WARNING
Before doing the pilot turn-down test, always make sure that all manual fuel valves are
closed.
If the pilot turn-down test must be repeated, stop the combustion equipment completely
each time and discharge all of the unburned gas and oil from the fuel chamber and flue.
Failure to discharge unburned gas may result in an explosion hazard.
After completing the pilot turn-down test, turn off the power switch to turn off the power
supply. Make sure to return all test jumpers and limit or controller settings to their original
values. Resuming normal operation without returning the settings to their original values,
etc., may damage the equipment or cause a gas leak or explosion.
Close the fuel valve before using the flame simulator for a check while this device is attached.
If you use the flame simulator during normal operation, since a flame will seem to be present,
fuel will continue to be supplied even if the pilot burner or main burner is off, possibly
causing an explosion.
CAUTION
To ensure proper operation of this device, follow the directions given in this user’s manual
and in the manuals for the combustion equipment and for any other devices that are used.
When planning a combustion safety control system, please discuss the details with our sales
representatives.
Installation, wiring, maintenance, inspection, and adjustment must be carried out by a
professional with technical training in combustion equipment and flame safeguard system.
Use this product correctly within the range of the rated specifications stated in the user’s
manual. Not doing so may cause device failure or malfunction.
Do not install where exposed to any of the following:
• Certain chemicals or corrosive gases (ammonia, sulfur, chlorine, ethylene compounds,
acid, etc.)
• Splashing water or excessive humidity.
• High temperatures
• Prolonged vibration
All wiring and installation must comply with applicable local electrical codes, ordinances and
regulations.
Provide appropriate maintenance and inspection for the product, following the methods,
procedures, replacement cycle, etc., specified by this user’s manual.
When discarding of this device, dispose of it as industrial waste, following local regulations.
If timers and auxiliary relays are needed for additional functions, select ones with being
listed or component recognized by authorities, and be sure to design the circuit correctly.
Use this device within the operating ranges given in the specifications for temperature,
humidity, voltage, vibration, shock, mounting position, atmosphere, etc.
Make sure that the flame detector does not detect the ignition spark. If the ignition spark is
detected, change the position of the flame detector or ignition electrode.