Basler AEC 42-7 User manual

Publication: Rev First Printing 01/93 Copyright
9 2709 00 990 G Revised 09/01 1993-2001
Basler Electric
Phone 618 654-2341
Route 143 Box 269
Highland IL 62249 USA
Power Systems Group
Fax 618 654-2351
http://www.basler.com
INSTRUCTIONS
FOR
VOLTAGE REGULATOR
AEC 42-7
9 2709 00 100
GENERAL INFORMATION
DESCRIPTION
The AEC 42-7 voltage regulator is designed for
use on 50/60 Hz brushless generators. The
regulator includes frequency compensation,
overexcitation shutdown, a solid-state buildup
circuit, and EMI filtering.
ELECTRICAL SPECIFICATIONS
DC Output Power
Maximum continuous: 7 Adc at 42 Vdc
10 second Forcing: 15 Adc at 90 Vdc (at
240 Vac supply
voltage)
Exciter Field DC Resistance
Minimum: 6 ohms
Maximum: 105 ohms
AC Power Input
Operating Range: 220 to 260 Vac
Phase: 1-Phase
Frequency: 50/60 Hz
Burden: <900 VA
Sensing Input: 200-252 Vac ±10%
2-phase, 50/60 Hz at
<1 VA Burden
Voltage Adjust Range:180 to 277 Vac
Regulation Accuracy: <1% No-load to Full
load, Average Sensing
Paralleling: Input for 5 Vac from
External CT / Burden
Resistor to allow 10%
Droop
Response Time: Less than 1.5 cycles
for ±5% change in
sensing voltage. Link
(T C) and Adjustable
Stability to optimize re-
sponse
EMI Suppression: Internal EMI filter
Frequency Compensation Rate:
Twice volts per Hertz
(See Figure 1 for
curve)
Overexcitation Shutdown:
Time Delayed:Inverse
Trip Range: From no trip @ 50 Vdc
to instantaneous at
100. (See Figure 2.)
Disable link terminals
(N D) provided for par-
allel operation.
Voltage Buildup Internal provision for
automatic buildup
from 6 Vac, “SoftStart”
Power Dissipation 20 watts (typical)
PHYSICAL SPECIFICATIONS
Temperature:
Operating: -20°C to 60°C
(-4°F to 140°F)
Storage: -40°C to 85°C
(-40°F to 185°F)
Vibration: Withstands 1.3 G's at
2 to 27 Hz.; 0.036"
double amplitude at
27 to 52 Hz.; and 5
G's at 52 to 1000 Hz
Shock Withstands up to 20
G's in each of three
mutually perpendicu-
lar axes
Weight 0.68 kg. (1.5 lbs.)
FREQUENCY COMPENSATION
The frequency compensation characteristic of
Figure1isused toimprovesystemloadpickup
performance by restraining voltage recovery
until frequency has also started to recover.
The regulator is shipped from the factory set at
a 47 Hz”'corner frequency” for 50 Hz systems.
For 60 Hz systems, a 57 Hz corner frequency
is achieved by removing the “50-50" external
link.
OVEREXCITATION TIME DELAY
If exciter field voltage exceeds 52 ± 2 Vdc, the
regulator automatically removes the field
current, after a time delay. The time delay is
inversely proportional to the magnitude of the
detected field over voltage condition up to 95
±5 Vdc point. Beyond 95 ±5 Vdc, the field
voltage is removed at a much faster rate. This
shutdown function may be disabled for parallel
operation by linking terminals N and D
together.
INSTALLATION
MOUNTING
The regulator may be mounted on the gen-
erator in any convenient position. Refer to
outline drawing Figure 3.
Figure 4provides the
drilling template.
EXCITER FIELD POWER CIRCUIT
Connectregulator+wiretothebrushlessexciter
field F+ terminal, and the - wire to the field F-
terminal. Refer to Figure 5.
If the exciter field resistance is less than 6
ohms, and if the full-load field current does not
exceed the maximum continuous current rating
of the regulator (7 Adc), a resistor of sufficient
wattage must be added in series with the field to
bring the total resistance to 6 ohms.
POWER INPUT
Connect wiring as shown in Figure 5. Power for
the regulator is derived from the generator
auxiliary winding, connected to wires 3 and 4.
Theoperablepowerinput range is220-260 Vac.
SENSING INPUTS
For sensing, wires U and V areconnected to the
generator phase U and phase V respectively.
Wires X and Y are connected to the opposite
ends of the U and V phase coils, or commoned
together at the neutral (star) point.
QUADRATURE DROOP INPUT
When paralleling is required, a current
transformer (CT) and variable burden resistor
(rheostat) should be connected to terminals A
and B. The ratio of the CT and the maximum
value of the burden must be chosen so that at
maximum current the voltage applied to
terminals A and B does not exceed 5 Vac rms.
A suitable value of burden would be a rheostat
adjustable from 0 - 5 ohms (10 Watts) for a CT
with a 1 Aac secondary current at full load.
These terminals may either be linked or left
open when paralleling is not required.
FUSES
It is recommended that a fuse or fuses with high
interruption capability be installed per the inter-
connection diagram. A suitable fuse type would
be LittelFuse (type 3AG, rated 250 Vac, 6.3 A,
“Slo-Blo.” Dimensions are 6.3 mm x 32 mm (1
¼" x ¼").
CAUTION
The DC resistance of the exciter field must
be equal to or greaterthan 6 ohms and less
than 100 ohms.
NOTE
Fuse(s) MUST be installed per the
interconnection diagram to avoid
interrupting field current directly.
NOTE
The ground terminal must be bonded
either to a metal ground by the mounting
screw or by means of a cable to the most
suitable earthing point available close to
the regulator.

