ABB MPS-C 2000 User manual

NOTE: This Instruction Book is provided solely for the convenience of the
purchaser, and does not purport to cover all details or variations in equipment nor
to provide contingency to be met in connection with installation, operation, or
maintenance. Should further information be desired or should particular problems
arise which are not covered sufficiently for the purchaser’s purposes, the matter
should be referred to the nearest Sales Representative.
CONTENTS
PAGE
INTRODUCTION................................................................................................ 3
FUNCTIONS...................................................................................................... 4
SETTINGS......................................................................................................... 4
RANGE SELECTION................................................................................ 4
LONG TIME FUNCTION........................................................................... 4
SHORT TIME FUNCTION......................................................................... 4
INSTANTANEOUS FUNCTION.................................................................. 5
GROUND FUNCTION............................................................................... 5
CURRENT UNBALANCE........................................................................... 6
CURRENT SENSOR THRESHOLDS......................................................... 6
INFORMATION FUNCTION...................................................................... 6
TEST FUNCTIONS............................................................................................ 7
VOLTAGE INTERFACE MODULE (VIM)............................................................. 7
SETTINGS.............................................................................................. 7
MPS-C 2000 SETUP INSTRUCTIONS................................................................ 8
GENERAL INSTRUCTIONS..................................................................... 8
MENU LAYOUT...................................................................................... 9
METERING SUBMENU........................................................................... 10
SETTINGS SUBMENU............................................................................ 11
CHANGE SETTINGS SUBMENU............................................................. 12
AVAILABLE SETTINGS.......................................................................... 13
PASSWORD PROTECTION................................................................... 13
RECORDS SUBMENU........................................................................... 14
Courtesy of NationalSwitchgear.com

IB 6.1.2.8-1B
Page 3 ABB
INTRODUCTION
The electronic trip control unit described in this publication is a solid state,
microprocessor controlled unit, used in conjunction with a power circuit breaker to
protect power systems. The power circuits being protected are typically 3-phase,
with and without a neutral connection, 50 or 60 Hz with AC RMS voltages between
208 and 600 volts and continuous currents as high as 4200 amps, while ground
currents may not exceed 1200 amps.
The primary function of the electronic trip control unit is the coordination in the
opening of circuit breakers to protect equipment in the event of a fault that
produces short circuit currents of up to 130 KA.
The MPS-C 2000 trip control unit measures current to an accuracy of within 1% of
the cicuit breaker rating.
The Voltage Interface Module (VIM) option measures voltage to an accuracy of
within 1% of the circuit breaker rating, and power to within 2% of the circuit
breaker rating.
The trip unit is completely self-powered, taking the the tripping energy from the
current through the breaker without any auxiliary power supply.
The complete control of the circuit breaker is achieved by a system comprising:
(a) current sensors, (b) an electronic trip control unit, and (c) a magnetic latch trip
device.
The sensors, the electronic trip control device and magnetic latch are mounted
as an integral part of the circuit breaker to provide complete protection for
overcurrent, short circuit and ground faults. Internal diagnostic circuitry is provided
to determine and visually identify the cause of circuit breaker tripping, either as
overload, short circuit or ground fault.
Courtesy of NationalSwitchgear.com

IB 6.1.2.8-1B
Page 4
ABB
1. FUNCTIONS.
The electronic trip control device provides the following four basic functions:
1.1 Protection Function
Four basic trip elements within the unit perform the protective functions:
Long time, short time, instantaneous and ground.
1.2 Information Function
An indicator (target) and an LCD screen display information for the tripping functions.The indicator shows if
the device has issued a trip command and the LCD can be polled to determine the type of trip. The LCD and
keypad buttons are used to determine the settings of the unit. A red LED indicates self-monitoring functions.
1.3 Test Functions
The unit can be connected to an external test set to check functions and settings.
1.4 Communication Functions
The unit can be connected to switchgear mounted devices which are connected to ABB INCOM Protocol.
2. SETTINGS.
2.1 Range Selection
The range selector provides the primary amperage used as the base for the unit. It is either set for the 1 X or
0.5 X the breaker rating: Default is 1 X.
2.2 Long Time Function
2.2.1 Threshold (pickup)settings- The range of settings is: 0.5 to 1.0 in steps of 0.1. Multipliers are used in
conjunction with sensor rating and the range selector. Multipliers are selected by keypad input and displayed on
the LCD. Default is 1.0.
2.2.2 Trip Time - Time is defined by long time overcurrent curves (graph) and intermediate values between band
limits. Default is MAX.
2.2.3 Reset Time - Real time is counted up if the current exceeds the function threshold and counted down if the
current drops below the function threshold. Real time is set to zero if the current drops below the power supply
threshold.
2.3. Short Time Function
2.3.1 Threshold (pickup) settings - 2 3 4 5 6 7 8 9 10 DISABLED. The settings are multiples of the sensor ratings
and the range selector. Settings are made by the keypad and the LCD display. If the INST function is disabled, the
short time unit cannot be disabled. Default is DISABLED.
Courtesy of NationalSwitchgear.com

