
18
Two Stage Variable Speed Sequence of Operation
White-Rodgers 50V61 Series Integrated
Furnace Control
When the service disconnect 1is in the “ON” position,
power is applied through the blower door interlock
switch 3to the controls line voltage input terminals 6and
out of the control to the primary side of the
control transformer 9,and from the “CIRC” 7
terminal to the ECMTM Fan Motor 3. The secondary
side of the control transformer supplies 24 volts to the
control through terminal “TH” and “TR” we. Control
terminal “R” gsupplies 24 volts to the “R” terminal of
the room thermostat.
Once power is applied, the control flashes the LED
light “ON” for one second and performs a self
check routine. Following the normal system check,
the control flashes the LED one time per second (slow
flash) continuously while in stand-by.
On a call for heat, 24 volts is applied from the room
thermostats “W1” terminal to the “W1” terminal g
on the control. The control checks and confirms
normally closed contacts at the temperature cut
out “TCO” a, auxillary limit (downflow and some
upflow/horizontal models), the flame roll-out bi-metal
control (two bi-metal controls are now used on
downflow/horizontal models) aand normally open
contacts at the safety pressure switch #1 p. With all
safety and control switches in their proper position,
the control will energize the induced draft motor
on high speed 9and flash the LED two times per
second continuously (fast flash) during a call for heat.
When safety pressure switch “#1” pcloses, the
control switches the induced draft motor to low
speed 0and begins the ignition sequence. The hot
surface ignitor 9is energized for several seconds
allowing the thermal element to heat up. The control
then switches 24 volts to its “MVL” iand “MV
COM” uterminals to terminals #1 iand #2 uon
the gas valve. The redundant and main solenoids are
energized allowing gas flow and main burner ignition.
When flame current is sensed by the control through
its “FP” fterminal, the 45 second indoor blower
motor time delay “ON” begins. Flame failure response
time is set for two seconds. After flame has been
established for ten seconds, the flame failure response
time is reset for 0.7 seconds. If flamed current is not
sensed by the control fwithin the trial for ignition
period, the main valve low and redundant gas valve
solenoids iare de-energized. The control will begin
a 30 second interpurge cycle and adds additional
seconds (see note) to the hot surface ignitor warm-up
timing. The control energizes the gas valve for the
second attempt to establish main burner ignition.
If again flame current is not sensed by the control
within the trial for ignition period (see note), the
control will repeat the previous cycle before locking
out. At the end of the indoor blower motor delay
“ON” timing, the microprocessor will close the
normally open K3 relay contacts j completing a
24 volt signal circuit to pin #15 of the ECMTM motor,
signaling it to turn on and run at the low heat blower
speed, supplying warm air to the space. 24 volts
W1 gterminal from the thermostat is also applied
to the ECMTM motor harness pin #12 h, which signals
the ECMTM motor to run at the low heat speed setting.
If the temperature in the space continues to fall, the
thermostat second stage contacts “W2” close.
24 volts are switched from thermostat terminal “W2” to
the “W2” terminal gon the control. A 30 second,
2nd stage recognition time delay begins. At the end
of the 30 second delay, the induced draft motor is
switched to high speed 9causing pressure switch
#2 oto close. When pressure switch #2 closes,
24 volts is switched from control terminal “MVH” oto the
gas valve terminal #3 oenergizing the second
stage solenoid, allowing increased gas flow to the
burners. At the same time, the microprocessor
closes the normally open K1 relay contacts j
completing a 24 volt signal circuit to pin #13 k of the
ECMTM2 motor signaling the indoor blower motor to
run at the high heat blower speed.
When second stage thermostat contacts “W2” satisfy,
the induced draft motor is switched back to low
speed 0causing pressure switch #2 yto open,
breaking the circuit to the second stage gas
valve solenoid y. Gas flow is reduced to the burners.
The indoor ECMTM blower motor 4will be switched
back to the low heat fan speed after a 30 second delay.
When first stage thermostat contacts “W1” satisfy,
the main valve low and the redundant gas valve
solenoids iare de-energized extinguishing main
burner flame. Once the control senses the loss of
flame current (0.7 sec.) f, the induced draft motor 9
is de-energized after a five second post-purge cycle.
The indoor blower motor “OFF” timing begins. At the
end of the indoor blower motor “OFF” timing, the indoor
blower motor is de-energized and the cycle is complete.
Note: See Timing Chart for details or the Integrated Furnace
Control Label.