BEKA BA358E User manual

Issue: 6
19th April 2016
BA358E
Intrinsically safe
4/20mA l p-p wered
panel m unting
Rate T taliser
Issue 6

1. Descripti n
2. Operati n
2.1 Controls
2.2 Displays
3. Intrinsic Safety Certificati n
3.1 ATEX gas certificate
3.2 Zones, gas groups & T rating
3.3 pecial conditions for safe use
3.4 4/20mA input
3.5 Reset terminals
3.6 Certification label information
4. System Design f r Hazard us Areas
4.1 Flow transmitter loops
4.2 Resetting the total display to zero
4.3 Remote indication
5. Installati n
5.1 Location
5.2 EMC
5.3 Installation procedure
5.4 cale card
6. C nfigurati n and Calibrati n
6.1 Calibration structure
6.2 Accessing configuration & calibration
functions.
6.3 ummary of configuration
functions.
6.4 Rate totaliser function
6.5 Display resolution
6.6 Display update time
6.7 Upper display
6.8 Lower display
6.9 Position of decimal points
6.10 Calibration of rate display using an
external current source.
6.11 Calibration of rate display using internal
reference.
6.12 Clear grand total
6.13 Timebase
6.14 Function of P push button
6.15 Total scale factor
6.16 Clip off
6.17 Local reset of total and grand total
displays.
6.18 ecurity code
6.19 Reset to factory defaults
6.20 Over-range
7. Lineariser
7.1 Calibration using external current
source.
7.1.1 Example, Adding break-points
to a new Rate Totaliser
7.2 Calibration using internal reference
7.2.1 Example, Adding break-points
to a new Rate Totaliser
7.3 Error messages
7.4 Under and over-range
7.5 Default configuration
8. Calibrati n Examples
8.1 Using an external current source
8.2 Using the internal reference
9. Maintenance
9.1 Fault finding during commissioning
9.2 Fault finding after commissioning
9.3 ervicing
9.4 Routine maintenance
9.5 Guarantee
9.6 Customer comments
10. Access ries
10.1 cale card
10.2 Tag information
10.3 Alarms
10.3.1 olid state output
10.3.2 Intrinsic safety
10.3.3 Configuration and adjustment
10.3.4 Alarm enable
10.3.5 Type of alarm
10.3.6 etpoint adjustment
10.3.7 Alarm function
10.3.8 Alarm output status
10.3.9 Hysteresis
10.3.10 Alarm delay
10.3.11 Alarm silence time
10.3.12 Flash display
10.3.13 Access setpoint
10.3.14 Adjusting alarm setpoints
from display mode.
10.4 Display backlight
10.4.1 Loop powered
10.4.2 eparately powered
Appendix 1
ATEX dust certification
Appendix 2
IECEx certification
Appendix 2
FM and cFM certification
22
The BA358E is CE marked to show compliance with the European Explosive Atmospheres Directive
94/9/EC and the European EMC Directive 2004/108/EC
CONTENTS

1. DESCRIPTION
The BA358E is a panel mounting intrinsically safe
4/20mA loop-powered Rate Totaliser primarily
intended for use with flowmeters. The instrument
simultaneously displays the rate of flow and the
total flow in engineering units on two separate
displays. The BA358E only introduces a 1.2V
drop, which allows it to be installed into almost any
4/20mA flow loop. No additional power supply or
battery is required.
The rate totaliser has been certified intrinsically
safe for use in gas and dust hazardous areas by
Notified Body Intertek Testing and Certification Ltd
and complies with the European ATEX Directive
94/9/EC. The EC-Type Examination certificate
specifies that under fault conditions the output
voltage, current and power at the 4/20mA input
terminals will not exceed those specified for simple
apparatus in Clause 5.7 of EN 60079-11, which
simplifies installation and documentation.
For international applications the BA358E has
IECEx, FM and cFM certification which are
described in Appendixes 2 and 3.
2. OPERATION
Fig 1 shows a simplified block diagram of a
BA358E. The 4/20mA input current flows through
resistor R1 and forward biased diode D1. The
voltage developed across D1, which is relatively
constant, is multiplied by a switch mode power
supply and used to power the instrument. The
voltage developed across R1, which is proportional
to the 4/20mA input current, provides the input
signal for the analogue to digital converter.
Each time a 4/20mA current is applied to the
instrument, initialisation is performed. After a short
delay the following display sequence occurs which
takes about twelve seconds:
All segments of the display are activated
Loading message displayed
Configuration message displayed
Model and firmware version displayed
The BA358E Rate Totaliser starts
functioning, using configuration information
stored in the instrument’s permanent
memory. Unless total and grand total
displays have been reset to zero, new flow
will be added to the existing totals.
If the 4/20mA current is disconnected during
operation the latest total and grand total are stored
in permanent memory.
Fig 1 implified block diagram of BA358E
2.1 C ntr ls
The BA358E is controlled and calibrated via four
front panel push buttons located below the display.
In the operating mode i.e. when the instrument is
displaying rate and total flow the push button
functions are:
Summary f Push Butt n Functi ns
PDisplays input current in mA or as a
percentage of span. Modified when
optional alarms are fitted.
▼ hows rate display calibration at 4mA
input.
▲ hows rate display calibration at
20mA input.
Ehows time since instrument was
powered or total display was reset.
E+▼ Grand total –
displays least significant 8 digits
E+▲ Grand total –
displays most significant 8 digits.
▼+▲ Resets total display
Configurable function
P+▼ hows firmware version
P+▲ Alarm setpoint access
Configurable function
P+E Access to configuration menu
3

