switch. DIP switch definition as
follows:
Abnormal alarm settings of the
power supply connection
【Checking LED Indicator】
This series provide LED indicators to monitor the operating
status of the device, which can comprehensively simplify the
troubleshooting. The detailed status of each LED is described
in the table below:
P1 is connected and running
normally
P1 is disconnected and running
abnormally.
P2 is connected and running
normally
P2 is disconnected and running
abnormally
Power supply link without alarm
The device is powering on or
running abnormally.
The device is powered off or
running abnormally.
Blink once per second, and the
device is running well.
Ethernet port connection is
active.
Ethernet port connection is
inactive.
【Specification】
10/100/1000Base-T(X)
self-adapting RJ45 port, full/half
duplex self-adapting or specified
operating mode, support
MDI/MDI-X self-adaption
2-pin 7.62mm pitch terminal
blocks, support 1 channel relay
alarm information output
Power supply indicator, running
indicator, interface indicator and
alarm indicator
12~48VDC
Support dual power supply
redundancy, nonpolarity and
anti-reverse connection
4-pin 7.62mm pitch terminal
block
No-load consumption:
4.85W@24VDC
Full-load consumption:
10.32W@24VDC