manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Autometers Systems
  6. •
  7. Measuring Instrument
  8. •
  9. Autometers Systems A-35M User manual

Autometers Systems A-35M User manual

P2
S1
S2
P2
S1
S2
P2
S1
S2
LOAD
MAINS
LOAD
TX-TX+
1 2
+ - +
1A FAST BLOW FUSE 1A FAST BLOW FUSE
AUX
L1
L2
L3
N
L1
L2
L3
SHIELD
S0 RS485 Current inputs
9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8
Voltage inputs L N L N
Pulse Modbus L3 L2 L1
S2 S1 S2 S2 S1S1
Electrician
The A35M meter should only be installed by a fully qualified electrician who has
knowledge of electricity meters connected with current transformers.
It is the installer who is fully responsible for the safe installation of this meter. It must be
installed to meet the current electrical regulations concerning installation of meters.
EMC Installation Requirements
Whilst this unit complies with all relevant EU EMC (electro-magnetic compatibility)
regulations, any additional precautions necessary to provide proper operation of this and
adjacent equipment will be installation dependent and so the following can only be
general guidance:
Avoid routing wiring to this unit alongside cables and products that are, or could be, a
source of interference.
The supply to the unit should not be subject to excessive interference. In some cases, a
supply line filter may be required.
To protect the product against incorrect operation or permanent damage, surge
transients must be controlled. It is good EMC practice to suppress transients and surges
at the source. The unit has been designed to automatically recover from typical
transients; however in extreme circumstances it may be necessary to temporarily
disconnect the supply for a period of greater than 10 seconds to restore correct
operation.
Screened communication leads are recommended and may be required. These and other
connecting leads may require the fitting of RF suppression components, such as ferrite
absorbers, line filters etc., if RF fields cause problems.
It is good practice to install sensitive electronic instruments that are performing critical
functions in EMC enclosures that protect against electrical interference causing a
disturbance in function.
Password Entry
Wiring Information
Power Supply
The Auxiliary connection must be connected to power up the meter.
Wiring
Electrical and communication connections are made directly to the front of the meter.
Electrical Connections
2.5mm flexible stranded cable is recommended for all main electrical connections. For the
low voltage communication connections we recommend a twisted shielded cable Belden
9841 2 wire or 9842 4 wire or equivalent.
Phasing and polarity of the AC current and voltage inputs and their relationship is critical to
the correct operation.
Programming the meter
When you receive the meter
there will be at least one value
that you must programme into
the meter. This is the current
transformer ratio.
If the meter has been purchased with the intention of using the RS 485
Modbus output then you will have to program the Modbus parameters you
require. See reverse Communication. (RS 485 Modbus)
Pulse Definition
The pulse outputs can be set to generate pulses to
represent kWh/kVarh
Pulse constant: 0.001/0.01/0.1/1/10/100/1000 kWh or
kVarh per Pulse
Pulse width: 200/100/60 Ms.
The pulse output is passive type, complies with
IEC62053-31 Class A.
ATTENTION: Pulse output must be wired as shown in
the wiring diagram below. Scrupulously respect
polarties and the connection mode. Opto-coupler with
potential-free SPST-No Contact.
Contact range: 5~27VDC Max. current Input: 27mADC
A-35M
METER
3 PHASE 4 WIRE
Uimp
R
OUTPUT
P+ Com
Pulse Rate (Energy Value per Pulse)
Pulse rate options: 0.001 , 0.01 , 0.1 , 1, 10, 100, 1000 kWh /
kVarh per Pulse. Default : 0.01 kWh (100imp/kWh)
Use and to select Pulse Rate option.
Long press the setting will flash.
Use and to choose Options.
Long press for confirmation.
P
MD
PF Hz
P
MD
PF Hz
E
E
To Enter programing mode.
Press for 3 seconds
Display will show pass
0000
The first digit will flash.
Press once to increment the number to 1
Press and hold down to enter program mode.
Press to scroll down to programme various
parameters
E
MD
PF Hz
E
P
Pulse Output
This option allows you to configure the pulse output. The
output can be set to provide a pulse for a defined amount
of energy active or reactive. Use this section to set up the
pulse output—Units: kWh, kVArh
From the set-up menu, use and buttons to select
the Pulse output option.