Full Descripti n f Push Butt n Functi ns
PWhile this button is pushed the rate
display will show the input current in
mA, or as a percentage of the
instrument span depending upon how
the instrument has been configured.
When the button is released the normal
display in engineering units will return.
The function of this push button is
modified when optional alarms are fitted
to the instrument.
▼While this button is pushed the
instrument will show the calibrated rate
display with 4mA* input - usually zero
for flow applications. When the button
is released the flow rate will again be
displayed.
▲ While this button is pushed the
instrument will show the calibrated rate
display with 20mA* input. When the
button is released the flow rate will
again be displayed.
EWhile this button is pushed the Rate
Totaliser will display the time in hours,
minutes and seconds since the
instrument was powered or the total
display was reset. The elapsed time is
not saved when power is removed.
E+▼ While these buttons are pushed the
total display will show the least
significant eight digits of the grand total,
and the grand total annunciator will be
activated.
E+▲ While these two buttons are pushed the
total display will show the most
significant eight digits of the grand total
and the grand total annunciator will be
activated.
After the two buttons have been pushed
for ten seconds ‘CLr no’ with the ‘no’
flashing will be displayed. If no action
is required, pressing E will return the
instrument to the operating mode.
Operating the ▼ or ▲ button will toggle
the display to ‘CLr YE ’ with ‘YE ’
flashing, operating the E button will then
clear the grand total and ‘Gt CLrd’ will
be displayed to confirm the operation.
The instrument will then automatically
return to the operating mode.
electable function in the configuration
menu. ee section 6.17
N te: Totalisation will continue until
‘CLr no’ or ‘CLr YE5’ are displayed.
▼+▲ Resets the total display to zero
when these two push buttons are
operated simultaneously. electable
function in the configuration menu.
ee section 6.17
P + ▼ Rate Totaliser displays firmware
version.
P + ▲ Provides direct access to the alarm
setpoints when optional alarms are
fitted to the Rate Totaliser and the
‘AC5P’ access setpoints in display
mode function has been enabled.
ee section 10.2.13
P+E Provides access to the configuration
menu via optional security code.
N te: * If the Rate Totaliser has been
calibrated using the CAL function,
calibration points may not be 4 and
20mA.
2.2 Displays
The BA358E has two digital displays and
associated annunciators, plus a flow indicator as
shown on page 1.
Lower hows the flow rate on the five digit
display plus sign 12mm high display.
Upper hows the total flow on the eight digit
display (seven with negative sign) 18mm high
display which may be reset to zero by
operating the ▼ + ▲ instrument push
buttons or by an external contact
closure.
The rate and total displays may be interchanged,
see section 6.7
Flow This disc on the lower left hand side of
indicator the display rotates when the input
current
exceeds 4.000mA, indicating that flow
is being detected by the Rate Totaliser.
For bi-directional flow, the disc rotates
when flow exceeds ±0.05% of span.
Annunciat rs
Reset Activated when total display is reset to
zero by operating the ▼ + ▲ buttons
simultaneously or by connecting the
reset terminals together.
4

Hold Activated when flow rate falls below the
clip-off value and totalisation is
inhibited.
Grand Is a 16 digit (15 digit with negative sign)
Total number which is not zeroed when the
total display is zeroed. The Grand Total
is viewed from the operating mode as
two eight digit numbers, it may be reset
to zero from within the configuration
menu or from the operating mode.
3. INTRINSIC SAFETY CERTIFICATION
The BA358E rate totaliser has ATEX and IECEx
gas and dust certification. This section of the
instruction manual describes ATEX gas
certification. ATEX dust, IECEx and other
approvals are each described in separate
appendixes to this manual.
3.1 ATEX gas certificati n
Notified Body Intertek Testing and Certification Ltd
have issued the BA358E with an EC-Type
Examination Certificate number
IT 11ATEX27254X. This confirms compliance
with harmonised European standards and it has
been used to confirm compliance with the
European ATEX Directive for Group II, Category
1G equipment, Ex ia IIC T5 Ga Ta = -40 to
+70ºC. The Rate Totaliser bears the community
mark and subject to local codes of practice may be
installed in any of the European Economic Area
(EEA) member countries. ATEX certificates are
also acceptable for installations in witzerland.
This section of the instruction manual describes
ATEX installations in explosive gas atmospheres
conforming with EN60079-14 Electrical
Installations in Hazardous Areas. When designing
systems for installation outside the UK the local
Code of Practice should be consulted.
3.2 Z nes, gas gr ups and T rating
The BA358E Rate Totaliser has been certified
Ex ia IIC T5. When connected to a suitable
system it may be installed in:
Zone 0 explosive gas air mixture
continuously present.
Zone 1 explosive gas air mixture likely
to occur in normal operation.
Zone 2 explosive gas air mixture not
likely to occur, and if it does
will only exist for a short time.
Be used with gases in groups:
Group A propane
Group B ethylene
Group C hydrogen
Having a temperature classification of:
T1 450oC
T2 300oC
T3 200oC
T4 135oC
T5 100oC
At ambient temperatures between -40 and +70oC.
N te: The specified operating temperature of the
BA358E is –20 to +70ºC. At temperatures below
–20ºC the instrument will continue to totalise but
the display will not function.
This allows the Rate Totaliser to be installed in all
gas Zones and to be used with most common
industrial gases.
3.3 Special c nditi ns f r safe use
The ATEX certificate has an ‘X’ suffix indicating
that special conditions apply for safe use.
WARNING
T av id an electr static charge being
generated instrument encl sure sh uld
nly be cleaned with a damp cl th.
3.4 4/20mA input
The input safety parameters for the 4/20mA input,
terminals 1 and 3 are:
Ui = 30V dc
Ii = 200mA
Pi = 0.84W
The maximum equivalent capacitance and
inductance between the two 4/20mA input
terminals 1 and 3 is:
Ci = 13nF
Li = 16µH
The maximum permitted loop cable parameters
can be calculated by adding these figures to Ci and
Li of other instruments in the loop and subtracting
the totals from the maximum cable capacitance Co
and cable inductance Lo permitted for the Zener
barrier or galvanic isolator powering the loop.
Although the BA358E does not comply with the
requirements for simple apparatus, the EC-Type
Examination Certificate states that for intrinsic
safety considerations, under fault conditions the
output voltage, current and power at terminals 1 &
3 will not exceed those specified by clause 5.7 of
EN 60079-11 for simple apparatus. This simplifies
the application and intrinsic safety documentation
for a loop into which the BA358E is connected.
Apart from Ci, the affect of the Rate Totaliser may
be ignored when assessing loop safety.
5

