manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ADTRAN
  6. •
  7. Control Unit
  8. •
  9. ADTRAN Total Access 300 Series User manual

ADTRAN Total Access 300 Series User manual

Other manuals for Total Access 300 Series

11

This manual suits for next models

4

Other ADTRAN Control Unit manuals

ADTRAN NetVanta SHDSL User manual

ADTRAN

ADTRAN NetVanta SHDSL User manual

ADTRAN Job Aid+ 1442707G1 User manual

ADTRAN

ADTRAN Job Aid+ 1442707G1 User manual

ADTRAN Job Aid+ 1442981G8C User manual

ADTRAN

ADTRAN Job Aid+ 1442981G8C User manual

ADTRAN SFP+ 10G User manual

ADTRAN

ADTRAN SFP+ 10G User manual

ADTRAN Job Aid+ Total Access 5000 1442910G1C User manual

ADTRAN

ADTRAN Job Aid+ Total Access 5000 1442910G1C User manual

ADTRAN SFP User manual

ADTRAN

ADTRAN SFP User manual

ADTRAN Total Access 1500 FT1 DP Instruction Manual

ADTRAN

ADTRAN Total Access 1500 FT1 DP Instruction Manual

ADTRAN Total Access Quad BNC Instruction Manual

ADTRAN

ADTRAN Total Access Quad BNC Instruction Manual

ADTRAN ATLAS 800 Series Module QUAD E1 User manual

ADTRAN

ADTRAN ATLAS 800 Series Module QUAD E1 User manual

ADTRAN SFP User manual

ADTRAN

ADTRAN SFP User manual

ADTRAN Octal E&M User manual

ADTRAN

ADTRAN Octal E&M User manual

ADTRAN T200 H2TU-R User manual

ADTRAN

ADTRAN T200 H2TU-R User manual

ADTRAN E220 HFAC HDSL Product manual

ADTRAN

ADTRAN E220 HFAC HDSL Product manual

ADTRAN Total Access 300 User manual

ADTRAN

ADTRAN Total Access 300 User manual

ADTRAN TRACER QUAD E1 User manual

ADTRAN

ADTRAN TRACER QUAD E1 User manual

ADTRAN T400 Maintenance and service guide

ADTRAN

ADTRAN T400 Maintenance and service guide

ADTRAN MX2820 User manual

ADTRAN

ADTRAN MX2820 User manual

ADTRAN Total Access 300 Series Product manual

ADTRAN

ADTRAN Total Access 300 Series Product manual

ADTRAN T3 User manual

ADTRAN

ADTRAN T3 User manual

ADTRAN 1200065L1-1 User manual

ADTRAN

ADTRAN 1200065L1-1 User manual

ADTRAN OC-3 User manual

ADTRAN

ADTRAN OC-3 User manual

ADTRAN 1200222L1 User manual

ADTRAN

ADTRAN 1200222L1 User manual

ADTRAN Job Aid+ 1442804G1 User manual

ADTRAN

ADTRAN Job Aid+ 1442804G1 User manual

ADTRAN Job Aid+ 1442910G1 User manual

ADTRAN

ADTRAN Job Aid+ 1442910G1 User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

