
Power for the exciter field and regulator
circuitry is derived from the generator output
or auxiliary winding. The operable power
input range is 90 to 132 Vac.
For sensing, single-phase voltage from the
generator is connected between E1 and 4.
Note that terminal 4 is common to both power
and sensing.
FREQUENCY COMPENSATION
The frequency compensation characteristic is
to improve system load pickup performance
by restraining voltage recovery until frequency
has also started to recover.
The regulator is preset at the factory for 45 Hz
“corner frequency” for 50 Hz system. For 60
Hz system, a 55 Hz “corner frequency” is
achieved by disconnecting the external Hz
leads. Be sure to insulate the disconnection.
Frequency Compensation Curves
OVEREXCITATION SHUTDOWN
If the exciter field voltage exceeds 100 ±5
Vdc, the regulator automatically removes the
field current after a time delay. The time
delay is inversely proportional to the mag-
nitude of the detected overvoltage condition
up to the 135 ±5 Vdc point. Beyond 135 ±5
Vdc, the field voltage is removed within 0.2
seconds.
After shutdown, reset the regulator by
decreasing voltage below 6 Vac either by
stopping the prime mover or interrupting the
regulator input with a reset switch for 2
seconds or more.
Typical Time Delay Characteristic Curves
VOLTAGE ADJUST RHEOSTAT (VAR)
Screwdriver adjustable potentiometer adjusts
generator output voltage. Adjustment CW
increases voltage.
When using remote voltage adjust rheostat
(VAR), the VAR wire on the regulator should
be cut and the rheostat connected to both
ends. A 1 kohm and 1/2 watt resistance is
adequate for most applications. See
Interconnection Diagrams.
OPERATION
The following system operation procedures
provide instructions for adjusting the VR63-
4A/UL Voltage Regulator.
CAUTION
Meggers and high potential test
equipment must not be used. Incorrect
use of such equipment could damage the
semiconductors contained in the
regulator.
PRELIMINARY SET-UP
To prevent damage to the regulator, complete
the following steps before proceeding with
system start-up.
a. Verify that the voltage regulator
specification conforms with the generator
system requirements.
b. Ensure that the regulator is correctly
connected to the generator. See
Interconnection Diagram.
c. Install fuses per FUSES paragraph.
d. Set the regulator VAR fully CCW and the
remote VAR (if used) to centered.
SYSTEM START-UP
a. Start the prime mover and bring up to
rated speed. Voltage should buildup. If a
minimum residual of 6 Vac is not
present, perform field flashing.
b. Slowly adjust VAR CW until the
generator output voltage reaches
nominal value. If used, adjust remote
voltage adjust to set generator output to
exact value desired.
ACCESSORY EQUIPMENT
Voltage Adjust Rheostat for remote mounting-
Order Basler P/N 17724 for locking, slotted
shaft rheostat.
OPERATIONAL TEST
a. Connect the test setup as shown in
Operational Test. Do not apply power.
Ensure that light bulbs are rated for 120
V and less than 100 W.
b. Adjust regulator VAR and/or remote VAR
to maximum CCW.
c. Apply 240V, 60 Hz power to regulator.
d. Slowly adjust the regulator VAR control
CW.
RESULT:
1) Before minimum brilliance is reached, the
light bulb should attain maximum brilliance
to signify the regulating point.
2) At the regulating point, a small change in
the VAR should turn the light bulb on or
off.
FIELD FLASHING
When the regulator is operated with the
generator for the first time, the polarity of
residual magnetism may not correct or the
magnitude not enough. If the generator does
not build-up after startup, shut down the prime
mover and proceed with the following steps:
a. With the prime mover at rest, apply a dc
source (not grounded) of not more than
12V, to terminals F+(positive) and F-
(negative) in series with a limiting resistor
of 3-5 ohms.
b. Allow approximately 3 seconds before
removing the dc source.
c. Start prime mover and measure voltage
at regulator leads 3and 4. If voltage is
greater than 6 volts, voltage build-up
should be successful. Repeat field
flashing procedure if less than 6 V
residual is measured.
d. If repeating steps 1 and 2 does not result
in generator voltage build-up, replace the
voltage regulator.
CONFIDENTIAL INFORMATION
OF BASLER ELECTRIC COMPANY, HIGHLAND, IL.
IT IS LOANED FOR CONFIDENTIAL USE, SUBJECT
TO RETURN ON REQUEST, AND WITH THE
MUTUAL UNDERSTANDING THAT IT WILL NOT BE
USED IN ANY MANNER DETRIMENTAL TO THE
INTEREST OF BASLER ELECTRIC COMPANY.
Publication:
9 1668 00 995
© 1998, Basler Electric Co., Highland, IL 62249
First Printing November 1986
Revision: D December 1998