Function Description .................. 2
Component Parts ....................... 2
Safety regulations....................... 2
Control Device............................ 3
Installation .................................. 4
Functional testing....................... 5
Operation.................................... 6
Troubleshooting ......................... 7
Technical data ............................ 8
Declaration ................................. 8
Keep this manual for
future use!
VA-ALERT W
Full Tank Alarm for sewage tanks

AFRISO EMA AB • Kilvägen 2, 232 37 Arlöv, Sweden • Tel +46-40-92 20 50 • [email protected] • www.afriso.se
2
VA-ALERT W
Full Tank Alarm for sewage tanks • Installation instructions
Subject to design modifications.
VA-ALERT W
Alarm unit must not be disposed
with household garbage, but should
be handled as electronic waste.
Safety /
important to consider
• Carefully read the installation manual
before assembly
• The alarm apparatus may only be installed in
dry indoor spaces.
• The equipment may only be used for indica-
tion of high level alarm in the sewage tanks or
water tanks.
• Not to be used in conjunction with oil
or petrol!
• If the idea is to be buried, ensure that the
sensor can be accessed simply by mounting
a manhole, etc.
• The sensor has a standard 2 m cable.
Longer needed should the sensor cable
extended by Cable: RKK 2 x 0.75 mm2.
Use not multicore cable (for pump control
signals or the like).
Function Description
VA Alert W sewage tanks is a wireless alarm for
(closed) sewage tanks. The system consists of
a receiver unit for indoor as well as a battery-
powered transmitter module (VA Alert W / T)
sensor for placement under the cap to the tank.
This unit has an estimated run time of approx-
imately 12 months. The central unit has built-in
relay which enables connection to eg alarm
lamp or SMS alert.
VA Alert W is for cisterns / tanks containing
electrically conductive fluids. Full Tank Alarm
is given when the tank content have reached to
the two electrodes at the VA probe’s lower part.
The transmitter unit is battery powered and
powered by 2 AA batteries. The unit has built-in
warning of low battery voltage which warns in
good time before the battery is depleted (about
2-3 months before).
Components parts
VA-probe with a transmitter module
+
!

AFRISO EMA AB • Kilvägen 2, 232 37 Arlöv, Sweden • Tel +46-40-92 20 50 • [email protected] • www.afriso.se 3
VA-ALERT W
Full Tank Alarm for sewage tanks • Installation instructions
Subject to design modifications.
Press here.
+ -
12 VDC
NO C NC
Relay
output
Hold down the button and insert the battery.
When both LEDs are lit for about 1 second
at the same time, release the button now.
Both LEDs show flashing, 10 seconds in
between. After about 10 minutes a return to
normal operation.
If necessary, move the receiver unit to a
location where the transmitter’s signal can
be received safely.
External connection
VA-Alert W/R
Control Device
Check the alarm function
Short the sensor input with a paper clip or
similar, alternatively connect the sensor
and dip the electrode in water. Within
about 30 seconds, the buzzer sounds in
the receiver and the red LED will flash.
Press the button on the receiver -> sound
is muted. Remove the short circuit, alter-
natively, take the transmitter out of the
water. The red LED should go off within 30
seconds. Testing the alarm function is OK.
Range Test
Before assembly it must be tested on the
location of the receiver can receive the
radio signal from the transmitter. Place the
receiver at the desired location and con-
nect the AC adapter. Place the transmit-
ter module in place in the well during the
”cap”. Remove the battery from the battery
holder.
NOTE! There are many things that can in-
terfere with the radio signal. For example,
cars and bicycles placed between trans-
mitters and receivers can adversely affect
the signal. Therefore, it is very important
that the same conditions also apply after
range tests.

AFRISO EMA AB • Kilvägen 2, 232 37 Arlöv, Sweden • Tel +46-40-92 20 50 • [email protected] • www.afriso.se
4
VA-ALERT W
Full Tank Alarm for sewage tanks • Installation instructions
Subject to design modifications.
Installation
Installation should be done by qualified and
competent electrician.
Mounting the probe:
For the probe through the tank connection
and screw the sensor connector in the
cistern sleeve.
Insert the cable through the gland and
connect the sensor cable as shown below.
Insert the batteries and slide the circuit
board into the housing. Press the lid and
tighten the cable gland.
Install the mounting bracket in a suitable
place in the tank neck during the manhole
cover. See picture below. Use the supplied
plugs and screws.
Mounted on the far side in relation to the
receiver for best signal.
Place the transmitter electronics of the
holder and close the holder. Place the elec-
tronics with the cable pointing downwards
and a position as high up as possible in the
well to ensure that good scope as possible.
See picture below.
Placing the sensor in the tank is suitably in
the sleeve on the tank. The sensor has
a 1” connection. Height tank is adjusted by
sliding the sensor to the desired position
and fixed bytighten the adjustment screw in
1” terminal. Depending on the type of tank/
neck tank sensor may have to be mounted
in other ways. For instructions, contact the
tank manufacturer. See examples below.