1
jobAid
DESCRIPTION
The Total Access®362S Single Family Unit (SFU) Optical Network
Terminal (ONT) is a Gigabit Passive Optical Network (GPON) ONT
with RF Overlay and Single Wire Return Device (SWRD) powering
(SFU ONT, P/N 4187712G2). The Total Access 300 Series has 2
POTS, and 2 Ethernet interfaces. The figure above illustrates the
SFU ONT inner enclosure. GPON technology provides a consistent
and common approach to advancing the public communications
network using:
♦Traditionaltelephoneservice[PlainOldTelephoneService(POTS)]
♦Highspeeddataservices(10/100/1000)
♦Videoservices
♦SWRDpoweringthroughETH 2(10/100)
ThisJobAidcoverstheelectronicsmodules(SFUONT)andhousings
listedinthefollowingtable:
NOTE
Refer to the Total Access 300 Series GigE SFU ONT with RF Overlay
and SWRD Powering Installation and Maintenance Guide (P/N
64187712G2-5) for more extensive installation instructions.
Total Access
362S
Description
1187712G2 Total Access 362S Electronics Module
Total Access
SFU Housings
Description
1187770G1 TotalAccessONTSpliceHousing
1187771G1 TotalAccessONTwithOptiTapHousing
RING
TIP
RING
TIP
FXS 0/1
FXS 0/2
ETH 0/1
ETH 0/2
POTS 2
ETH 1
CLEI
TIP RING
TEL. NUMBER
TIP RING
TIP RING
TIP RING
RF Connection
Surface
Mounting
Hole
Surface Mounting Hole
Hinge
Hinge
Security
Screw
Two-screw
Terminal
Bridges
Ethernet
Connections
Fiber Optic
Cable
Ground
Power
Ethernet Drop
POTS Drop
Ground and Power
Drop Callout
Ground Drop
Fiber Drop
ETH 2
SWRD Powering
Total Access 300 Series
GigE SF ONT
with RF Overlay and SWRD Powering
FRONT PANEL LEDS
INSTALLATION
AfterunpackingtheSFUONT,inspectitfordamage.Ifdamageisnoted,
fileaclaimwiththecarrierandthencontactADTRAN.Formoreinfor‐
mation,refertothewarranty.
Required Tools and Supplies
StandardtechniciantoolsareusedforinstallingSFUONT.Foracomplete
listofspecialtools,suppliesandtestequipment,refertotheTotalAccess
300SeriesGigESFUONTwithRFOverlayandSWRDPoweringInstallation
andMaintenanceGuide(P/N64187712G2‐5).
Mount the Enclosure
Completethefollowingstepstomounttheenclosure:
1. Chooseaverticalsurfacenearanapprovedground,butawayfrom
downspouts,permanentwatersprinklers,orotherwatersources.
Thesubscribershouldhaveeasyaccessfortesting.
2. Usethetopandbottomexternalmountingholesasatemplateto
markfastenerlocations.Usealeveltoensuretheunitislevelto
preventwarping.
3. Pre‐drillthemarkedlocationsandinstallfastenersoranchors
appropriatetothemountingsurface(eachanchorratedto15lbs
minimum).
4. MounttheSFUONTtothesideofthesubscriber’spremise.
TheElectronicsModuleisinstalledinthehousingandswingsopenon
hinges.Toreleasethismodule,loosentheSecurityScrew(refertothe
illustrationonthefirstpage)andswingtheelectronicsModuletotheleft.
CAUTION
!
Donotuseaknifetocuttheopeningintherubbergrommets.Thismay
resultinanexcessivelylargeholeandcompromisetheintegrityofthe
unitallowingmoistureintotheunit.
Label Status Description
POWER {
z
Off
Green
Nopower
PowerisOn
NETWORK
STATUS
z
z
z
Green
Yellow
Red
OLThasactivatedtheONT
OLTisdiscoveringandranging
TheOLThasshutdowntheONT
SWRD POWER
(ETH2)
{
z
Off
Green
Powerdisabled
PowerisOn
POTS 1 and 2 {
z
2
Off
Green
GreenFlashing
Fiberisdisconnected,GPONinter‐
faceisdown,orbothportsareidle
ordisabled
