© 2021 Alarmtech www.alarmtech.se Alarmtech reserves the right to changes CD470 manual 2124en Page 1of 2
DETECTORS
Shock- and vibration detector
DATASHEET AND INSTALLATION MANUAL CD 470
DESCRIPTION
CD 470 offers reliable monitoring against attacks with
mechanical tools. The CD 470 is a chock- and vibration
detector with 3 separate detection channels: an integra-
tion channel / saw channel for weak signals with long
duration, a counting channel that senses strong impact
on the monitored surface and an explosion channel
which senses very strong signals from e.g. an explosion.
CD 470 shares design with CD 475 but has built-in relays
for the alarm and tamper outputs. This allows the CD 470
to be connected directly to the alarm central unit, this
means that no analyser unit is necessary.
CD 470 is polarity independent, just like CD 475.
FEATURES
Relay outputs for alarm and tamper
Polarity independent for easy connection
3 separate detection channels
Cover radius up to 3m
Resistant to interference
Detailed sensitivity setting
Suitable for 24-hour monitoring
DAY and NIGHT control of LED
OPERATING PRINCIPLE
The CD 470 uses a piezoelectric sensor to monitor the vibration
signature of the mounting surface that occurs when it is
crushed or cut with tools. The signal has a special signature
with a broad spectrum and high amplitude that the electronics
detects, then opens the alarm relay and illuminates the LED.
The CD 470 has a built-in self-control and voltage monitoring.
Fault is indicated by a flashing LED (alarm relay remains closed).
The indication is controlled by a DAY and NIGHT function. With
8Vdc on the power input, DAY mode is active and LED lights up
at alarm and with pulsating shine in case of failure. At 6Vdc,
NIGHT mode is active and LED is switched off in case of alarm
or fault.
Resetting the detector after alarm can be done in two different
ways:
Disconnect power to the detector
Switch from DAY to NIGHT mode
MOUNTING
1. Loosen the screw for the cover and lift it off.
2. Select the mounting location and mark the mounting holes
with the bottom part as a template.
3. Drill with a 2-2.5 mm drill for the two supplied mounting
screws.
NOTE! A clean and smooth mounting surface under the
detector provides maximum range.
CONNECTIONS
The detector has 6 screw terminals:
#
Function
1
DC Input voltage (-) or (+)
2
DC Input voltage (-) or (+)
3
Alarm output, relay (NC)
4
Alarm output, relay (C)
5
Tamper output, relay (NC)
6
Tamper output, relay (C)
© 2021 Alarmtech www.alarmtech.se Alarmtech reserves the right to changes CD470 manual 2124en Page 2of 2
DIP-SWITCH
The DIP switch with 6 switches is used to program the functions
of the detector.
DIP Sensitivity (1 = lowest sensitivity, 8 = highest)
1
2
3
4
5
6
7
8
1
OFF
OFF
OFF
OFF
ON
ON
ON
ON
2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
3
OFF
ON
OFF
ON
OFF
ON
OFF
ON
DIP Counting Channel, Number of hits
3
6
4
OFF
ON
DIP Saw/Integration Channel
Integration Channel
OFF
Integration Channel ON
5
OFF
ON
DIP Autoreset of alarm (after 4 s)
Autoreset OFF
Autoreset ON
6
OFF
ON
DETECTION RADIUS
The approximate range of different materials is given in the
table below. Note, however, that the stated numbers only
serve as guide values and are strongly dependent on joints etc.
The actual range must be determined in practical tests.
Material
Wood/Glass/
Plywood
Brick*/
Plastering*
Steel/Concrete *
Radius
r = 2 m
r = 1 m
r =3 m
COMMISSIONING AND ADJUSTMENT
NOTE! For detector to show short blink, following procedure
must be done within 5 minutes after detector is powered on.
Commissioning and adjustment is very simple. Check that the
Autoreset is active (DIP 6 ON), the LED will then indicate when
the detector is alarmed, and after about 4 seconds, the alarm
goes out while the alarm relay closes. The counting channel
causes each received pulse to be displayed with a short flash on
the LED until the number of pulses set is reached (3 or 6), then
alarm is indicated. The alarm is indicated by a steady light as
long as the alarm relay is open.
1. Set the DIP switch to medium sensitivity, 6 hits, active saw
channel and auto reset. This is done by setting DIP 1=OFF
and DIP 2-6=ON.
2. Tap next to the detector and check that each tap is regis-
tered and that the alarm relay opens after 6 pulses.
3. Now tap relatively strongly with eg. the back of a screw-
driver on the most remote point to be protected.
4. If the pulses are not detected (short flash on the LED),
incrementally increase the sensitivity with DIP 1-3 as
shown in the table until the LED shows the received pulse.
5. If the diode instead shows alarm directly (steady light),
reduce the sensitivity incrementally with DIP 1-3 according
to the table until the LED shows the received pulse.
6. Check and adjust all connections. Finally, check that both
the alarm output and the tamper switch are received cor-
rectly at the control panel.
A fairly common mistake is to set higher sensitivity than
required, which results in false alarms. We therefore
recommend to not connect the detector in live operation
until after a few weeks so that the setting has been veri-
fied.
* When mounting on brick / plaster / concrete, the mounting
plate MP550 must be used for correct
operation.
TECHNICAL DATA
Detection radius
Up to 3m
Input voltage
8 –15 VDC (DAY mode), 6 VDC (NIGHT mode)
Max. ripple
0.2 Vpp at 12 V
Current consumption (typical) quiescent
8.0 mA (at 12 V)
Current consumption (typical) alarm
7.1 mA (at 12 V)
Alarm output
Relay (Max 50V / 120 mA), R < 30 Ω
Alarm indication
LED, DAY/NIGHT controlled
DAY and NIGHT control
DAY≥8 V, NIGHT=6 V input voltage
Alarm time
4s (when Auto Reset) or latching
Alarm reset
Input voltage below 1 V
Tamper protection
Pry-off and cover removal
Tamper output
Relay (Max 50V / 120 mA), R < 30 Ω
Low voltage alarm or fault in electronics
<5V indicated by flashing LED
Environmental class (EN50130-5:2011)
II
Operating temperature range
-40°C till +55°C
Operating humidity
max. 95% RH
Housing
White ABS plastic, IP 42
Size [H x D x W]
20 x 23 x 80 mm
Approvals
EN 50131-2-8 Grade 3 (EN-ST-000263), SSF 1014-5 Klass 3 (20-33),
VdS 2480 Klasse B (G121502)
INCERT (B-582-1001, only approved as shock detector)
ORDERING INFORMATION
CD 470
Shock- and vibration detector Grade 3
Mounting plate MP 550
Mounting plate suitable for CD 470

