ABB Relion REC670 Instructions for use

RELION® 670 SERIES
—
Bay control REC670
Version 2.2 ANSI
Application manual


Document ID: 1MRK 511 401-UUS
Issued: October 2017
Revision: A
Product version: 2.2.1
© Copyright 2017 ABB. All rights reserved

Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party,
nor used for any unauthorized purpose.
The software and hardware described in this document is furnished under a license and
may be used or disclosed only in accordance with the terms of such license.
This product includes software developed by the OpenSSL Project for use in the
OpenSSL Toolkit. (http://www.openssl.org/) This product includes cryptographic
software written/developed by: Eric Young ([email protected]) and Tim Hudson
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.

Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or
product description and are not to be deemed as a statement of guaranteed properties.
All persons responsible for applying the equipment addressed in this manual must
satisfy themselves that each intended application is suitable and acceptable, including
that any applicable safety or other operational requirements are complied with. In
particular, any risks in applications where a system failure and/or product failure would
create a risk for harm to property or persons (including but not limited to personal
injuries or death) shall be the sole responsibility of the person or entity applying the
equipment, and those so responsible are hereby requested to ensure that all measures
are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested to
notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the use
of this manual or the application of the equipment.

Conformity
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for
use within specified voltage limits (Low-voltage directive 2006/95/EC). This
conformity is the result of tests conducted by ABB in accordance with the product
standard EN 60255-26 for the EMC directive, and with the product standards EN
60255-1 and EN 60255-27 for the low voltage directive. The product is designed in
accordance with the international standards of the IEC 60255 series and ANSI C37.90.

Table of contents
Section 1 Introduction..........................................................................21
This manual............................................................................................ 21
Intended audience.................................................................................. 21
Product documentation...........................................................................22
Product documentation set................................................................22
Document revision history................................................................. 23
Related documents............................................................................24
Document symbols and conventions...................................................... 24
Symbols.............................................................................................24
Document conventions...................................................................... 25
IEC 61850 edition 1 / edition 2 mapping.................................................26
Section 2 Application...........................................................................37
General IED application..........................................................................37
Main protection functions........................................................................38
Back-up protection functions.................................................................. 39
Control and monitoring functions............................................................ 40
Communication.......................................................................................48
Basic IED functions.................................................................................51
Section 3 Configuration....................................................................... 53
Description of configuration REC670......................................................53
Introduction........................................................................................53
Description of configuration A30...................................................53
Description of configuration B30...................................................55
Description of configuration C30.................................................. 57
Description of configuration D30.................................................. 59
Section 4 Analog inputs.......................................................................61
Introduction............................................................................................. 61
Setting guidelines................................................................................... 61
Setting of the phase reference channel.............................................61
Example........................................................................................62
Setting of current channels................................................................62
Example 1.....................................................................................63
Example 2.....................................................................................63
Example 3.....................................................................................64
Table of contents
Bay control REC670 2.2 ANSI 1
Application manual

Examples on how to connect, configure and set CT inputs
for most commonly used CT connections.................................... 67
Example on how to connect a wye connected three-phase
CT set to the IED.......................................................................... 68
Example how to connect delta connected three-phase CT
set to the IED................................................................................73
Example how to connect single-phase CT to the IED.................. 76
Relationships between setting parameter Base Current, CT
rated primary current and minimum pickup of a protection IED........ 78
Setting of voltage channels............................................................... 78
Example........................................................................................79
Examples how to connect, configure and set VT inputs for
most commonly used VT connections..........................................79
Examples on how to connect a three phase-to-ground
connected VT to the IED.............................................................. 80
Example on how to connect a phase-to-phase connected
VT to the IED................................................................................ 82
Example on how to connect an open delta VT to the IED for
high impedance grounded or ungrounded networks.................... 84
Example how to connect the open delta VT to the IED for
low impedance grounded or solidly grounded power systems..... 87
Section 5 Local HMI............................................................................ 91
Display.................................................................................................... 92
LEDs....................................................................................................... 95
Keypad....................................................................................................96
Local HMI functionality............................................................................98
Protection and alarm indication......................................................... 98
Parameter management ...................................................................99
Front communication....................................................................... 100
Section 6 Wide area measurement system.......................................101
C37.118 Phasor Measurement Data Streaming Protocol
Configuration PMUCONF..................................................................... 101
Identification.................................................................................... 101
Application....................................................................................... 101
Operation principle.......................................................................... 101
Short guidance for use of TCP................................................... 102
Short guidance for use of UDP...................................................103
Protocol reporting via IEEE 1344 and C37.118 PMUREPORT............ 105
Identification.................................................................................... 105
Application....................................................................................... 106
Table of contents
2Bay control REC670 2.2 ANSI
Application manual