AtleaseoneportisOffHook
AtleastoneportisRinging
ETH 1 and 2 {
z
z
Off
Green
YellowFlashing
Linkisdown,noactivity,orAdmin‐
istrativelyShutdown
Linkisup
TXorRXactivity
Product P/N: 4187712G2
Issue Date: September 2010
Document P/N: 64187712G2-22C
264187712G2-22C
7. ReplacetherubbergrommetwhileclosingtheElectronicsModule.
ThisplaceslessstressonthewiringandallowstheElectronics
Moduletoclosewithoutpinchinganywiring.
Route OptiTap Fiber Drop Cable
Refertotheillustrationbelowforfiberinstallations:
1. PlacetheOptiTapfiberdropinthesamerubbergrommetchannel
asthegroundcable.Thegroundcableshouldbe“behind”theOpti‐
Tapfiber.
2. ConnecttheOptiTapfiber.
3. PlacetheOptiTapconnectorinthecut‐outinthehousing.
4. Connectthefibercabletotheconnectoronthebottomofthe
ElectronicsModule.
5. RoutethecablesothatwhentheElectronicsModuleisclosed,the
fiberisnotpinched.
NOTE
TherearewireroutingclipsonthelowerrightoftheElectronicsModule
housing.Itisrecommendedthatthesenotbeused.Routethepowerwires
sothattheyarenotpinchedwhentheElectronicsModuleisclosed.
Install SC/APC Optical Connection
NOTE
RefertotheTotalAccess300SeriesGigESFUONTwithRFOverlayand
SWRDPoweringInstallationandMaintenanceGuide(P/N64187712G2‐5)for
informationoninstallingtheSC/APCopticalconnection.
Toinstalltheopticalconnector,completethefollowing:
1. Withtheelectronicsmoduleswungopen,routethefiberthrough
themostdirectgrommetentranceandconnectittotheappropriate
SC/APCopticalconnection.
2. Checkthattherearenobendsinthefiberlessthan30mm(1.2
inches)radiusor60mm(approximately2.5inches)indiameter.
Whenthemaintenancedoorisclosed,itshouldnotcomeincontact
withthefiber.
Local Power Source Wiring
TheSFUONTneedstobepoweredbyaULListedPowerSupplysuitable
fortheapplicationwithOutputatLPSLevels.
ThisSFUONTshouldonlybeoperatedfromthetypeofcertified/listed
powersupplyrecommendedbythepowersupplymanufacturer.
Do not tie wrap
the optical cable.
Route it as shown.
Ground Drop
Rubber Grommet
Tie Wrap
Opti-Tap Connector
+12VDC
12VRTN
SIGRTN
ONBAT
REPBAT
BATMIS
LOWBAT
7
6
5
4
3
2
1
Ground Connection
Refertotheillustrationbelowandintheoppositecolumntoinstallthe
groundconnection:
1. Removetherubbergrommetfromthehousingandinserta#6solid
coppergroundwirethroughtherubbergrommet.
2. Replacetherubbergrommetinthehousing.
3. Routethegroundwire12inchesbelowfinishedgradebythe
shortestandmostdirectroutetotheACpowergroundsystem
MultiGroundedNeutral(MGN)ofthecustomerpremises.Ensure
thewireisfreeofanysharpbends.
4. Attachthegroundwiretothesideofthesubscriber’spremiseswith
stainlesssteelhalfmoonclampsortie‐wrapthegroundwiretothe
riserconduitoftheBuriedFiberDrop.
5. CleantheMGNconnectorwithemeryclothtoinsureastable
connection.
6. AttachthegroundwirefromtheSFUONTtotheMGNconnector
withtheappropriateULapprovedgroundclamp/fitting.
7. Coattheconnectionwithametalcorrosionpreventative.
8. AttachaWarningGroundTagtothisgroundingconnection.
Power/Alarm Connections
NOTE
WiringthePower/AlarmconnectorimproperlycoulddamagetheSFU.
TheSFUONTissuppliedwitha7‐conductorEuro‐TypePower/Alarm
Connector.TomakeconnectionsfromtheUPStothepowerconnector
completethefollowingsteps:
1. RemovethePower/AlarmConnectorbypullingitoutoftheelec‐
tronicsmodule.