IB 6.1.2.8-1B
Page 5 ABB
2.3.2 Trip time - Time is defined by the short time overcurrent curves (graph). I²t function is selectable.
I²t curves are fixed and do not vary with pickup settings. I²t is operational only from 2X to 4X. Trip times with I²t out
are defined as follows: Default is maximum with I²t in.
Maximum = 0.350 - 0.500 sec
Intermediate = 0.20 - 0.320 sec
Minimum = 0.080 - 0.170 sec
2.3.3 Reset time - Real time is counted up if the current exceeds the function threshold and counted down if the
current drops below the function threshold.
2.4 Instantaneous Function
2.4.1 Threshold (pickup) settings - 3 4 5 6 7 8 9 10 11 12 DISABLED. The settings are multiples of the range
selector setting and are made via the keypad and the LCD screen. If the short time unit is disabled, the
instantaneous unit cannot be disabled. Default is 12.
2.4.2 Trip time - There is no intentional delay in the instantaneous function.
2.4.3 The instantaneous unit includes a jumper on the circuit board which eliminates the possibility of instantaneous
and short time being simultaneously disabled.
2.5 Ground Function
2.5.1 Threshold (pickup) settings - These settings are made via the keypad and the LCD screen. This function may
also be disabled. Default is 1200 A.
SENSOR RATINGS
SETTINGS
200
600
800
100,200,300,
600,900,& 1200A
1600
2000
2500
300,400,600,
800,1000,& 1200A
3000
3200
4000
4200
500,600,800,
900,1000, & 1200A
Courtesy of NationalSwitchgear.com

IB 6.1.2.8-1B
Page 6
ABB
2.5.2 Trip time - The time is defined by the overcurrent curves (graph). I²t function is selectable. I²t curves are fixed
and do not vary with pickup settings. If the I²t function is out, the trip times are defined as follows: Default is
Maximum with I²t in.
2.5.3 Reset time - Real time is counted up if the current exceeds the function threshold and counted down if the
current drops below the function threshold. Real time is set to zero when the curent drops below the power pickup
point.
2.5.4 Residual ground current - In a three phase, four wire system the ground fault functions can discriminate
between a ground fault and a neutral current.
2.5.5 Ground fault summing - The reset technique used for long-time and short-time function is applied. i.e, real time
is counted up if the current exceeds the function threshold and counted down if the current drops below the function
threshold. The ground function includes arcing ground summation for tripping. This feature allows arcing grounds
occurring sufficiently close together to be summed so that their magnitude will exceed the threshold setting of the
ground element.
2.6 Current Unbalance
2.6.1 Pickup settings - 5% to 50% in increments of 1% and DISABLED. These changes can be made either via the
keypad and LCD or the NIM communications unit. Default is DISABLED. The current unbalance function is only
available for systems with VIM attached.
2.7 Current Sensor Thresholds
2.7.1 Long time - 0.5X to 1.0X of sensor rating in increments of 0.1.
Short time - 2X to 10X of sensor rating in increments of 1.
Instantaneous - 3X to 12X of sensor rating in increments of 1.
Ground - 100 amps to 1200 amps
300 amps to 1200 amps
500 amps to 1200 amps
Depending on sensor rating. See section 2.5.1
2.8 Information Function
2.8.1 The information function consists of an LCD screen, a mechanical target, a light emitting diode (LED) and six
keypad buttons.
2.8.2 The mechanical target provides indication that the unit has caused a circuit breaker opening. Further
information about the function such as the type of trip, LT, ST, INST, GND, I UNB, V UNB, or UV and the fault
current is displayed when any keypad button in depressed after a trip has occurred, or can be found in the records
menu.
DELAY
SETTING
100 - 800A
SENSORS
1600 - 2500A
3000 - 4200A
MAX 5.2 - 9.5 SEC 0.59 - 1.2 SEC 0.35 - 0.50 SEC
INT 2.1 - 4.2 SEC 0.24 - 0.47 SEC 0.20 - 0.32 SEC
MIN 0.68 - 1.3 SEC 0.07 - 0.18 SEC 0.05 - 0.17 SEC
Courtesy of NationalSwitchgear.com