Operation principle.......................................................................... 108
Frequency reporting................................................................... 110
Reporting filters.......................................................................... 112
Scaling Factors for ANALOGREPORT channels....................... 113
PMU Report Function Blocks Connection Rules in PCM600
Application Configuration Tool (ACT)......................................... 115
Setting guidelines............................................................................ 121
Section 7 Differential protection........................................................ 127
High impedance differential protection, single phase HZPDIF (87)......127
Identification.................................................................................... 127
Application....................................................................................... 127
The basics of the high impedance principle............................... 129
Connection examples for high impedance differential protection.... 135
Connections for three-phase high impedance differential
protection....................................................................................135
Connections for 1Ph High impedance differential protection
HZPDIF (87)............................................................................... 136
Setting guidelines............................................................................ 137
Configuration.............................................................................. 138
Settings of protection function.................................................... 138
T-feeder protection..................................................................... 138
Tertiary reactor protection.......................................................... 142
Alarm level operation..................................................................145
Section 8 Current protection..............................................................147
Instantaneous phase overcurrent protection PHPIOC (50).................. 147
Identification.................................................................................... 147
Application....................................................................................... 147
Setting guidelines............................................................................ 148
Meshed network without parallel line..........................................149
Meshed network with parallel line...............................................151
Directional phase overcurrent protection, four steps
OC4PTOC(51_67)................................................................................ 153
Identification.................................................................................... 153
Application....................................................................................... 153
Setting guidelines............................................................................ 154
Settings for each step.................................................................156
Setting example..........................................................................160
Instantaneous residual overcurrent protection EFPIOC (50N)............. 165
Identification.................................................................................... 165
Table of contents
Bay control REC670 2.2 ANSI 3
Application manual

Application....................................................................................... 165
Setting guidelines............................................................................ 165
Directional residual overcurrent protection, four steps EF4PTOC
(51N/67N)............................................................................................. 168
Identification.................................................................................... 168
Application....................................................................................... 169
Setting guidelines............................................................................ 171
Common settings for all steps.................................................... 171
2nd harmonic restrain.................................................................173
Parallel transformer inrush current logic.....................................173
Switch onto fault logic.................................................................174
Settings for each step (x = 1, 2, 3 and 4)................................... 175
Line application example............................................................ 178
Four step directional negative phase sequence overcurrent
protection NS4PTOC (46I2)..................................................................183
Identification.................................................................................... 184
Application....................................................................................... 184
Setting guidelines............................................................................ 186
Settings for each step ................................................................186
Common settings for all steps.................................................... 189
Sensitive directional residual overcurrent and power protection
SDEPSDE (67N)...................................................................................190
Identification.................................................................................... 191
Application....................................................................................... 191
Setting guidelines............................................................................ 193
Thermal overload protection, one time constant Fahrenheit/
Celsius LFPTTR/LCPTTR (26)............................................................. 202
Identification.................................................................................... 202
Thermal overload protection, two time constants TRPTTR (49)...........202
Identification.................................................................................... 202
Application....................................................................................... 202
Setting guideline.............................................................................. 203
Breaker failure protection CCRBRF(50BF)...........................................206
Identification.................................................................................... 206
Application....................................................................................... 206
Setting guidelines............................................................................ 207
Stub protection STBPTOC (50STB)..................................................... 210
Identification.................................................................................... 210
Application....................................................................................... 210
Setting guidelines............................................................................ 211
Table of contents
4Bay control REC670 2.2 ANSI
Application manual