2. Refertotheillustrationontheoppositecolumnand“LocalPower
SourceWiring”sectiontoassistincompletingthenextsteps.
3. RemovetherubbergrommetfromthehousingandinserttheUPS
cablethroughthegrommet.
4. ToterminatethetwoUPSpowerleads(Pins6and7)and,ifneeded,
thefivealarmstatusleadsinthepowerconnector,cutallwiresand
stripbacktheinsulation.LoosenallthescrewsonthePowerAlarm
Connector.Insertonewireatatimeandtightenthescrewstomake
anelectricalcontact.
5. ReinstallthePower/AlarmConnector.
6. TieWrapthewiresasappropriate.
123
+ 12VDC
12V RTN
SIG RTN
ON BAT
REP BAT
BATMIS
LOW BAT
7654321
+ 12VDC
12V RTN
SIG RTN
ON BAT
REP BAT
BAT MIS
LOW BAT
7654321
Euro-Type
Power/Alarm
Connector
Back of Electronics Module
64187712G2-22C 3
UsethePin‐Outinformationinthetablebelowasneeded.
CAUTION
!
Usecautionwhenroutingwiresandcables.Avoidseverebendingand
routingoversharpedges.Usegrommetswhenpossibletoavoidwearon
cableinsulation.
1. InstalltheUPScablethatrunsfromtheSFUONTtothePower/
AlarmConnectoroftheUPSviathecustomerprovidedPVCcon‐
duit(ormethodusedbyyourlocaltelephonecompanypractice).
2. Closetheelectronicsmoduleclosedandtightenthesecurityscrew
withthe5/32Hextamperproofbit.
3. Ifnecessary,tiewrapboththe#6groundwireandtheUPScable
runtotheBuriedFiberDropriserconduit.
POTS Connection
ThetelephoneserviceorPOTSconnectionscanbemadewitheithertwo‐
screwterminalbridges,orRJ‐11connectors.
Ifthetwo‐screwterminalbridgesareusedtheRJ‐11jacksprovidea
diagnostictestpoint.InsertinganRJ‐11jack(i.e.,telephonecableor
telephonetestset)willconnectthetelephonesettotheSFUONTandalso
disconnectthesubscriberservicefromtheSFUONTprovidingfault
isolationtotheSFUorpremiseswiring.
ToterminatethePOTSlinesonthetwo‐screwterminalbridgescomplete
thefollowing:
1. Trimeachwiretolengthandstripinsulation.Identifyeachpairin
theservicecable.
2. LoosenthescrewsfromtheTIP(green)andRING(red).
3. Wraptheappropriatewirearoundtheappropriatescrewand
tightenthescrewstosecuretheconnections.
POTScanalsobeconnecteddirectlytotheRJ‐11jack.Inthiscasethetwo‐
screwterminalbridgesbecomeisolatedandarenotused.
RF Connection
RoutetheRFcablethroughthelargegrommetatthebottomofthe
enclosureandattachittotheRFconnectorlocatedonbottomthe
electronicsModule.Refertotheillustrationonthefirstpageasneeded.
SWRD Installation
Refer to the figure below and complete the following steps:
Pin-Out
Power/Alarm
Description Pin-Out
UPS
1LOWBAT 1
2BATMIS 2
3REPBAT 3
4ONBAT 4
5SIGRTN 5
612VRTN 6
7+12VDC7
1. Whennotinuse,placewatersealingF‐connectorbootsorshrink
tubingon“A ” and“B”.
2. AttachedtheSWRDusingtheMountingPointstothecustomer’s
premesisincloseproximitytotheSFUONT.
3. GroundtheSWRDbyattachingoneendofan18‐gaugewire(or
larger)totheEarthGroundscrew.Attachtheotherendofthewire
tothesamegroundastheSFUONT.
4. RemovetheretainingscrewthatholdstheConnectorCovertothe
SWRD,andremovetheUpperandLowerRubberSeals.
5. ConnectpowertotheSWRDbyconnectingtheRJ‐45 ETH 2 SWRD port
oftheSFUONTtotheRJ‐45ONT + PWRConnectionPort(D)ofthe
SWRD.Refertothefollowingtableasneeded:
6. OncepowerisconnectedtotheSWRD,thePowerLEDwill
illuminatesteady.
7. PositiontheRJ‐45cablesintheslotsintheUpperandLowerRubber
Seals,andreinstallthemintheSWRD.
8. InstalltheConnectorCoverandsecuretheConnectorCoverusing