IB 6.1.2.8-1B
Page 7 ABB
2.8.3 The target resets automatically when the unit is re-energized. Reset occurs in 2 seconds.
2.8.4 The red LED blinks once per second to indicate that the MPS-C 2000 unit is powered up and functioning
normally. (self monitor light).
2.8.5 The red self monitor light blinks five times per second to indicate long-time pickup and continues to do so until
reset or the breaker trips.
2.8.6 When the unit is powered up and the settings table has timed out, the LCD screen will display metering
information provided that the unit has enough line current to power up or is externally powered.
3. TEST FUNCTIONS
3.1 The unit continuously monitors the condition of the microprocessor and is reported by a flashing LED on the front
panel. Upon failure, the LED will glow steadily.
3.2 The unit is compatible with the 607 test set.
4. VOLTAGE INTERFACE MODULE (VIM)
4.1 The VIM performs the following functions:
a. Provides the phase voltage for remote display.
b. Houses the electronics for performing the power, power factor and frequency processing based
on current data from the MPS-C 2000 box.
c. Performs calculations to determine voltage unbalance and undervoltage faults.
4.2 If a VIM device is installed the MPS-C 2000 unit must be connected to a NIM communications unit.
4.3 If a VIM is installed in the unit, a cable connects the unit to the potential transformer located on the rear of the
MPS-C 2000 mounting plate and plugs directly into the VIM board.
4.4 Settings
4.4.1 Voltage unbalance
4.4.1.1 Pickup - 5% to 50% in increments of 1% and DISABLED. Set via the front panel or the NIM communication
unit. Default is DISABLED. Connection to a NIM is necessary for this function to be enabled.
4.4.1.2 Trip time - 0.1 to 25.0 seconds in increments of 1 second. Set via the front panel or the NIM communications
unit. Default is 25.0 seconds.
4.4.2 Undervoltage trip
4.4.2.1 Pickup - 1 to 600 volts in increments of 1 and DISABLED. Set via the front panel or the NIM communications
unit. Default is DISABLED. Connection to a NIM is necessary for this function to be enabled.
4.4.2.2 Trip time - 0.1 to 25.0 seconds in increments of 1 second. Set via the front panel or the NIM communications
unit. Default is 25.0 seconds.
Courtesy of NationalSwitchgear.com

IB 6.1.2.8-1B
Page 8
ABB
5. MPS-C 2000 SETUP INSTRUCTIONS
5.1 General Instructions
5.1.1 The front panel keypad consists of four directional arrow keys, a cancel key, an enter key, and an LCD
window.
5.1.2 When the MPS-C 2000 unit is connected to a power source, an initial title screen is displayed in the LCD
window.
This screen display is replaced after approximately three seconds by a setup screen.
Subsequent Main Menu screens are accessed by pressing the “E” key and the up and down keys. See section 6.
5.1.3 Each Main Menu has a Submenu, used for entering and displaying values. These are accessed by pressing
the “E” key while in the Main Menu. The up and down keys are used in the submenus to display the desired type of
values or settings and the “E” key is pressed again to access these. The up and down keys are then used to scroll
through the settings.
5.1.4 Pressing the “C” key in any screen will back up the display to the previous screen.
Courtesy of NationalSwitchgear.com

IB 6.1.2.8-1B
Page 9 ABB
6. MENU LAYOUT
6.1 The following layout shows the Main Menus and submenus accessed by pressing the “E” key and the up and
down arrows. To exit the submenus to return to the Main Menu, the “C” key should be pressed.
For layouts of the submenus, refer to sections 6.2 through 6.5.
MPS-C-2000
Version 1.0
Ia: ## Ib: ##
Ic: ## In: ##
====MAIN MENU====
Metering Menu
====MAIN MENU====
Show Settings
====MAIN MENU====
Change Settings
====MAIN MENU====
Records Menu
INITIAL SCREEN
Press "E" (or wait 3 seconds)
Press "E"
Press "Up and Down
Arrows"
===METER MENU===
Load Values
Press "E"
=SETTINGS MENU=
MPS Settings
Press "E"
==CHANGE MENU==
MPS Settings
Press "E"
=RECORDS MENU=
MPS Fault Event
Press "E"
SUBMENUS
See sec 6.2
See sec 6.3
See sec 6.4
See sec 6.5
This screen is displayed
when unit has power and
MPS-C-2000 screen has
"timed out"
Press "Up and Down
Arrows"
Press "Up and Down
Arrows"
Courtesy of NationalSwitchgear.com