Pole discrepancy protection CCPDSC(52PD)...................................... 212
Identification.................................................................................... 212
Application....................................................................................... 212
Setting guidelines............................................................................ 213
Directional underpower protection GUPPDUP (37)..............................214
Identification.................................................................................... 214
Application....................................................................................... 214
Setting guidelines............................................................................ 216
Directional overpower protection GOPPDOP (32)................................220
Identification.................................................................................... 220
Application....................................................................................... 220
Setting guidelines............................................................................ 222
Broken conductor check BRCPTOC (46)............................................. 226
Identification.................................................................................... 226
Application....................................................................................... 227
Setting guidelines............................................................................ 227
Capacitor bank protection CBPGAPC.................................................. 227
Identification.................................................................................... 227
Application....................................................................................... 228
SCB protection........................................................................... 230
Setting guidelines............................................................................ 232
Restrike detection.......................................................................234
Voltage-restrained time overcurrent protection VRPVOC (51V)...........235
Identification.................................................................................... 235
Application....................................................................................... 235
Base quantities........................................................................... 236
Application possibilities...............................................................236
Undervoltage seal-in...................................................................237
Setting guidelines............................................................................ 237
Explanation of the setting parameters........................................ 237
Voltage-restrained overcurrent protection for generator and
step-up transformer.................................................................... 239
Overcurrent protection with undervoltage seal-in....................... 239
Section 9 Voltage protection............................................................. 241
Two step undervoltage protection UV2PTUV (27)................................241
Identification.................................................................................... 241
Application....................................................................................... 241
Setting guidelines............................................................................ 242
Equipment protection, such as for motors and generators.........242
Table of contents
Bay control REC670 2.2 ANSI 5
Application manual

Disconnected equipment detection............................................ 242
Power supply quality ..................................................................242
Voltage instability mitigation....................................................... 242
Backup protection for power system faults.................................243
Settings for two step undervoltage protection............................ 243
Two step overvoltage protection OV2PTOV (59)................................. 244
Identification.................................................................................... 245
Application....................................................................................... 245
Setting guidelines............................................................................ 246
Equipment protection, such as for motors, generators,
reactors and transformers.......................................................... 246
Equipment protection, capacitors............................................... 246
Power supply quality...................................................................247
High impedance grounded systems........................................... 247
The following settings can be done for the two step
overvoltage protection................................................................ 247
Two step residual overvoltage protection ROV2PTOV (59N)...............249
Identification.................................................................................... 249
Application....................................................................................... 249
Setting guidelines............................................................................ 250
Equipment protection, such as for motors, generators,
reactors and transformersEquipment protection
for transformers.......................................................................... 250
Equipment protection, capacitors............................................... 250
Power supply quality...................................................................251
High impedance grounded systems........................................... 251
Direct grounded system..............................................................252
Settings for two step residual overvoltage protection................. 252
Voltage differential protection VDCPTOV (60)..................................... 254
Identification.................................................................................... 254
Application....................................................................................... 254
Setting guidelines............................................................................ 256
Loss of voltage check LOVPTUV (27).................................................. 258
Identification.................................................................................... 258
Application....................................................................................... 258
Setting guidelines............................................................................ 258
Advanced users settings............................................................ 258
Section 10 Frequency protection.........................................................259
Underfrequency protection SAPTUF (81).............................................259
Identification.................................................................................... 259
Table of contents
6Bay control REC670 2.2 ANSI
Application manual

Application....................................................................................... 259
Setting guidelines............................................................................ 260
Overfrequency protection SAPTOF (81)...............................................260
Identification.................................................................................... 261
Application....................................................................................... 261
Setting guidelines............................................................................ 261
Rate-of-change of frequency protection SAPFRC (81)........................ 262
Identification.................................................................................... 262
Application....................................................................................... 262
Setting guidelines............................................................................ 263
Frequency time accumulation protection function FTAQFVR (81A).....264
Identification.................................................................................... 264
Application....................................................................................... 264
Setting guidelines............................................................................ 266
Section 11 Multipurpose protection..................................................... 269
General current and voltage protection CVGAPC................................ 269
Identification.................................................................................... 269
Application....................................................................................... 269
Current and voltage selection for CVGAPC function..................270
Base quantities for CVGAPC function........................................ 273
Application possibilities...............................................................273
Inadvertent generator energization.............................................274
Setting guidelines............................................................................ 275
Directional negative sequence overcurrent protection............... 275
Negative sequence overcurrent protection.................................277
Generator stator overload protection in accordance with IEC
or ANSI standards...................................................................... 280
Open phase protection for transformer, lines or generators
and circuit breaker head flashover protection for generators..... 282
Voltage restrained overcurrent protection for generator and
step-up transformer.................................................................... 283
Loss of excitation protection for a generator.............................. 283
Section 12 System protection and control...........................................287
Multipurpose filter SMAIHPAC..............................................................287
Identification.................................................................................... 287
Application....................................................................................... 287
Setting guidelines............................................................................ 289
Setting example..........................................................................289
Table of contents
Bay control REC670 2.2 ANSI 7
Application manual