VOLTAGE ADJUST RHEOSTAT (V)
An internal screwdriver preset (V) provides
coarse adjustment of generator output voltage.
A clockwise adjustment of V increases voltage.
Thevoltageregulatorisshippedfromthefactory
with a link across terminals P and Q. If a re-
mote voltage adjust rheostat is used, the link
should be removed and the rheostat connected
to P and Q. A 1 kilo-ohm, 0.5 W potentiometer
will provide a 'fine' voltage range adjustment of
approximately ±10% over most of the coarse
range of adjustment. See Figure 5,
Intercon-
nection Diagram
.
V/HZ "CORNER FREQUENCY" SELECTION
For50 Hzsystems,theregulatoris presetat the
factory for a47 Hz "corner frequency" witha link
fitted across terminals “50". If operation at 60
Hz is required, this link should be removed; the
"corner frequency" is now set to 57 Hz. Do not
operate the system at 60 Hz with the 50 Hz link
still in place.
OVEREXCITATION SHUTDOWN
Overexcitation shutdown is provided to remove
output excitation should the regulator output
voltage exceeds 52 ± 2 Vdc for a sufficient time.
Theinverse-time-delay curve isshownin Figure
2. For voltages above 95 ±5 Vdc, there is a
second and much shorter inverse time curve.
Afteroutputpowerisremoved,theregulatorcan
be reset by decreasing the input voltage to less
than 6 Vac for a minimum of 2 seconds. This
may be accomplished by stopping the prime
mover or interrupting the regulator input by
means of a reset switch.
In cases where the generator is operating in a
parallel mode, it is sometimes considered
undesirable to allow the regulator to shut down,
whichmay cause the generator to be ”motored.”
Terminals N and D may be linked together to
prevent overexcitation shutdown. Note, how-
ever, that continuous running at output levels
greater than the continuous rating may result in
eventual regulator failure, and that other means
should be employed to protect the system.
OPERATION
GENERAL
The following system operation procedures
provide instructions for adjusting the AEC 42-7
voltage regulator. Symptoms resulting from a
faulty regulator and certain generator system
problems are included, together with suggested
remedies.
Complete the followingsteps before proceeding
with system startup.
PRELIMINARY SETUP
a. Verify that the voltage regulator
specifications conform with the generator
system requirements.
b. Ensure that the regulator links are fitted
correctly where required, as follows.
(1) If the remote voltage adjust rheostat is
not required, ensure terminals P and
Q are linked together.
(2) If a 57 Hz corner frequency for 60 Hz
systems is desired, ensure the”'50 -
50" link is removed. If a 47 Hz corner
frequency for 50 Hz systems is
desired, ensure the “50 - 50" link is
connected.
(3) If the system is to be run in parallel,
consider whether shutdown of the
generator's excitation is acceptable. If
not, ensure that the link between
terminals N and D is in place.
c. Ensure that the voltage regulator is cor-
rectly connected to the generator system:
F+ to field positive, F- to field negative, and
terminals 3 and 4 to the auxiliary winding
supply. It is vital that the sensing con-
nections are correctly made to all 4 wires
U, V, X, and Y. Ensure that the metal ring
tag at one mounting hole is bonded to
ground via either a metal screw or short
length of cable.
d. Install the fuses as directed in the previous
section.
e. Set the regulator and external voltage
adjust, if used, as follows:
Regulator Volts Adjust 'V' Fully CCW
Remote Volts Adjust Centered
Stability Adjust 'S' Centered
SYSTEM STARTUP
a. Perform the preliminary setup procedure
checking wiring carefully.
b. Start prime mover and bring up to rated
speed.
RESULT: The voltage should build up to less
than nominal value.
c. Slowly adjust the regulator voltage adjust V
until the generator output voltage reaches
the nominal value. Should a low frequency
oscillation or hunting be present on the
generator output voltage, adjust stability
control S to cause this to be damped out.
In general, clockwise increases the
stability. But in some cases, too far CW
may start to reduce stability again, and will
invariably slow the response of the
generator to load changes. An optimum
setting method is to adjust S slowly CCW
until the generator voltage just starts to
become unstable. Then turn it up to ¼ turn
CW from that position.
d. If used, adjust the external voltage adjust
rheostat to fine trim the voltage to the exact
value desired.
RESULT: Voltage should now have built up
and be stable at the desired value. If voltage
does not build up to rated value, check that
there is no short circuit or excessive load
present on the generator lines. If a minimum
residual of 6 Vac is not present, perform “Field
Flashing” as ex-plained later.
e. Check regulator under normal operating
and loading conditions.
RESULT: Voltage regulation should be better
than ±1.0% no-load to full-load. If regulation is
not within this range, check the following:
(1) Voltage reduction under loads of cosq >
0.0 may be due to speed reduction due
to loading of the prime mover. This may
be causing the frequency compensation
(V/Hz) circuit to reduce voltage at a
speed which is less than the "corner
frequency".
(2) Replace voltage regulator.
FIELD FLASHING
When the regulator is operated with the
generator for the first time, the polarity of
residual magnetism may be reversed or too
small to achieve the necessary buildup voltage
for the regulator. If reversing the field con-
nections does not induce buildup, and the
residual voltage is less than the specified value
of 6 Vac, shut down the prime mover and pro-
ceed with the following steps:
a. With the prime-mover at rest and the
regulator field output wires disconnected,
apply a DC source (NOT ground-ed) of not
more than 24 Vdc with Positive to F+ and
Negative to F-, in series with a
current-limiting resistor of 3-5 ohms. (The
set battery is a suitable source.)
b. Allow approximately 3 seconds before
removing the DC source.
c. With the voltage regulator disconnected
(wires 3 and 4), start the prime mover and
measure the “residual” voltage available at
the auxiliary winding. If this voltage is
greater than 6 Vac, reconnect voltage
regulator, and voltage buildup should be
successful.If less than6 Vacis measured,
repeat field flashing procedure.
d. If repeating steps a and b does not result
in generator voltage buildup, and residual
is greater than 6 Vac, replace voltage
regulator.
MAINTENANCE
PREVENTIVE MAINTENANCE
A periodic inspection of the unit should be made
to ensure it is kept clean and free from
accumulations of dust and moisture. It is vital to
ensurethat allthewireandterminalconnections
are kept sound, secure and free of corrosion.
OPERATIONAL TEST
a. Connect the test setup as shown in Figure
6. Do NOT apply power. Ensure the light
bulbs are rated120 volts andless than 100
watts. Alternatively a single 240 V bulb
may be used.
b. Adjust theinternal (V) andexternal voltage
adjust potentiometers fully CCW.
c. Apply 240 Vac, 50/60 Hz power to the
regulator.
d. Slowly turn the internal voltage adjust V in
the CW direction.
WARNING!
If a glass fuse is used, it
should be enclosed for safety.
CAUTION
Meggers and high-potential test
equipment must not be used.
Incorrect use of such equipment could
NOTE
All AC voltage readings are to be taken
with an 'average' reading voltmeter rated
speed.