IB 6.1.2.8-1B
Page 10
ABB
===METER MENU===
Load Values
SUBMENU
==LOAD VALUES==
Ia: ###
Press "E"
Ib: ###
Ic: ###
In: ###
Van: ###
Vbn: ###
Vcn: ###
Vab: ###
Vbc: ###
Vca: ###
KW3p: ###
KVAr3p:###
KVA3p: ###
KWHr3p: ###
KVarHr3p: ###
PF: ###
Freq: N/A
Scroll up and down
using arrow keys
These
values will
not be
displayed if a
VIM is not
attached
===METER MENU===
Demand Values
Press
"Up and
Down"
Arrows
=DEMAND VALUES=
Ia: ###
Press "E"
Ib: ###
Ic: ###
In: ###
KW3p: ###
KVAr3p: ###
KWHr3p: ###
KVarHr3p: ###
These
values will
not be
displayed if a
VIM is not
attached
Press "C"
Press "C"
6.2 METERING SUBMENU
EE
KEYPAD INPUT SEQUENCE FOR METERING SUBMENU
E
Ia: ## Ib: ##
Ic: ## In: ##
C E
==LOAD VALUES==
Ia: ###
=DEMAND VALUES=
Ia: ###
===METER MENU===
Demand Values
Default
screen
display
Press keys in this sequence to access metering submenus.
Courtesy of NationalSwitchgear.com

IB 6.1.2.8-1B
Page 11 ABB
=SETTINGS MENU=
MPS Settings
SUBMENU
=SHOW SETTINGS=
Rating: ####
Press "E"
LT Pickup: ####
LT Delay: ####
ST Pickup: ####
ST Delay: ####
ST Curve: ####
INST Pkup: ####
GND Pkup: ####
GND Delay: ####
GND Curve:####
Test Crv: ####
Dmnd Intvl: ####
I Unbal: ####
I Unb Dly: ####
PASSWORD
Scroll up and down
using arrow keys
=SETTINGS MENU=
VIM Settings
Press
"Up and
Down"
Arrows
==SHOW VIM SET==
V Unbal: ####
Press "E"
V Unb Dly: ###
UV Pkup: ###
UV Delay: ###
Dmnd Intvl: ###
Press "C"
Press "C"
6.3 SETTINGS SUBMENU
E
KEYPAD INPUT SEQUENCE FOR SETTINGS SUBMENU
E
Ia: ## Ib: ##
Ic: ## In: ##
C E
=SHOW SETTINGS=
Rating: ####
=SHOW VIM SET=
V Unbal: ####
Default
screen
display
Press keys in this sequence to access Settings submenus.
E
Courtesy of NationalSwitchgear.com

IB 6.1.2.8-1B
Page 12
ABB
==CHANGE MENU==
MPS Settings
SUBMENU
=ENTER PASSWORD=
( )
Press "E"
LT Pickup: ####
LT Delay: ####
ST Pickup: ####
ST Delay: ####
ST Curve: ####
INST Pkup: ####
GND Pkup: ####
GND Delay: ####
GND Curve: ####
Test Crv: ####
Dmnd Intvl: ####
I Unbal: ####
I Unb Dly: ####
PASSWORD
Scroll up and down
using arrow keys
==CHANGE MENU==
VIM Settings
Press "E"
V Unb Dly: ###
UV Pkup: ###
UV Delay: ###
Dmnd Intvl: ###
6.4 CHANGE SETTINGS SUBMENU
EE
KEYPAD INPUT SEQUENCE
E
Ia: ## Ib: ##
Ic: ## In: ##
C E
* * * *
=CHANGE SETTINGS =
Rating: ####
Press "E" PRESS "E" TO CHANGE
SETTINGS
Press "C"
=ENTER PASSWORD=
( )
* * * *
==CHNG VIM SET==
V Unbal:####
Press "E"
Press "C"
PRESS "E" TO CHANGE
SETTINGS
E
E
6.4.1 To change settings PRESS ""E", (an asterisk will appear after the setting) TOGGLE
BETWEEN SETTINGS USING LEFT AND RIGHT ARROW KEYS, PRESS "E" TO ACCEPT,
THEN PRESS "C".
See instructions below for
changing settings
sec. 6.4.1
Press keys in this sequence to access change settings submenus
Default
screen
display =CHANGE SETTINGS =
Rating: ####
==CHANGE MENU==
VIM Settings
==CHNG VIM SET==
V Unbal:####
Press
"Up and
Down"
Arrows
Courtesy of NationalSwitchgear.com