Section 13 Secondary system supervision..........................................293
Current circuit supervision (87).............................................................293
Identification.................................................................................... 293
Application....................................................................................... 293
Setting guidelines............................................................................ 294
Fuse failure supervision FUFSPVC...................................................... 294
Identification.................................................................................... 294
Application....................................................................................... 294
Setting guidelines............................................................................ 295
General.......................................................................................295
Setting of common parameters.................................................. 296
Negative sequence based.......................................................... 296
Zero sequence based.................................................................297
Delta V and delta I ..................................................................... 298
Dead line detection.....................................................................298
Fuse failure supervision VDSPVC (60).................................................299
Identification.................................................................................... 299
Application....................................................................................... 299
Setting guidelines............................................................................ 300
Section 14 Control...............................................................................303
Synchronism check, energizing check, and synchronizing
SESRSYN (25)..................................................................................... 303
Identification.................................................................................... 303
Application....................................................................................... 303
Synchronizing............................................................................. 303
Synchronism check.................................................................... 305
Energizing check........................................................................ 307
Voltage selection........................................................................ 308
External fuse failure....................................................................309
Application examples.......................................................................310
Single circuit breaker with single busbar.................................... 311
Single circuit breaker with double busbar, external voltage
selection..................................................................................... 312
Single circuit breaker with double busbar, internal voltage
selection..................................................................................... 313
Double circuit breaker.................................................................314
Breaker-and-a-half......................................................................315
Setting guidelines............................................................................ 318
Table of contents
8Bay control REC670 2.2 ANSI
Application manual

Autorecloser for 1 phase, 2 phase and/or 3 phase operation
SMBRREC (79).................................................................................... 323
Identification.................................................................................... 323
Application....................................................................................... 324
Auto reclosing operation Off and On.......................................... 327
Initiate auto reclosing and conditions for start of a reclosing
cycle........................................................................................... 328
Initiate auto reclosing from circuit breaker open information...... 328
Blocking of the auto recloser...................................................... 328
Control of the auto reclosing dead time for shot 1......................329
Long trip signal........................................................................... 329
Maximum number of reclosing shots..........................................330
ARMode
=
3ph,
(normal setting for a three-phase shot)............ 330
ARMode
=
1/2/3ph
..................................................................... 330
ARMode
=
1/2ph
, 1-phase or 2-phase reclosing in the
first shot...................................................................................... 331
ARMode
= 1ph+1*2ph, 1-phase or 2-phase reclosing in the
first shot...................................................................................... 331
ARMode = 1/2ph + 1*3ph, 1-phase, 2-phase or 3-phase
reclosing in the first shot.............................................................331
ARMode
= 1ph + 1*2/3ph, 1-phase, 2-phase or 3-phase
reclosing in the first shot.............................................................331
External selection of auto reclosing mode..................................332
Auto reclosing reset timer...........................................................333
Pulsing of the circuit breaker closing command and counter..... 333
Transient fault.............................................................................333
Permanent fault and reclosing unsuccessful signal....................333
Lock-out initiation........................................................................334
Evolving fault.............................................................................. 335
Automatic continuation of the auto reclosing sequence............. 336
Thermal overload protection holding the auto recloser back......336
Setting guidelines............................................................................ 336
Configuration.............................................................................. 336
Auto recloser settings................................................................. 345
Apparatus control APC......................................................................... 350
Application....................................................................................... 350
Bay control QCBAY.................................................................... 356
Switch controller SCSWI............................................................ 357
Switches SXCBR/SXSWI........................................................... 357
Proxy for signals from switching device via GOOSE
XLNPROXY................................................................................ 358
Table of contents
Bay control REC670 2.2 ANSI 9
Application manual