Figure 1. Frequency Compensation Curves Figure 2. Typical Inverse Time Delay Characteristic
Curve
V S
%
AEC 42-7
Q
P
B
A
50
50
-
+
4
3
V
Y
X
U
20 AWG LEAD WIRE
125mm (4.912")
(4.528")
140mm
115mm
(5.512")
100mm (3.928")
GROUND CONNECTION
ATTHIS MOUNTING HOLE
4mm (0.157")
17mm (0.667")
77mm (3.02")
33mm (1.29")
Figure 3. AEC 42-7 Outlined Diagram
RESULT:
(1) Before fully CW is reached, the light
bulbshould reachfullbrilliancetosignify
the regulator is controlling correctly.
(2) At this regulating point, a small
change in either of the adjustments
should result in the light bulb being
turned full on or off.

Figure 6. Test Setup Diagram
Figure 5
.
Interconnection Diagram, 480 Vac Generator
Other Basler Controllers manuals

Basler
Basler VR63-4A/UL User manual

Basler
Basler KR4FFX User manual

Basler
Basler DECS-250 User manual

Basler
Basler SSR 32-12 User manual

Basler
Basler SR4A User manual

Basler
Basler DECS-200 User manual

Basler
Basler DGC-2020ES Quick guide

Basler
Basler DGC-2020ES User manual

Basler
Basler DGC-2020HD Service manual

Basler
Basler AVC63-4 User manual

Basler
Basler AVC63-12A1 User manual

Basler
Basler AVC63-2 User manual

Basler
Basler AVC63-12 User manual

Basler
Basler BE2000E User manual

Basler
Basler AVC63-4A User manual

Basler
Basler DGC-2020ES User manual

Basler
Basler AVC634A-12 User manual

Basler
Basler APR 63-5 User manual

Basler
Basler AVC63-2.5 User manual

Basler
Basler SR6A User manual