IB 6.1.2.8-1B
Page 13 ABB
6.4.2 Available Settings
The following is a list of choices for each setting in the CHANGE SETTINGS Submenu:
MPS SETTINGS
LT PICKUP: 0.5X, 0.6X, 0.7X, 0.8X, 0.9X, 1.0X Sensor rating.
LT DELAY: MIN, INT, MAX
ST PICKUP: 2X, 3X, 4X, 5X, 6X, 7X, 8X, 9X, 10X, 11X, 12X Sensor rating, and DISABLED.
ST DELAY: MIN, INT, MAX
ST CURVE: DEF, IIT
INST PICKUP: 3X, 4X, 5X, 6X, 7X, 8X, 9X, 10X, 11X, 12X Sensor rating, and DISABLED if INST disable jumper is
not blocked.
GND PICKUP: See ground sensor table, section 2.5.1
GND DELAY: MIN, INT, MAX
GND CURVE: DEF, IIT
TEST CURVE: LT, ST, INST, GND
DEMAND INTERVAL: 15, 30, and 60 minutes
CURRENT UNBALANCE: 5 to 50 percent, in increments of 1%
CURRENT UNBALANCE DELAY: .10 to 25.0 seconds in increments of .1% and DISABLED
VIM SETTINGS
VOLTAGE UNBALANCE: 5 to 50 percent in increments of 1%
VOLTAGE UNBALANCE DELAY: .10 to 25.0 seconds in increments of .1% and DISABLED
UNDERVOLTAGE PICKUP: 1 to 600 Volts in increments of 1 volt
UNDERVOLTAGE DELAY: .10 to 25.0 seconds in increments of .1% and DISABLED
DEMAND INTERVAL: 15, 30, and 60 minutes
6.4.3 Password Protection
If a password has not been programmed into the unit, the PASSWORD screen can be bypassed simply by pressing
“E”. To enter a password, scroll down to the PASSWORD screen in the CHANGE SETTINGS Submenu, press “E”,
using the UP and DOWN keys, scroll up or down to the desired letter or number, press the RIGHT arrow key to
move to the next space and select the desired letter or number, repeat for the remaining two spaces and then press
“E”. You will be asked to verify the password change. Retype the password to verify and press “E”.
It will be necessary to enter this password to gain access to the CHANGE SETTINGS submenu from this point.
To change the password just repeat the above instructions. To erase the password, thereby defaulting back to the
original unit setting, program blank spaces in the CHANGE PASSWORD screen.
If a password is lost or unknown, call your local service center for further instructions.
Courtesy of NationalSwitchgear.com

IB 6.1.2.8-1B
Page 14
ABB
=RECORDS MENU=
MPS Fault Event
SUBMENU
=MPS FLT EVENT=
Event : ##
Press "E"
Type: ###
Ticks: ###
Ia: ###
Ib: ###
Ic: ###
In: ###
Scroll up and down
using arrow keys
=RECORDS MENU=
Breaker Oper.
==BREAKER OPER==
Count: ######
Press "E"
KSIa: ####
KSIb: ####
KSIc: ####
Press "C"
Press "C"
6.5 RECORDS SUBMENU
KEYPAD INPUT SEQUENCE FOR RECORDS SUBMENU
E
Ia: ## Ib: ##
Ic: ## In: ##
C E
=RECORDS MENU=
VIM Fault Event
=VIM FAULT EVENT=
Type: ####
Vab: ###
Vbc: ###
Vca: ###
Press "E"
Press "C"
E E
C E
Press "Up
and Down"
Arrows
==MPS FLT EVENT==
Event: ##
=BREAKER OPER=
Count: ######
=VIM FAULT EVENT=
Type: ####
Courtesy of NationalSwitchgear.com
Other manuals for MPS-C 2000
1
Table of contents
Other ABB Control Unit manuals

ABB
ABB 500 Series User manual

ABB
ABB jokab safety Smile Tina Series User manual

ABB
ABB i-bus KNX User manual

ABB
ABB ACS880-1604 User manual

ABB
ABB NPBA-01 Installation manual

ABB
ABB ACL30-04 Series Troubleshooting guide

ABB
ABB FCAN-01 Installation manual

ABB
ABB WaveLINE 6731-21-500 User manual

ABB
ABB ACQ580-34 User manual

ABB
ABB REC650 ANSI Instructions for use

ABB
ABB Tina 5A User manual

ABB
ABB ACS880-04 drive modules User manual

ABB
ABB ACS580-04 User manual

ABB
ABB 650 series Instructions for use

ABB
ABB i-bus EIB User manual

ABB
ABB FPTC-02 User manual

ABB
ABB ACQ810 Use and care manual

ABB
ABB ACSM1 Series Use and care manual

ABB
ABB +P906 User manual

ABB
ABB COM600 series User manual