Other Alarmtech Security Sensor manuals

Alarmtech MC 746-E User manual

Alarmtech

Alarmtech MC 746-E User manual

Alarmtech GD 375 Instruction Manual

Alarmtech

Alarmtech GD 375 Instruction Manual

Alarmtech MC 740-E-M14 User manual

Alarmtech

Alarmtech MC 740-E-M14 User manual

Alarmtech AD 800 Manual

Alarmtech

Alarmtech AD 800 Manual

Alarmtech AD 800-AM Manual

Alarmtech

Alarmtech AD 800-AM Manual

Alarmtech GD 370 User guide

Alarmtech

Alarmtech GD 370 User guide

Alarmtech MC 472 User manual

Alarmtech

Alarmtech MC 472 User manual

Alarmtech MC 740-E User manual

Alarmtech

Alarmtech MC 740-E User manual

Alarmtech MC 340 2x4,7k User manual

Alarmtech

Alarmtech MC 340 2x4,7k User manual

Alarmtech MC 346 User manual

Alarmtech

Alarmtech MC 346 User manual

Alarmtech CD 400 User manual

Alarmtech

Alarmtech CD 400 User manual

Alarmtech MC 470 User manual

Alarmtech

Alarmtech MC 470 User manual

Alarmtech CD 470-I User manual

Alarmtech

Alarmtech CD 470-I User manual

Alarmtech AD 700 User manual

Alarmtech

Alarmtech AD 700 User manual

Alarmtech MC 140 User manual

Alarmtech

Alarmtech MC 140 User manual

Alarmtech MC 740-E User manual

Alarmtech

Alarmtech MC 740-E User manual

Alarmtech GD 335 User manual

Alarmtech

Alarmtech GD 335 User manual

Alarmtech CD 470 User manual

Alarmtech

Alarmtech CD 470 User manual

Popular Security Sensor manuals by other brands

SKF 234-13163-9 Service manual

SKF

SKF 234-13163-9 Service manual

Autonics PR Series product manual

Autonics

Autonics PR Series product manual

Orno OR-GB-430 Operating and instalation instructions

Orno

Orno OR-GB-430 Operating and instalation instructions

STEINEL IS 345 MX PF manual

STEINEL

STEINEL IS 345 MX PF manual

Haneco SKYLUX Smart Control installation guide

Haneco

Haneco SKYLUX Smart Control installation guide

quiko QK-FTP40 Operating and installation instructions

quiko

quiko QK-FTP40 Operating and installation instructions

Bosch DS306E installation instructions

Bosch

Bosch DS306E installation instructions

Knick ProLine P52000 VPD user manual

Knick

Knick ProLine P52000 VPD user manual

Bosch D-tect 120 Professional instructions

Bosch

Bosch D-tect 120 Professional instructions

Elk Products ELK-319WA manual

Elk Products

Elk Products ELK-319WA manual

Yale ENA-DC SmartHome Alarm series user manual

Yale

Yale ENA-DC SmartHome Alarm series user manual

Extech Instruments 401050 user guide

Extech Instruments

Extech Instruments 401050 user guide

Interlogix TX-2810-01-4 Installation sheet

Interlogix

Interlogix TX-2810-01-4 Installation sheet

OKM FS Future Series user manual

OKM

OKM FS Future Series user manual

Jung DWPM17360AL manual

Jung

Jung DWPM17360AL manual

Ursalink EM300 Series user guide

Ursalink

Ursalink EM300 Series user guide

Baumer UNDK 20I6903/S35A manual

Baumer

Baumer UNDK 20I6903/S35A manual

Interlogix AP633A installation instructions

Interlogix

Interlogix AP633A installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.