3.5 Reset terminals
The BA358E total display may be reset to zero by
connecting the reset terminals R 1 and R 2
together. These two terminals have the following
input and output intrinsic safety parameters:
Ui = 30V dc
Ii = 200mA dc
Pi = 0.84W
Uo = 6V dc
Io = 2.5mA dc
Po = 3.75mW
The maximum equivalent capacitance and
inductance between them is:
Ci = 13nF
Li = 8H
The total display may be reset to zero from within
the hazardous area by any mechanically operated
switch connected directly to terminals R 1 and
R 2. Alternatively, the BA358E may be configured
so that the total display is reset to zero when the ▲
and ▼ push buttons are operated simultaneously
for two seconds.
To reset the total display from the safe area a
Zener barrier or intrinsically safe relay is required
to transfer the contact closure into the hazardous
area. Almost any intrinsically safe relay with
certification permitting the contacts to be
connected to equipment in the hazardous area
may be used. Alternatively, a positive polarity
Zener barrier with intrinsic safety parameters equal
to or less than the input parameters of the reset
terminals may be used as shown in Fig 3A. The
total resistance of the barrier, switch and
interconnecting wiring must be less than 1kΩ.
N te:
The negative reset terminal R 2 is internally
connected to the negative 4/20mA input
terminal 3.
3.6 Certificati n label inf rmati n
The certification label is fitted in a recess on the
top outer surface of the instrument enclosure. It
shows the ATEX certification information and
BEKA associates' name and location. Non
European certification information may also be
shown.
BA358E certification label
6

4. SYSTEM DESIGN FOR HAZARDOUS AREA
4.1 Fl w transmitter l ps
A BA358E Rate Totaliser may be connected in
series with almost any intrinsically safe 4/20mA
flow loop and calibrated to display the rate of flow
and total flow. There are three basic design
requirements:
1. The intrinsic safety output parameters of the
4/20mA loop, which are defined by the Zener
barrier or galvanic isolator powering the loop, must
be equal to or less than:
Uo = 30V dc
Io = 200mA
Po = 0.84W
2. The maximum permitted cable capacitance of the
loop must be reduced by 13nF. The maximum
permitted cable inductance is not reduced by the
inclusion of the BA358E.
3. The loop must be able to tolerate the additional
1.2V required to operate the Rate Totaliser.
When fitted with an optional backlight this
increases to 5.0V if the backlight is loop powered.
ee 10.3.1
Figs 2a and 2b illustrates typical applications in
which a Rate Totaliser is connected in series with a
2-wire flow transmitter powered by a Zener barrier
and alternatively by a galvanic isolator.
Fig 2a Loop powered by a Zener barrier
Fig 2b Loop powered by a galvanic isolator
4.2 Resetting the t tal display t zer
The BA358E total display may be reset to zero by
momentarily connecting the reset terminals R 1
and R 2 together with a resistance of less than
1kΩ. Within the hazardous area in which the
BA358E is located this may be achieved with a
manually activated industrial push button as shown
in Fig 3b.
The push button switch and the wiring connecting it
to the Rate Totaliser must comply with the
requirements for simple apparatus specified in
Clause 5.7 of EN60079-11. i.e. be able to
withstand a 500V rms insulation test for one
minute. The switch button should comply with the
electrostatic requirements specified by Clause 7 of
EN60079-0 and material composition defined in
Clause 8.
If it is required to reset the total display from the
safe area a Zener barrier, galvanic isolator or
intrinsically safe relay must be used to transfer the
contact closure into the hazardous area. Fig 3a
shows how a single channel positive polarity Zener
barrier may be used.
N te:
The negative reset terminal R 2 is internally
connected to the negative 4/20mA input
terminal 3.
4.3 Rem te indicati n
A BA358E may be driven via an intrinsically safe
interface from a 4/20mA safe area signal to provide
a remote indication of rate and total flow within a
hazardous area. The type of interface is not
critical, either a Zener barrier or a galvanic isolator
may be used, providing that Ui, Ii and Pi of the
BA358E 4/20mA input are not exceeded.
If one side of the 4/20mA current loop may be
earthed, a single channel Zener barrier provides
the lowest cost protection. If the 4/20mA signal is
not isolated, then two Zener barriers, a two
channel Zener barrier or a galvanic isolator must
be used.
When the hazard is a IIC gas and two single
channel Zener barriers or a two channel Zener
barrier are used, only one barrier or channel may
be a 28V 93mA device. A 10V 50 or diode
return barrier may be used for the second channel
to form a safe combination.
Again it is necessary to ensure that the voltage
capability of the 4/20mA signal is sufficient to drive
the BA358E Rate Totaliser plus the voltage drop
introduced by the intrinsically safe interface. Figs
3a, 3b and 3c show the alternative circuits which
may be used.
7