theRetainingScrew.Torquethescrewto5in‐lbs.
9. Usingcoaxialcable,connecttheTV/DHCTport(A)oftheSWRDto
theset‐topnetworkinsidethecustomer’shome.
10. Usingcoaxialcable,connecttheRFDropfromtheSFUONTtothe
ONT/PowerPort(B)ontheSWRD.
11. Tiewrapallwirestotheappropriatelocationstoprovidemaximum
stressreliefandminimizeanypotentialhazardstotheconnections.
SWRD RJ-45 Pin-Out
Pin Name Description ColorCode
1 TX+ TransmitPositive White/Orange
2TX‐TransmitNegative Orange
3 RX+ ReceivePositive White/Green
4Power +12VDC Blue
5Power +12VDC White/Blue
6RX‐ReceiveNegative Green
7 Ground N/A White/Brown
8Ground N/A Brown
Power
LED
ONT
LED
A
A: TV/DHCT Port. Starting at the home set-top connect to the data network
via the SWRD’s TV/DHCT port.
B: ONT/Power Port. Downstream video and power from ONT.
C. LAN Connection Port. Data connection for computer network.
D. ONT Connection Port. Data connection to the ONT and power from the ONT.
B
LAN
LED
D
C
Mounting
Point
Mounting
Point
Earth
Ground
Mounting
Points
(Connector Cover, Screw
and Rubber Seals removed
for illustration purposes)
For more information, refer to the Installation and Maintenance Practice (P/N 64187712G2-5)
available online at www.adtran.com.
Warranty:ADTRAN will replace or repair this product within the warranty period if it does not
meet its published specifications or fails while in service. Warranty information can
be found online at www.adtran.com/warranty.
©2010 ADTRAN, Inc. All Rights Reserved. *64187712G2-22C*
Ethernet 1 Port Connection
IftheONTisgoingtosupportupto1Gigabitoperation(10/100/1000),the
cableusedshouldberatedCAT‐6.Ifanethernetcableisnotavailable,
usetheEthernetRJ‐45Pin‐Outtablebelowandstripbackthejacketofthe
subscriberEthernetcableandconnectthe4‐pairtwistedwirestotheRJ‐45
PlugusinganRJ‐45crimper.
InserttheterminatedRJ‐45jackintotheappropriateRJ‐45ETH 1 Port
socketontheSFUONT.Refertotheillustrationonthefirstpageforthese
connections.
OPERATIONAL SPECIFICATIONS
♦VoltageRange:10.5to15VDC
♦MaximumCurrent:1.5Amps
♦OperationalTemperatureRange:–40°Cto+65°C
♦StorageTemperatureRange:–40°Cto+85°C
♦RelativeHumidity:95%,noncondensing
♦Dimensions:9.7”Wx12”Hx4”D(25cmx30cmx10cm)
♦Weight:3lbs0.8oz.(1.6kg),enclosureandelectronicsmodule
MAINTENANCE
TheSFUONTdoesnotrequireroutinehardwaremaintenancefornormal
operation.ADTRANdoesnotrecommendthatrepairsbeattemptedin
thefield.Repairservicesmaybeobtainedbyreturningthedefectiveunit
toADTRAN.Refertothewarrantyforfurtherinformation.Fieldsupport
forsoftwareisprovidedthroughupgradefacilities.
SAFETY AND REGULATORY COMPLIANCE
TheTotalAccess300SeriesSFUONTisNRTLListedtotheapplicableUL
safetystandards.TheTotalAccess300SeriesSFUONTsmeetorexceedall
theapplicablerequirementsofNEBS,andTelcordiaGR‐63‐CORE.
TheTotalAccess300SeriesSFUONTisintendedfordeploymentinthe
OutsidePlant(OSP)atlocationswheretheNECapplies(forexample,
CustomerPremises)andisintendedtobeinstalledbytrainedservice
personnel.ConfigurationCodesfortheSFUONTarelistedbelow.
Ethernet 1 Port RJ-45 Pin-Out
Pin Name Description ColorCode
1 TRD0+ Transmit/ReceivePositive White/Orange
2TRD0‐Transmit/ReceiveNegative Orange
3 TRD1+ Transmit/ReceivePositive White/Green
4 TRD2+ Transmit/ReceivePositive Blue