Reservation function (QCRSV and RESIN)................................361
Interaction between modules...........................................................363
Setting guidelines............................................................................ 367
Bay control (QCBAY)..................................................................367
Switch controller (SCSWI).......................................................... 367
Switch (SXCBR/SXSWI).............................................................368
Proxy for signals from switching device via GOOSE
XLNPROXY................................................................................ 369
Bay Reserve (QCRSV)...............................................................370
Reservation input (RESIN)......................................................... 370
Interlocking (3)...................................................................................... 370
Configuration guidelines.................................................................. 371
Interlocking for line bay ABC_LINE (3)............................................ 372
Application.................................................................................. 372
Signals from bypass busbar....................................................... 372
Signals from bus-coupler............................................................373
Configuration setting...................................................................377
Interlocking for bus-coupler bay ABC_BC (3)..................................378
Application.................................................................................. 378
Configuration.............................................................................. 378
Signals from all feeders.............................................................. 378
Signals from bus-coupler............................................................381
Configuration setting...................................................................382
Interlocking for transformer bay AB_TRAFO (3)..............................383
Application.................................................................................. 383
Signals from bus-coupler............................................................384
Configuration setting...................................................................385
Interlocking for bus-section breaker A1A2_BS (3)...........................386
Application.................................................................................. 386
Signals from all feeders.............................................................. 386
Configuration setting...................................................................389
Interlocking for bus-section disconnector A1A2_DC (3).................. 390
Application.................................................................................. 390
Signals in single breaker arrangement....................................... 390
Signals in double-breaker arrangement..................................... 393
Signals in breaker and a half arrangement.................................396
Interlocking for busbar grounding switch BB_ES (3)....................... 397
Application.................................................................................. 397
Signals in single breaker arrangement....................................... 398
Signals in double-breaker arrangement..................................... 402
Table of contents
10 Bay control REC670 2.2 ANSI
Application manual

Signals in breaker and a half arrangement.................................403
Interlocking for double CB bay DB (3)............................................. 404
Application.................................................................................. 404
Configuration setting...................................................................404
Interlocking for breaker-and-a-half diameter BH (3)........................ 405
Application.................................................................................. 405
Configuration setting...................................................................406
Voltage control......................................................................................407
Identification.................................................................................... 407
Application....................................................................................... 407
Setting guidelines............................................................................ 443
TR1ATCC or TR8ATCC general settings...................................443
TR1ATCC (90) or TR8ATCC (90) Setting group ....................... 444
TCMYLTC and TCLYLTC (84) general settings.........................454
Logic rotating switch for function selection and LHMI presentation
SLGAPC............................................................................................... 455
Identification.................................................................................... 455
Application....................................................................................... 455
Setting guidelines............................................................................ 455
Selector mini switch VSGAPC.............................................................. 456
Identification.................................................................................... 456
Application....................................................................................... 456
Setting guidelines............................................................................ 457
Generic communication function for Double Point indication
DPGAPC...............................................................................................457
Identification.................................................................................... 457
Application....................................................................................... 457
Setting guidelines............................................................................ 458
Single point generic control 8 signals SPC8GAPC...............................458
Identification.................................................................................... 459
Application....................................................................................... 459
Setting guidelines............................................................................ 459
AutomationBits, command function for DNP3.0 AUTOBITS................ 459
Identification.................................................................................... 460
Application....................................................................................... 460
Setting guidelines............................................................................ 460
Single command, 16 signals SINGLECMD.......................................... 460
Identification.................................................................................... 460
Application....................................................................................... 461
Setting guidelines............................................................................ 462
Table of contents
Bay control REC670 2.2 ANSI 11
Application manual

Section 15 Scheme communication.................................................... 465
Scheme communication logic for distance or overcurrent
protection ZCPSCH(85)........................................................................465
Identification.................................................................................... 465
Application....................................................................................... 465
Blocking schemes.......................................................................466
Delta blocking scheme............................................................... 467
Permissive schemes...................................................................468
Intertrip scheme..........................................................................472
Setting guidelines............................................................................ 472
Blocking scheme........................................................................ 472
Delta blocking scheme............................................................... 473
Permissive underreaching scheme............................................ 473
Permissive overreaching scheme...............................................473
Unblocking scheme.................................................................... 473
Intertrip scheme..........................................................................474
Current reversal and Weak-end infeed logic for distance protection
3-phase ZCRWPSCH (85)....................................................................474
Identification.................................................................................... 474
Application....................................................................................... 474
Current reversal logic................................................................. 474
Weak-end infeed logic................................................................ 475
Setting guidelines............................................................................ 476
Current reversal logic................................................................. 476
Weak-end infeed logic................................................................ 477
Local acceleration logic ZCLCPSCH.................................................... 477
Identification.................................................................................... 477
Application....................................................................................... 477
Setting guidelines............................................................................ 478
Scheme communication logic for residual overcurrent protection
ECPSCH (85)....................................................................................... 479
Identification.................................................................................... 479
Application....................................................................................... 479
Setting guidelines............................................................................ 480
Current reversal and weak-end infeed logic for residual
overcurrent protection ECRWPSCH (85)............................................. 481
Identification.................................................................................... 481
Application....................................................................................... 481
Fault current reversal logic......................................................... 481
Weak-end infeed logic................................................................ 482
Table of contents
12 Bay control REC670 2.2 ANSI
Application manual