Fig 3a implest circuit with one side of
20mA current loop connected to
earth.
Also illustrates resetting from safe area.
Fig 3b Two Zener barrier channels are
required if the 4/20mA current loop
can't be earthed at the barrier busbar.
Also shows optional resetting from
hazardous area
Fig 3c Galvanic isolator can be used with any
4/20mA current loop.
8

5. INSTALLATION
5.1 L cati n
The BA358E Rate Toyslider has a robust glass
reinforced modified PPO enclosure with a
toughened glass window. The front of the Rate
Totaliser has IP66 protection and a gasket seals
the joint between the instrument enclosure and the
panel. The rear of the instrument has IP20
protection.
The Rate Totaliser will function and is certified
intrinsically safe at ambient temperatures between
–40ºC and +70ºC, but the display only functions at
ambient temperatures between –20ºC and +70ºC.
Fig 4 shows the overall BA358E Rate Totaliser
dimensions together with the recommended panel
cut-out dimensions. To achieve an IP66 seal
between the instrument enclosure and the
instrument panel the smaller tolerance aperture
should be used, and the Rate Totaliser should be
secured with four panel mounting clamps.
Although the Rate Totaliser front panel provides
IP66 protection it should be shielded from direct
sunlight and severe weather conditions.
Fig 4 BA358E dimensions
5.2 EMC
The BA358E Rate Totaliser complies with the
requirements of the European EMC Directive
2004/108/EC. For specified immunity all wiring
should be in screened twisted pairs, with the
screens earthed at one point within the safe area.
9

5.3 Installati n Pr cedure
a. Cut the specified aperture in the panel. To
achieve an IP66 seal between the instrument
enclosure and the instrument panel the
aperture must have the tighter tolerances
specified in Fig 4.
b. lide the gasket over the body of the Rate
Totaliser before inserting the instrument into
the panel aperture.
c. Firstly ensure that all the panel mounting
clamps are closed by turning the knurled
screws fully anti clockwise until the two pips
in the clamp foot align with holes in the clamp
body.
d. Place a clamp in the recess on each side of
the Rate Totaliser, pulling gently to slide it
onto the dovetail as shown in Fig 5. Push
the knurled screw slightly forward to engage
the thread and tighten by turning clockwise
until it is just finger tight. When all four
clamps are fitted ensure that the gasket
behind the front panel bezel is correctly
positioned before fully tightening the clamps
to secure the instrument. The maximum
recommended clamp tightening torque is
22cNm (1.95 lbf in) which is approximately
equivalent to finger-tight plus one half turn.
D n t ver tighten.
e. Connect the panel wiring to the rear terminal
block(s) as shown in Figs 4. To simplify
installation, the terminals are removable so
that the panel wiring can be completed
before the instrument is installed.
Fig 5 Fitting panel mounting clamps
5.4 Scale card
The Rate Totaliser’s units of measurement are
shown on a printed scale card in a window at the
right hand side of the display. The scale card is
mounted on a flexible strip that is inserted into a
slot at the rear of the instrument as shown in Fig 6.
Thus the scale card can easily be changed without
removing the BA358E Rate Totaliser from the
panel or opening the instrument enclosure.
New instruments are supplied with a printed scale
card showing the requested units of measurement,
if this information is not supplied when the Rate
Totaliser is ordered a blank card will be fitted.
A pack of self-adhesive scale cards printed with
common units of measurement is available as an
accessory from BEKA associates. Custom printed
scale cards can also be supplied.
To change a scale card, unclip the protruding end
of the flexible strip by gently pushing it upwards
and pulling it out of the enclosure. Peel the
existing scale card from the flexible strip and
replace it with a new printed card, which should be
aligned as shown below. Do not fit a new scale
card on top of an existing card.
Install the new scale card by gently pushing the
flexible strip into the slot at the rear of the
instrument, when it reaches the internal end-stop
secure it by pushing the end of the flexible strip
downwards so that the tapered section is held by
the rear panel.
Align the self-adhesive
printed scale card onto the
flexible strip and insert the
strip into the Rate
Totaliser as shown below.
Fig 6 Inserting flexible strip carrying scale card
into slot at the rear of Rate Totaliser.
10