5TRD2‐Transmit/ReceiveNegative White/Blue
6TRD1‐Transmit/ReceiveNegative Green
7 TRD3+ Transmit/ReceivePositive White/Brown
8TRD3‐Transmit/ReceiveNegative Brown
Configuration Codes Input Output
PowerCode(PC) F C
TelecommunicationCode(TC) – –
InstallationCode(IC) A –
ThisdevicecomplieswithPart15oftheFCCrules.Operationissubjectto
thefollowingtwoconditions:
1. Thisdevicemaynotcauseharmfulinterference.
2. Thisdevicemustacceptanyinterferencereceived,including
interferencethatmaycauseundesiredoperation.
ChangesormodificationsnotexpresslyapprovedbyADTRANcould
voidtheuser’sauthoritytooperatethisequipment.
WARNING
!
The10/100/1000Base‐Tport(s)andPOTSareclassifiedasType4as
definedinAppendixBofGR‐1089‐COREIssue4,andaresuitablefor
connectiontointra‐buildingorunexposedwiringorcablingonly.Donot
metallicallyconnecttheseportstointerfaceswhichconnecttotheOutside
Plant(OSP)ortotheOSPwiring.The10/100/1000Base‐TportsandPOTS
aredesignedforuseasanintra‐buildinginterfaceonly(Type4portsas
describedinGR‐1089‐COREIssue4)andrequireisolationfromexposed
OSPcabling.TheadditionofPrimaryProtectorsisnotsufficient
protectioninordertoconnectthisinterfacemetallicallytoOSPwiring.
CAUTION
C
TheTotalAccess300SeriesSFUONTscontainaClass1LaserModulethat
complieswith21CFR1040.10and1040.11.
CAUTION
!
♦ ElectrostaticDischarge(ESD)candamageelectronicmodules.When
handlingmodules,wearanantistaticdischargewriststraptoprevent
damagetoelectroniccomponents.Placemodulesinantistaticpacking
materialwhentransportingorstoring.Whenworkingonmodules,
alwaysplacethemonanapprovedantistaticmatthatiselectrically
grounded.
♦ Thisequipmentmustbeconnectedtoaknown,reliableearthground
atalltimesduringinstallationandservice.RefertotheNational
ElectricalCode(NEC)andstate/localcodesfordetailsongrounding
requirements.A6AWGcoppergroundconductorshallbeusedto
connecttheequipmenttoearthground.
♦ PerGR‐1089‐COREtheTotalAccess300SeriesSFUONTsaredesigned
andintendedforinstallationaspartofaCommonBondingNetwork
(CBN).TheTotalAccess300SeriesSFUONTarenotdesignednor
intendedforinstallationaspartofanIsolatedBondingNetwork
(IBN).
♦ PerGR‐1089‐CORESection9,theSFUONTsdonothaveaninternal
DCconnectionbetween12Vandframeground.
♦ TheTotalAccess300SeriesSFUONTsChassisframegroundterminal
mustbeconnectedtoanearthgroundtoensuretheONTSFUis
properlygrounded.
NOTE
♦ Powersupplyinputandoutputconductorsofequipmentwhichare
outsideofthebuilding,areintendedtobelessthat140feetandhave
adequateclearancefrompowerandlightningconductorsin
accordancewithNEC725and800.FinalacceptanceoftheListed
equipmentinstallationwillultimatelybeuptothelocalAuthority
HavingJurisdiction(AHJ).
♦ Themainfeedisopticalandthereforenotclassifiedasanytypeofport
asdefinedinAppendixBofGR‐1089‐COREIssue4.
♦ TheTotalAccess300SeriesSFUONTsaredesignedtooperatewith
nominaloperatingvoltageof12VDCandaminimumoperating
voltageof10.5VDC.TheTotalAccess362willnotbedamagedbyany
steadystatevoltagebetween10.5VDCand15.0VDCinmagnitude.
C A U T I O N
C A U T I O N
!
SUBJECT TO ELECTROSTATIC DAMAGE
OR DECREASE IN RELIABILITY.
HANDLING PRECAUTIONS REQUIRED.
ADTRAN CUSTOMER CARE:
From within the U.S. 1.800.726.8663
From outside the U.S. +1 256.963.8716
PRICING AND AVAILABILITY 1.800.827.0807