Press to enter the selection routine. The unit symbol will
flash.
Use and buttons to choose kWh or kVArh.
On completion of the entry procedure, press to confirm
the setting and press to return to the main set up menu.
MD
PF Hz P
MD
PF Hz P
E
E
V/A
IMPORTANT
Current transformer
P1 must face mains
LOAD
MAINS
S2 S1
P2
Enter password (see password entry on the front page)
Press to step to c.t. rate
Press and hold down to enter program mode 1st
digit will flash
Press to increment number on first digit
Press to move cursor to the right
Repeat 4 and 5 until all four numbers have been entered
Press and hold for 2 seconds
Wait a few seconds until display shows confirmed
Press to return back to home page
This meter is now locked and cannot be altered again
C.T. Rate (Setting the Current Transformer Ratio)
Example of meter set at 200/5 amp
Example of how the display should look for a meter
programmed to 200/5 amp.
See table below for more settings.
C.T.2 (Current Transformer)
Set C.T.2 secondary current input.
Options: 5A or 1A
Default CT2: 5A
Long press to enter the CT2 routine.
Press for 3s, the CT2 setting will flash.
Use and to choose CT2 with 5A or 1A.
MD
PF Hz P
E
E
C.T Primary
100/5
150/5
200/5
250/5
300/5
400/5
500/5
600/5
Number to program
into the meter
20
30
40
50
60
80
100
120
C.T Primary
800/5
1000/5
1200/5
1500/5
1600/5
2000/5
2500/5
3000/5
Number to program
into the meter
160
200
240
300
320
400
500
600
Communication (RS 485 Modbus)
Baud rate
Baud rate options: 2400 4800 9600 19200 38400 (bps).
Default: 9600bps
From the Set-up menu, Use and to select the Baud
rate options.
Long press to enter the selection routine.
The Baud Rate setting will flash. Use and to choose
Baud Rate.
And long press for confirmation
MD
PF Hz P
MD
PF Hz P
E
E
Parity
Parity Options: NONE, EVEN, ODD.
Default Parity : EVEN
Note that if parity is set to ODD or EVEN, Stop Bits will be set
to 1 and cannot be changed.
From the Set-up menu, Use and to select the
Parity options.
Long Press to enter the selection routine.
The Parity setting will flash. Use and to choose
Parity.
Example shows:
Set Parity: EVEN
And long press for confirmation.
Press to return the main set up menu.
MD
PF Hz P
P
MD
PF Hz
E
E
Ph S
ESC
The Horizon Energy Monitoring System With the A-35M
VOLTAGE: 3X230/400V
CURRENT: 0.25~5(6)A
FREQUENCY: 50Hz
COMMS: RS485 Modbus RTU
BAUDRATE: 2400~38400BPS
INSTALLATION: CAT III
IC 1095
www.autometers.co.uk
Product development is continuous and Autometers Systems Limited reserves the
right to make alterations and manufacture without notice. Products as delivered may
therefor differ from the descriptions and illustrations in this publication
Autometers Systems Ltd.
4B Albany Road, Chorlton-cum-Hardy
Manchester M21 0AW
Email: [email protected]
Phone: 00(44) 0161 861 9056
Fax: 0161 881 3745
www.autometers.co.uk
The meter is a 72mm x 94.5mm
panel mounted meter with a
depth of 65mm The cut out hole
for the panel meter is 72mm x
94.5mm.
Dimensions
IMPORTANT NOTICE
RS Address
The RS485 port can be used for communications using Modbus RTU protocol.
Parameters such as Address, Baud rate, Parity, Stop bit can be selected.
From the set-up menu, use and buttons to
select the address ID.
Long press to enter the selection routine. The
current setting will be flashing.
Use and buttons to choose Modbus address
(001 to 247).
Press to move cursor to the right.
On completion of the entry procedure, long press
to confirm the setting and press to return the main
set-up menu.
MD
PF Hz P
E
E
MD
PF Hz
MD
PF Hz
P
P
E
E
E
E
V/A
V/A
Communications shield continuous
Communications Shield
Belden 9841 or Equal Cable Screened
Twisted pair with full Coax shielding
for RS 485 Modbus connection.
Red..…TX+ , Black…TX- , Green…Shield
to the next meter
RS 485 Modbus
Communication to enable
full data retrieval of kWh
for Graphic analysis and
Billing
S0 Current inputs
9 10 11 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8
Voltage inputs L N L N
12
RS485 S0 Current inputs
9 10 11 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8
Voltage inputs L N L N
12
RS485
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Do not enter the password and enter programming mode until you have read
the instructions of this leaflet and the full instruction leaflet enclosed. You
must know your complete programming requirement before entering
programming mode.
This meter will lock when you leave programming mode and cannot be
altered again.
This rule does not apply for setting the Modbus.
“MID approved appendix “B” and “D”