6. CONFIGURATION AND CALIBRATION
The BA358E is configured and calibrated via the
four front panel push buttons that are located
below the display.
All the configuration functions are contained in an
easy to use menu that is shown diagrammatically
in Fig 8. Each function is summarised in section
6.3 which includes references to more detailed
information. Although this simple menu driven
system enables most adjustments to be made
without repeated reference to this manual, it is
recommended that at least the summary of the
configurable functions in section 6.3 is read before
attempting configuration or recalibration.
When the instrument is fitted with alarms, the basic
menu is expanded to include the alarm functions
that are described in section 10.3 of this manual.
N te:
While the instrument is being configured or
calibrated totalisation is suspended, any flow
occurring during this time will not be
recorded.
6.1 Calibrati n structure
Fig 7 shows the BA358E calibration structure. The
4/20mA input current, which in flow applications
represents flow rate, is usually displayed on the
five digit plus sign lower display. If necessary this
flow signal may be linearised using the square root
extractor or the 16 segment lineariser which are
selectable in the instrument’s ‘FunC’ sub-menu.
The rate display may then be calibrated using the
'CAL' or '5Et' functions to show the flow rate in the
required linear engineering units. Both the zero
(display at 4mA) and the span (display at 20mA)
are adjustable, although for unidirectional flow
application the display at 4mA is usually zero.
The position of the decimal point in the rate display
is defined by the ‘dP’ function. To simplify
calibration the BA358E uses floating point
arithmetic, moving the rate display decimal point
position will therefore affect totalisation.
For bi-directional flow applications zero flow will be
represented by an input current other than 4mA.
When one of the two bi-direction functions in the
‘FunC’ sub-menu is selected, input currents below
that representing zero flow will be shown as a
negative flow rate and the total flow display will
count down. For input currents above that
representing zero flow will be shown as a positive
flow rate and the total flow display will count up.
The BA358E total display is calculated from the
rate display using two serial factors: the timebase
't-bA5E' and the total scaling factor '5CALE-t'. The
timebase divides the rate display according to
whether the rate display represents flow per
second, per minute or per hour. The total scaling
factor '5CALE-t' is a wide range configurable
dividing factor allowing the rate and total displays
to be in different units.
The total is calculated and the display updated
once per second, which defines the resolution of
the total flow display. When total alarms are used
for batching applications, this resolution may define
the accuracy of the system.
Fig 7 Calibration structure
11

6.2 Accessing the c nfigurati n and
calibrati ns functi ns.
Throughout this manual push buttons are shown
as P, E, ▼ or ▲, and legends displayed by the
Rate Totaliser are shown within inverted commas
e.g. 'CAL' and ' ALr2'.
Access to the configuration menu is obtained by
operating the P and E push buttons
simultaneously. If the Rate Totaliser’s security
code is set to the default 0000 the first parameter
'FunC' will be displayed. If a security code other
than the default code 0000 has already been
entered, the Rate Totaliser will display 'CodE'.
Pressing the P button will clear this prompt
allowing each digit of the code to be entered using
the ▲ and ▼ push buttons and the P button to
move control to the next digit. When the correct
four digit code has been entered pressing E will
cause the first parameter 'FunC' to be displayed.
If the code is incorrect, or a button is not pressed
within twenty seconds, the Rate Totaliser will
automatically return to the display mode.
Once within the configuration menu the required
parameter can be reached by scrolling through the
menu using the ▲ and ▼ push buttons as shown
in Fig 8. When returning to the display mode
following recalibration or a change to any function,
the Rate Totaliser will display ‘dAtA’ followed by
‘ AVE’ while the new information is stored in non-
volatile memory.
All new Rate Totalisers are supplied calibrated as
requested at the time of ordering. If calibration is
not requested, Rate Totalisers will be supplied with
the following default configuration:
Default C nfigurati n
Access code ‘CodE’ 0000
Function ‘FunC’ ‘5td’ Linear
Rate display at 4mA ‘Zero’ 0.00
Rate display at 20mA ‘5PAn’ 100.00
Resolution ‘rE5n’ 1 digit
P button in display mode ‘C—P’ %
Local reset of total ‘t-rE5Et’ off
Local reset of grand total ‘Gt-rE5Et’ off
Clip off ‘CLIP oFF’ 000.00
Timebase ‘t-bA5E’ 1
Total scale factor ‘5CALE-t’ 1.00
Upper display ‘di5P-1’ Total
Update time ‘uPdAtE’ 1
6.3 Summary f c nfigurati n functi ns
This section summarises each of the main
configuration functions and includes a cross
reference to a more detailed description. Fig 8
illustrates the location of each function within the
configuration menu. The lineariser and the
optional factory fitted alarms are described
separately in sections 7 and 10.2 of this manual.
Display Summary f functi n
'FunC' Rate T taliser functi n
Defines the relationship between the
4/20mA input current and the
instruments rate display.
For uni-directional flow may be set
to:
‘5td’ tandard linear relationship
‘root’ quare root extraction
‘Lin’ 16 segment adjustable
lineariser – see section 7.
For bi-directional flow may be set
to:
‘bi-5td’ tandard linear relationship
‘bi-Lin’ 16 segment adjustable
lineariser – see section 7.
ee section 6.4
'rE5n' Display res luti n
Defines the resolution of the least
significant rate display digit. May be
set to ‘1’, ‘2’, ‘5’ or ‘10’ digits.
ee section 6.5
‘uPdAtE’ Update
Defines the interval between
updates. May be set to ‘1’, ‘2’, ‘3’,
‘4’ or ‘5’ seconds.
ee section 6.6
‘di5P-1’ Upper display
Defines whether ‘totAL’ or ‘rAtE’ is
shown on the upper eight digit
display.
ee section 6.7
‘di5P-2’ L wer display
Turns lower six digit display ‘on’ or
‘oFF’.
ee section 6.8
'dP' Decimal p ints
Positions the decimal point in the
‘rAtE’ and ‘totAL’ displays.
ee section 6.9
12