Setting guidelines............................................................................ 482
Current reversal..........................................................................483
Weak-end infeed........................................................................ 484
Section 16 Logic..................................................................................485
Tripping logic SMPPTRC (94).............................................................. 485
Identification.................................................................................... 485
Application....................................................................................... 485
Three-pole tripping..................................................................... 486
Single- and/or three-pole tripping............................................... 487
Single-, two- or three-pole tripping............................................. 488
Lock-out......................................................................................489
Example of directional data........................................................ 489
Blocking of the function block..................................................... 491
Setting guidelines............................................................................ 491
Trip matrix logic TMAGAPC..................................................................491
Identification.................................................................................... 492
Application....................................................................................... 492
Setting guidelines............................................................................ 492
Logic for group alarm ALMCALH..........................................................492
Identification.................................................................................... 492
Application....................................................................................... 493
Setting guidelines............................................................................ 493
Logic for group alarm WRNCALH.........................................................493
Identification.................................................................................... 493
Application.................................................................................. 493
Setting guidelines....................................................................... 493
Logic for group indication INDCALH.....................................................493
Identification.................................................................................... 493
Application.................................................................................. 494
Setting guidelines....................................................................... 494
Configurable logic blocks......................................................................494
Application....................................................................................... 494
Setting guidelines............................................................................ 494
Configuration.............................................................................. 495
Fixed signal function block FXDSIGN...................................................496
Identification.................................................................................... 496
Application....................................................................................... 496
Boolean 16 to Integer conversion B16I.................................................497
Identification.................................................................................... 497
Table of contents
Bay control REC670 2.2 ANSI 13
Application manual

Application....................................................................................... 498
Boolean to integer conversion with logical node representation, 16
bit BTIGAPC......................................................................................... 499
Identification.................................................................................... 499
Application....................................................................................... 499
Integer to Boolean 16 conversion IB16.................................................500
Identification.................................................................................... 500
Application....................................................................................... 500
Integer to Boolean 16 conversion with logic node representation
ITBGAPC.............................................................................................. 501
Identification.................................................................................... 502
Application....................................................................................... 502
Elapsed time integrator with limit transgression and overflow
supervision TEIGAPC...........................................................................503
Identification.................................................................................... 503
Application....................................................................................... 503
Setting guidelines............................................................................ 503
Comparator for integer inputs - INTCOMP........................................... 504
Identification.................................................................................... 504
Application....................................................................................... 504
Setting guidelines............................................................................ 504
Setting example...............................................................................505
Comparator for real inputs - REALCOMP.............................................506
Identification.................................................................................... 506
Application....................................................................................... 506
Setting guidelines............................................................................ 506
Setting example...............................................................................507
Section 17 Monitoring..........................................................................509
Measurement........................................................................................509
Identification.................................................................................... 509
Application....................................................................................... 510
Zero clamping..................................................................................511
Setting guidelines............................................................................ 512
Setting examples........................................................................ 515
Gas medium supervision SSIMG (63).................................................. 522
Identification.................................................................................... 522
Application....................................................................................... 522
Setting guidelines............................................................................ 523
Liquid medium supervision SSIML (71)................................................ 524
Identification.................................................................................... 524
Table of contents
14 Bay control REC670 2.2 ANSI
Application manual
Other manuals for Relion REC670
6
Table of contents
Other ABB Control Unit manuals

ABB
ABB i-bus KNX User manual

ABB
ABB Relion 615 series User manual

ABB
ABB REF542plus User manual

ABB
ABB FCAN-01 User manual

ABB
ABB Welcome M2306 User manual

ABB
ABB RER 103 Operating and installation instructions

ABB
ABB RTAC-01 User manual

ABB
ABB FCAN-01 Installation manual

ABB
ABB FECA-01 EtherCAT User manual

ABB
ABB ACS880-304 +A003 Series User manual

ABB
ABB Foundation LD 810HSE Ex User manual

ABB
ABB RED615 ANSI User manual

ABB
ABB ACS880-14 User manual

ABB
ABB 500 Series User manual

ABB
ABB Welcome M2307 Setup guide

ABB
ABB REC 523 Product manual

ABB
ABB M4M Instruction Manual

ABB
ABB TA571-SIM User manual

ABB
ABB MTQ22-FBP.0 User manual

ABB
ABB COM600 series User manual