Other Autometers Systems Measuring Instrument manuals

Autometers Systems A-400 Series User manual

Autometers Systems

Autometers Systems A-400 Series User manual

Autometers Systems HORIZON HT-1095 User manual

Autometers Systems

Autometers Systems HORIZON HT-1095 User manual

Autometers Systems ADP3-80C User manual

Autometers Systems

Autometers Systems ADP3-80C User manual

Autometers Systems HORIZON HT-1095 User manual

Autometers Systems

Autometers Systems HORIZON HT-1095 User manual

Autometers Systems HORIZON HT-35 User manual

Autometers Systems

Autometers Systems HORIZON HT-35 User manual

Autometers Systems IC 970 Installation instructions

Autometers Systems

Autometers Systems IC 970 Installation instructions

Autometers Systems HORIZON HT-35 User manual

Autometers Systems

Autometers Systems HORIZON HT-35 User manual

Autometers Systems IC 995 User manual

Autometers Systems

Autometers Systems IC 995 User manual

Autometers Systems ic9 User manual

Autometers Systems

Autometers Systems ic9 User manual

Autometers Systems Q-180 User manual

Autometers Systems

Autometers Systems Q-180 User manual

Autometers Systems HORIZON HT-400 User manual

Autometers Systems

Autometers Systems HORIZON HT-400 User manual

Autometers Systems A-45 Series User manual

Autometers Systems

Autometers Systems A-45 Series User manual

Popular Measuring Instrument manuals by other brands

smartheart 19-006 instruction manual

smartheart

smartheart 19-006 instruction manual

janitza UMG 604-PRO installation instructions

janitza

janitza UMG 604-PRO installation instructions

Vogtlin SmartTrak 100 Series manual

Vogtlin

Vogtlin SmartTrak 100 Series manual

HEMCO AFA 500 MK 3 Installation, operation & maintenance manual

HEMCO

HEMCO AFA 500 MK 3 Installation, operation & maintenance manual

Fluke 381 Calibration manual

Fluke

Fluke 381 Calibration manual

Tokyo Keiso UL400 instruction manual

Tokyo Keiso

Tokyo Keiso UL400 instruction manual

Extreme Networks A3 MK II instruction manual

Extreme Networks

Extreme Networks A3 MK II instruction manual

Greenlee THM-250 instruction manual

Greenlee

Greenlee THM-250 instruction manual

Anton Paar Lovis 2000 M/ME Standard operating procedure

Anton Paar

Anton Paar Lovis 2000 M/ME Standard operating procedure

Telestream PRISM MPI user manual

Telestream

Telestream PRISM MPI user manual

Kane KANE458s Quick reference guide

Kane

Kane KANE458s Quick reference guide

Akron STYLE 9015 Instruction manual and parts list

Akron

Akron STYLE 9015 Instruction manual and parts list

Tektronix AA 501A instruction manual

Tektronix

Tektronix AA 501A instruction manual

Hanna Instruments AquaDip instruction manual

Hanna Instruments

Hanna Instruments AquaDip instruction manual

DayTronic 3000PLUS instruction manual

DayTronic

DayTronic 3000PLUS instruction manual

Signet 4150 operating instructions

Signet

Signet 4150 operating instructions

biosystems A25 Service manual

biosystems

biosystems A25 Service manual

Battenfeld 22280 instructions

Battenfeld

Battenfeld 22280 instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.