Display Summary f functi n
'CAL' Calibrati n f the rate display
using an external current s urce.
Enables the zero and span of the
rate display to be adjusted using an
external current source such as a
calibrator. When used with an
accurate traceable calibrator this is
the preferred method of calibration.
ee section 6.10
'5Et' Calibrati n f rate display using
internal references.
Enables the zero and span of the
rate display to be adjusted without
the need for an accurate input
current or disconnection from the
4/20mA loop.
ee section 6.11
‘Clr.Gt t’ Clear grand t tal
Resets the sixteen digit grand total
to zero when ‘Clr.YE ’ is selected
and ‘5urE’ is entered digit by digit to
confirm the instruction.
N te: Once cleared a grand total
can not be recovered.
ee section 6.12
‘t-bA5E’ Timebase
electable divisor to display flow
rate in units per second, per minute
or per hour.
elect:
‘tb-01’ for flow / second
‘tb-60’ for flow / minute
‘tb-3600’ for flow / hour
ee section 6.13
'C - - P' Functi n f P push butt n
The Rate Totaliser may be
configured to display the input
current in milliamps, or the input
current as a percentage of the
4/20mA input when the P push
button is operated in the display
mode.
elect:
‘PC’ % of 4/20mA input
‘4-20’ Current in mA
N te: ‘PC’ is not available with
lineariser.
ee section 6.14
Display Summary f functi n
‘5CALE-t’ T tal scale fact r
Defines the arithmetic relationship
between the rate and total displays.
May be adjusted between 0.0001
and 99999
5CALE-t = Units of rate display
Units of total display
To calculate 5CALE-t the required
units of measurement for the total
display must be converted to the
units of measurement used for the
rate display.
ee section 6.15 and Fig 6.
'CLiP- FF' Clip ff
To prevent the totalisation of very
low flow rates, this function defines
the flow rate below which totalisation
is inhibited and the ‘HOLD’
annunciator activated.
ee section 6.16
'L C.r5Et' L cal reset f t tal and grand
t tal.
Contains two independent functions
‘t-rE5et’ and ‘Gt-rE5Et’.
‘t-rE5Et’ enables the total display to
be reset to zero when ▼ and ▲
push buttons are operated
simultaneously for more than 2
seconds.
‘Gt-rE5Et’ enables the grand total to
be reset to zero when E and ▲ push
buttons are operated simultaneously
for more than 10 seconds.
ee section 6.17
'C dE' Security c de
Defines a four digit numeric code
that must be entered to gain access
to the configuration menu. Default
code 0000 disables this security
function and allows unrestricted
access to all conditioning functions.
ee section 6.18
13

Display Summary f functi n
'r5Et' Reset Rate T taliser t fact ry
defaults.
Contains two sub-functions,
elect:
‘ConF’ Returns instrument to
default configuration
shown in section 6.2
‘LtAb’ Returns lineariser to
defaults shown in
section 7.5
Both instructions must be confirmed
by entering ‘5urE’ digit by digit
before they will be executed.
ee section 6.19
14

15

6.4 Rate T taliser functi n: ‘FunC’
This configuration function defines the relationship
between the Rate Totaliser’s 4/20mA input current
and the instruments’s rate display. Three
alternatives are available for uni-direction flow and
two for bi-direction flow.
For uni-directional flow:
‘5td’ tandard linear relationship
‘root’ quare root extraction
‘Lin’ 16 segment adjustable lineariser
For bi-directional flow:
‘bi-5td’ tandard linear relationship
‘bi-Lin’ 16 segment adjustable lineariser
To reveal the existing instrument function, select
'FunC' from the configuration menu and press P.
If the function is set as required, press E to return
to the menu, or press the ▲ or ▼ button to change
the setting, followed by the E button to return to the
configuration menu.
‘5td’ Linear
Provides a linear relationship between the
4/20mA Rate Totaliser input current and
the instruments rate display for
uni-directional flow.
‘r t’ Square r t extracti n
Primarily intended to linearise the square
law 4/20mA output from differential
flowmeters.
For reference, the following table shows
the output current from a non-linearised
differential flowmeter.
% f full fl w Current utput mA
2.5 4.01
10.0 4.16
25.0 5.00
50.0 8.00
75.0 13.00
100.0 20.00
When the root function is selected the Rate
Totaliser will display flow in linear units for
uni-directional flow.
‘Lin’ 16 segment adjustable lineariser
May be adjusted to compensate for
flowmeter non-linearity with uni-directional
flow. Use of the lineariser is described in
section 7 of this instruction manual.
‘bi-5td’ Linear
Provides a linear relationship between the
4/20mA Rate Totaliser input current and
the instruments rate display for
bi-directional flow.
‘bi-Lin’ 16 segment adjustable lineariser
May be adjusted to compensate for
flowmeter non-linearity with bi-directional
flow. Use of the lineariser is described in
section 7 of this instruction manual.
6.5 Display res luti n: rE5n
This function defines the resolution of the least
significant display digit of the rate display.
Decreasing the display resolution can improve the
readability of a noisy signal. elect ''rE5n' from
the menu and press P which will reveal the current
display resolution. To change the resolution press
the ▲ or ▼ button to select 1, 2, 5 or 10 digits,
followed by the E button to enter the selection and
return to the configuration menu.
6.6 Display update time: ‘uPdAtE’
If the rate display is likely to change rapidly,
extending the time between display updates will
make the display easier to read. Five different
intervals between readings are selectable, 1, 2, 3,
4 or 5 seconds.
To reveal the existing update time select 'uPdAtE'
from the configuration menu and press P. If the
time is set as required, press E to return to the
menu, or press the ▲ or ▼ button to change the
time, followed by the E button to return to the
configuration menu.
This function only changes the interval between
successive display updates, it does not change the
instrument accuracy.
6.7 Upper display: ‘di5P-1’
The Rate Totaliser has two numeric displays:
Upper
8 digit 18mm high intended for showing total flow
display range –9999999 to 99999999
L wer
6 digits 12mm high intended for showing flow rate
display range –99999 to 99999
This function interchanges the rate and total
displays when the flow rate is required to be
predominant, resulting in a 5 digit plus sign upper
rate display and a 6 digit lower total display, or 5
digits plus sign when negative.
To reveal the existing upper display function select
'di5P-1' from the configuration menu and press P.
If set as required, press E to return to the
configuration menu, or press the ▲ or ▼ button to
toggle the function between ‘totAL’ and ‘rAtE’.
When set as required press E to enter the
selection and to return to the configuration menu.
16