AFRISO EMA AB • Kilvägen 2, 232 37 Arlöv, Sweden • Tel +46-40-92 20 50 • [email protected] • www.afriso.se 5
VA-ALERT W
Full Tank Alarm for sewage tanks • Installation instructions
Subject to design modifications.
Open here.
Press here.
Button 1.
Button 2.
Functional testing:
Control Device
• The alarm consists of a transmitter unit
VA Alert W / T with a conductive sensor
for placement in the sewage tank / cis-
tern. This unit is powered by 2 AA bat-
teries.
• Receiver VA Alert W / R for placement
on the wall indoors in a dry location.
The unit is powered by an included
power supply unit (12VDC).
Connect the AC adapter to the receiving
device. The unit should be flashing green
and red and a beep is emitted. Thereaf-
ter the unit flashes quickly about every 3
seconds.
To pair the devices
Hold button 1 down until the red flash and
green flash simultaneously every other
time. Now it is possible to pair the sender
and receiver. Keep pressing button 1 down
and press also down button 2 on the
receiver until green LED remains lit. Con-
tinue to hold down both buttons until the
green light LED disappears and the buzzer
sounds for approximately one second.
Release the buttons, the pairing is
complete.
Pairing of transmitter and receiver
(is already done upon delivery):
For use, the transmitter and receiver are
paired with each other. This is done upon
delivery. If the transmitter or receiver is
changed, the pairing must be redone.
Open the transmitter part by pulling in one
cover. The lid is sealed with O-ring (see
picture above). Remove the circuit board
and insert 2 AA batteries in the battery
holder.

AFRISO EMA AB • Kilvägen 2, 232 37 Arlöv, Sweden • Tel +46-40-92 20 50 • [email protected] • www.afriso.se
6
VA-ALERT W
Full Tank Alarm for sewage tanks • Installation instructions
Subject to design modifications.
”Alarm”-LED
”Normal”-LED
”Mute”-button
CAUSE/ERROR SOLUTION
Normal operation/No alarm Normal operation - no action
Green LED flashes briefly every two seconds.
Tank full Order emptying of the tank!
The built-in buzzer beeps and the red
LED flashes briefly every two seconds.
Low battery in the transmitter unit Change the batteries (2 AA batteries)
The built-in buzzer beeps and the red
and the green LED flashes briefly every two
second. (Can also be sensors in the liquid).
Operation:

AFRISO EMA AB • Kilvägen 2, 232 37 Arlöv, Sweden • Tel +46-40-92 20 50 • [email protected] • www.afriso.se 7
VA-ALERT W
Full Tank Alarm for sewage tanks • Installation instructions
Subject to design modifications.
CAUSE/ERROR SOLUTION
No LED flashing Check that the battery eliminator is
connected.
Weak radio signal Check range if necessery
(Radio signal not received within 24 hours) replace the placement of the receiver
Indicated by a red LED flashing twice. unit.
Check the batteries in the transmitter
unit.
Sensors in the liquid but not alarm unit. As above. Note that the transmission
of the the alarm is repeated every 6
hours.
Sensors in the air but the unit does not alarm. As above. Note that sending sensors
that are in the air is repeated every 6
hour.
”Alarm”-LED
”Normal”-LED
”Mute”-button
Troubleshooting:

Afriso EMA AB 2023-02-22
Afriso Ema AB
Kilvägen 2 • 232 37 Arlöv • Sweden
Phone: +46-40-92 20 50 • Fax: +46-40-19 33 58
www.afriso.se
VA-ALERT W Full Tank Alarm for sewage tanks • Installation instructions
Technical data:
VA-ALERT W/(R) - Alarm unit - Receiver
Power Supply: 12 V Plug-in Power
alt 12 VAC-trafo.
Temperature Range: 0 – 40 °C (operating)
-25 – +40 °C (during storage)
Relay Contact: Voltage free
Um 75 VDC, Im 2 A
Radio frequency 433 Mhz (free band)
receivers:
Degree of protection: IP 42
Measurements: 62 x 112 x 32 mm (BxHxD)
Weight: 85 g
VA-ALERT W/(T) - Alarm unit - Transmitter
Measuring principle: Conductive
Power Supply: 2 st AA-batteries
Alkaline type.
Radio frequency 433 Mhz (free band)
transmitter:
Measurements: ø 50 x 110 mm (diam x L)
Weight: 130 g
Temperature Range: -15 – +40 °C (during storage)
Degree of protection: IP 65
Declaration
Manufacturer: Afriso Ema AB,
Kilvägen 2, SE-232 37 Arlöv
Product: VA-ALERT W, Full Tank Alarm
for sewage tanks.
Technical Details: DC 4,5 V, IP42
The above-mentioned product
complies with the following European
directives and standards.
Directive for electromagnetic compatibility:
- EN 61000-6-4 (2007)
- EN 61000-6-1 (2007)
Low Voltage Directive:
- EN 61010-1 (2010)
Sign.
Urban Nilsson
Technical Manager
Date: 2015-03-11
Table of contents
Other AFRISO Security System manuals

AFRISO
AFRISO AG 11 User manual

AFRISO
AFRISO GS 1.1 User manual

AFRISO
AFRISO WGA 01 User manual

AFRISO
AFRISO WMS-WP6 User manual

AFRISO
AFRISO OM 1 User manual

AFRISO
AFRISO WGA 01 D User manual

AFRISO
AFRISO VA-ALERT User manual

AFRISO
AFRISO OM 1 User manual

AFRISO
AFRISO WMS-WP6 User manual

AFRISO
AFRISO WWG 1 User manual