manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Basler
  6. •
  7. Controllers
  8. •
  9. Basler VR63-4B User manual

Basler VR63-4B User manual

Other Basler Controllers manuals

Basler DECS-250 User manual

Basler

Basler DECS-250 User manual

Basler DGC-2020ES Quick guide

Basler

Basler DGC-2020ES Quick guide

Basler AVC63-4A User manual

Basler

Basler AVC63-4A User manual

Basler APR 63-5 User manual

Basler

Basler APR 63-5 User manual

Basler AVC63-4 User manual

Basler

Basler AVC63-4 User manual

Basler AVC63-2.5 User manual

Basler

Basler AVC63-2.5 User manual

Basler SSR 32-12 User manual

Basler

Basler SSR 32-12 User manual

Basler DGC-2020 User manual

Basler

Basler DGC-2020 User manual

Basler DGC-2020ES User manual

Basler

Basler DGC-2020ES User manual

Basler DECS-200 User manual

Basler

Basler DECS-200 User manual

Basler DGC-2020ES User manual

Basler

Basler DGC-2020ES User manual

Basler DGC-500 User manual

Basler

Basler DGC-500 User manual

Basler DGC-2020HD Service manual

Basler

Basler DGC-2020HD Service manual

Basler VR63-4A/UL User manual

Basler

Basler VR63-4A/UL User manual

Basler KR4FFX User manual

Basler

Basler KR4FFX User manual

Basler AVC63-12A1 User manual

Basler

Basler AVC63-12A1 User manual

Basler SR4A User manual

Basler

Basler SR4A User manual

Basler BE2000E User manual

Basler

Basler BE2000E User manual

Basler AVC63-2 User manual

Basler

Basler AVC63-2 User manual

Basler AVC634A-12 User manual

Basler

Basler AVC634A-12 User manual

Basler SR6A User manual

Basler

Basler SR6A User manual

Basler SCP 250 User manual

Basler

Basler SCP 250 User manual

Basler AVC63-12 User manual

Basler

Basler AVC63-12 User manual

Basler AEC 42-7 User manual

Basler

Basler AEC 42-7 User manual

Popular Controllers manuals by other brands

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

Ksenia intro Installation and configuration manual

Ksenia

Ksenia intro Installation and configuration manual

Inovance CAN200 Series manual

Inovance

Inovance CAN200 Series manual

Gauzy LC6 FLEX Controller Installation and operation guide

Gauzy

Gauzy LC6 FLEX Controller Installation and operation guide

Viking SLP-1 Technical practice

Viking

Viking SLP-1 Technical practice

CKD KBX-30E-U Series instruction manual

CKD

CKD KBX-30E-U Series instruction manual

Sharp Energy Sun Flux User manual & installation guide

Sharp Energy

Sharp Energy Sun Flux User manual & installation guide

Yamaha RCX40 user manual

Yamaha

Yamaha RCX40 user manual

AB Quality PowerFlex 400 Frames D-H Service bulletin

AB Quality

AB Quality PowerFlex 400 Frames D-H Service bulletin

Yamaha MJC8 owner's manual

Yamaha

Yamaha MJC8 owner's manual

AL-KO ATC operating instructions

AL-KO

AL-KO ATC operating instructions

Savant SmartControl 2 Deployment guide

Savant

Savant SmartControl 2 Deployment guide

GameSir T3S user manual

GameSir

GameSir T3S user manual

Kostal inveor operating manual

Kostal

Kostal inveor operating manual

Emerson Yarway 20-55 Operating and safety instructions

Emerson

Emerson Yarway 20-55 Operating and safety instructions

CoCo ACM-LV24 Quick installation guide

CoCo

CoCo ACM-LV24 Quick installation guide

Brooks SLA5810/20 Installation and operation manual

Brooks

Brooks SLA5810/20 Installation and operation manual

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

WARNING
To prevent personal injury or equipment
damage, only qualified technicians or
operators should install, operate, or
service this device.
ELECTRICAL SPECIFICATIONS
Dc Output Power:
4 Adc at 63 Vdc (252W) maximum
continuous,
7 Adc at 100 Vdc (700W) forcing one minute
(at 240 Vac input).
Exciter Field Dc Resistance:
15 ohms minimum; 100 ohms maximum.
Ac Power Input:
Operating range: 190 Vac to 240 Vac, +10%,
Single phase, 50/60 Hz +5%, Burden 500 VA.
Voltage Adjust Range:
171-264 Vac.
Regulation Accuracy:
Better than ±1.0% no load to full load.
Response Time:
Less than 1.5 cycles for +10% change in
sensing voltage.
EMI Suppression:
Internal electromagnetic interference filter
(EMI filter).
Overexcitation Shutdown:
Output power is removed under the following
conditions: Exciter field voltage exceeds
100+5 Vdc for a time inversely proportional to
voltage magnitude, or instantaneously if the
exciter field voltage exceeds 135+5 Vdc.
Voltage Build-up:
Internal provisions for automatic voltage build-
up from generator residual voltages as low as
10 Vac.
Power Dissipation:
8 Watts maximum.
PHYSICAL SPECIFICATIONS
Operating Temperature:
-40°C (-40°F) to +60°C (+140°F).
Storage Temperature:
-65°C (-85°F) to +85°C (+185°F).
CSA Approved
FUSES
It is recommended that fuses with high