6.8 L wer display: ‘di5P-2’
When only one display is required this function
allows the lower display to be disabled. To reveal
if the lower display is activated select 'di5P-2' from
the configuration menu and press P. If set as
required, press E to return to the configuration
menu, or press the ▲ or ▼ button to toggle the
function between ‘on’ and ‘oFF’. When set as
required press E to enter the selection and to
return to the configuration menu.
6.9 P siti n f the decimal p ints: ‘dP’
This function defines the position of the decimal
point in both the rate and total displays.
Rate display
The rate display can have up to five digits plus
sign, the decimal point may be positioned
between any of the digits, or may be omitted.
The BA358E uses floating point arithmetic so
moving the position of the rate display decimal
point will affect totalisation.
T tal display
The total display can have up to eight digits or
seven digits with a negative sign, the decimal
point may be positioned with up to five digits
after it, or it may be omitted.
N tes:
a. The position of the decimal point in the
Grand Total will be the same as that
selected for the Total Display.
b. If the total display decimal point can’t be
moved to the left it is likely that the existing
display will be over-ranged by the
adjustment. The total display should be
reset to zero, which should allow the decimal
point to be positioned as required.
c. If the decimal point is moved to the right, the
existing total display will be truncated, not
rounded, the lost precision can not be
recovered.
P siti ning the decimal p ints
To adjust the position of either the rate or total
display decimal point select 'dP' from the
configuration menu and press P. The upper
display defined as the rate or total display by
function ‘di5P-1’ (section 6.7) will be activated
and identified. The decimal point can be
positioned by operating the ▼ or ▲ push
button, when set as required enter the setting
and return to the conditioning menu by
operating the E button. Alternatively, to position
the lower display decimal point press the P
button which will display and identify the lower
display variable, but on the larger upper display.
The position of the decimal point can be
positioned in the same way by operating the ▼
and ▲ push buttons, when set as required
enter the setting and return to the conditioning
menu by operating the E button.
6.10 Calibrati n f the rate display using an
external current s urce: ‘CAL’
This function enables the zero and span of the rate
display to be adjusted using an external calibrated
current source. When used with an accurate
traceable current source this is the preferred
method of calibration.
Zer rate display with 4mA input
Span rate display with 20mA input
To calibrate the rate display select 'CAL' from the
configuration menu and press P. The BA358E will
display 'ZEro' which is a request for a 4mA input
current. Adjust the external current calibrator to
4.000mA and again press P which will reveal the
current zero rate display. The flashing digit of the
display can be changed by pressing the ▲ or ▼
buttons, when set as required pressing P will
transfer control to the next digit. When all the
digits have been adjusted, press E to enter the
new zero and return to the 'ZEro' prompt .
Pressing the ▲ button will cause the BA358E to
display ' PAn' which is a request for a 20mA input
current. Adjust the external current calibrator to
20.000mA and again press P which will reveal the
existing span rate display. The flashing digit of the
display can be changed by pressing the ▲ or ▼
buttons, when set s required pressing P will
transfer control to the next digit. When all the
digits have been adjusted press E to enter the new
rate span and return to the ' PAn' prompt. Finally
press E again to return to the configuration menu.
N tes:
a. The Rate Totaliser input current must be
adjusted to the required value before the zero
and span functions are entered by pressing the
P button.
b. Rate Totalisers may be calibrated at currents
other than 4 and 20mA, within the range 3.8 to
21.0mA providing the difference between the
two currents is greater than 4mA. If these
conditions are not complied with, the
instrument displays ‘FaiL’ and aborts the
calibration.
c. If the zero current is greater than the span
current the instrument will be reverse acting
i.e. an increasing input current will cause the
display to decrease.
17