interruption capability be installed per the
interconnection diagram to protect wiring from
faults before the regulator. Refer to the
Interconnection Diagram.
NOTE
Fuse must be installed per the
interconnection diagrams to avoid inter-
rupting the field current.
MOUNTING
The regulator may be mounted in any
position. Refer to the drilling diagrams.
Drilling Diagram
EXCITER FIELD POWER CIRCUIT (wires F+
and F-).
Connect the regulator wire F+ to the brushless
exciter field terminal F+, and wire F- to
terminal F-.
CAUTION
The dc resistance of the exciter field
must be equal to or greater than 15 ohms
and less than 100 ohms.
POWER/SENSING INPUT CIRCUIT (wires 3
and 4)
Connect as shown by the Interconnection
Diagram.
UNDERFREQUENCY CHARACTERISTIC
POINT
For 50 Hz systems, connect the Hz leads.
For 60 Hz systems, disconnect the Hz leads.
See curves the following figure.
Frequency Compensation Curves
OVEREXCITATION SHUTDOWN
This circuit removes the output power if the
exciter field voltage exceeds 100 ±5 Vdc after
a time delay. If the voltage exceeds, 135 +5
Vdc, the output power is removed
instantaneously.
After shutdown, reset the regulator by
decreasing voltage below 6 Vac either by
stopping the prime mover or interrupting the
regulator input with a reset switch for 2
seconds or more.
VOLTAGE ADJUST
Screwdriver adjustable potentiometer adjusts
generator output voltage. Adjustment CW
increases voltage.
STABILITY ADJUST
Screwdriver adjustable (on non-label side)
potentiometer adjusts the stability and
response of the generator output voltage.
Adjustment CW increases the stability.
NOTE: Excessive CCW rotation of this
adjustment may result in oscillations (hunting)
of the generator output voltage.
OPERATION
The following system operation procedures
provide instructions for adjusting the VR63-4B
Voltage Regulator.
CAUTION
Meggers and high potential test
equipment must not be used. Incorrect
use of such equipment could damage the
semiconductors contained in the
regulator.
PRELIMINARY SET-UP
To prevent damage to the regulator, complete
the following steps before proceeding with
system start-up.
a. Verify that the voltage regulator
specification conforms with the generator
system requirements.
CONFIDENTIAL INFORMATION
OF BASLER ELECTRIC COMPANY, HIGHLAND, IL.
IT IS LOANED FOR CONFIDENTIAL USE, SUBJECT
TO RETURN ON REQUEST, AND WITH THE
MUTUAL UNDERSTANDING THAT IT WILL NOT BE
USED IN ANY MANNER DETRIMENTAL TO THE
INTEREST OF BASLER ELECTRIC COMPANY.
Publication:
9 1668 00 996
© 1998, Basler Electric Co., Highland, IL 62249
First Printing August 1988
Revision: C January 1998
ECA: 16515
INSTRUCTION MANUAL
FOR
VOLTAGE REGULATOR
Model: VR63-4B
CALL US TODAY
1-888-POWER-58
REQUEST A QUOTE
[email protected]
SHOP ONLINE
www.genpowerusa.com
CALL US TODAY
1-888-POWER-58
REQUEST A QUOTE
[email protected]
SHOP ONLINE
www.genpowerusa.com
b. Ensure that the regulator is correctly
connected to the generator. See
Interconnection Diagram.
c. Install fuses per FUSES paragraph.
d. Set the regulator voltage control fully
CCW and the Stability Potentiometer to
mid-range.
SYSTEM START-UP
a. Start the prime mover and bring up to
rated speed. Voltage should buildup. If a
minimum residual of 10V is not present,
perform field flashing.
b. Slowly adjust voltage control until voltage
reaches nominal value.
OPERATIONAL TEST
a. Connect the test setup as shown in
Operational Test. Do not apply power.
b. Adjust regulator voltage adjust to
maximum CCW.
c. Apply 240V, 60 Hz power to regulator.
RESULT: Light bulb flashes momentarily.
d. Slowly adjust the regulator voltage adjsut
CW.
RESULT:
1) Before the full CW position is reached, the
light bulb reaches full brilliance to signify the
regulating point.
2) At the regulating point, a small change in
the voltage adjust should turn the light bulb on
or off.
FIELD FLASHING
When the regulator is operated with the
generator for the first time, the polarity of
residual magnetism may not correct or the
magnitude not enough. If the generator does
not build-up after startup, shut down the prime
mover and proceed with the following steps:
a. With the prime mover at rest, apply a dc
source (not grounded) of not more than
12V, to terminals F+(positive) and F-
(negative) in series with a limiting resistor
of 3-5 ohms.
b. Allow approximately 3 seconds before
removing the dc source.
c. Start prime mover and measure voltage
at regulator leads 3and 4. If voltage is
greater than 10 volts, voltage build-up
should be successful. Repeat field
flashing procedure if less than 10 V
residual is measured.
d. If repeating steps 1 and 2 does not result
in generator voltage build-up, replace the
voltage regulator.
Interconnection Diagram, 208/240 V Nominal
Operational Test