6.11 Calibrati n f the rate display using
internal reference: ‘5Et’
Using the ‘5Et’ function the rate display can be
calibrated without the need to know the value of
the 4/20mA input current, or to disconnect the
BA358E Rate Totaliser from the 4/20mA loop.
When using the ‘5Et’ function the instrument’s
internal reference is used to simulate a 4mA and
20mA input current.
Zer rate display with a simulated 4mA input
Span rate display with a simulated 20mA input
To calibrate the rate display select '5Et' from the
configuration menu and press P. The Rate
Totaliser will display 'ZEro', pressing P again will
reveal the current rate display at 4mA. The
flashing digit can be adjusted by pressing the ▲ or
▼ buttons, when set as required pressing P will
transfer control to the next digit. When all the
digits have been adjusted, press E to return to the
'ZEro' prompt.
To adjust the rate display at 20mA, press the ▲
button which will cause the Rate Totaliser to
display '5PAn', pressing P will then reveal the
existing rate display at 20mA. The flashing digit
can be adjusted by pressing the ▲ or ▼ buttons,
when set as required pressing P will transfer
control to the next digit. When all the digits have
been adjusted press E twice to return to the '5PAn'
prompt followed and then to the ‘5Et’ prompt in the
configuration menu.
6.12 Clear grand t tal: ‘Clr.Gt t’
The grand total is a separate sixteen digit counter
which duplicates the total display but is not zeroed
when the total display is reset to zero. The grand
total may be viewed in the operating mode in two
eight digit sections as described in section 2.1 of
this manual. The following table illustrates how
grand totals are displayed.
Grand t tal High display L w display
1234567890123456 12345678 90123456
-1234 -1234
-12345678 - 12345678
-1234567890 -12 32567890
-123456789012345 -1234567 89012345
The grand total counter can be reset to zero from
the 'CLr.Gtot' function in the configuration menu, or
from the operating mode if the local grand total
reset has been activated, see section 6.17.
To zero the grand total from within the
configuration menu select 'Clr.Gtot' and press P
which will cause the instrument to display 'Clr.no'.
Press the ▼ or ▲ button until 'CLr.YE ' is
displayed and then press P which will result in a
'0000' prompt. Using the ▼ and ▲ buttons and
the P button to move to the next digit, enter '5urE'
digit by digit to confirm the instruction. Pressing E
will then reset the grand total counter to zero,
briefly displaying ‘Gt CLrd’ to confirm that the
instruction has been performed and return the
instrument to the 'CLr.Gtot' prompt in the
configuration menu.
CAUTION
After resetting the riginal grand
t tal can n t be rec vered.
6.13 Timebase: t-bA5E
Together with the total scale factor '5CALE-t', this
function defines the arithmetic relationship
between the rate and total displays. The
timebase divides the rate display by 1, 60 or 3,600
depending upon whether the BA358E rate display
represents flow per second, per minute or per
hour. ee Fig 6.
To check or change the timebase select 't-bA5E'
from the configuration menu and press P which will
reveal the current setting. Pressing the ▼ or ▲
button will index though the following three options.
BA358E
Rate display
Represents
flow
elect
in
t-bA5E
menu
Total display
= rate display
divided by
Per second ‘tb – 1’ 1
Per minute ‘tb – 60’ 60
Per hour ‘tb – 3600’ 3600
After selecting the required divisor, press E to
return to the ‘t-bA5E’ prompt in the configuration
menu.
6.14 Functi n f the P push-butt n: ‘C - - P’
When the Rate Totaliser is in the operating mode,
operating the P push button will display the input
current in milliamps, or the displayed flow rate as a
percentage of the difference between the displayed
flow rate at 4mA and 20mA inputs.
To check or change the function of the P push
button select 'C - -P' from the configuration menu
and press P to reveal the current setting. Pressing
the ▲ or ▼ button will toggle the setting between
'4-20' the current display in milliamps and 'PC' the
percentage display. When set as required press
E to return to the ‘C - - P’ prompt in the
configuration menu.
N te: The percentage option ‘PC’ is not available
when the sixteen segment lineariser is selected
see section 6.4.
18

6.15 T tal scale fact r: ‘5CALE-t’
Together with the timebase 't-bA5E', this is a
dividing factor that defines the arithmetic
relationship between the rate and total displays.
When the flow rate and the total flow are required
in the same units 5CALE-t = 1.0
The total scale factor may be set to any value
between 0.0001 and 99999 allowing the total flow
and rate of flow to be displayed in different
engineering units.
5CALE-t = Units of rate display
Units of total display
When calculating 5CALE-t the required units of
measurement for the total display must be
converted to those used for the rate display as
shown in the following example:
The BA358E rate display represents litres per
second but the total flow display is required in UK
gallons. There are 4.5461 litres in a UK gallon.
5CALE-t = Units of rate display
Units of total display
= 1 litre
1 gallon
= 1 litre
1 / 4.5461 litres
5CALE-t = 4.5461
Alternatively, if the total display is required in
thousand of UK gallons
= 1 litre
1 / 4546.1 litres
5CALE-t = 4546.1
The total scale factor 5CALE-t is not dependent on
the rate display units of time. i.e. flow units per
second, minute or per hour. The timebase t-bA5E
accounts for these differences.
To check or change the total scale factor select
'5CALE-t' from the configuration menu and press P
to reveal the existing setting, one digit will be
flashing. The value of the flashing digit may be
changed by pressing the ▼ or ▲ button. When
this digit is set as required pressing P will transfer
control to the next digit, which may be adjusted in
the same way.
To position the decimal point, repeatedly operate
the P button until the decimal point starts flashing.
The decimal point can then be positioned by
pressing the ▼ or ▲ button.
When the required total scale factor has been set,
press E to enter the number and return to the
‘5CALE-t’ prompt in the configuration menu.
6.16 Clip- ff: ‘CLiP- FF’
To prevent totalisation of very low flow rates, which
over long periods may result in significant
totalisation errors, the BA358E rate display can be
conditioned to stop totalisation when the flow rate
falls below a specified clip-off threshold. Clip-off
is an absolute value, for bi-direction flow systems it
inhibits totalisation for flow rates between +clip-off
and –clip-off.
Clip-off is shown in the same units as the
instruments rate display. To check or change the
clip-off threshold select 'CLiP-oFF' from the
configuration menu and press P to reveal the
current level, one digit will be flashing. The value
of the flashing digit may be changed by pressing
the ▼ or ▲ button. When this digit is set as
required pressing P will transfer control to the next
digit, which may be adjusted in the same way.
When set as required, press the E button to enter
the revised threshold and return to the ‘CliP-oFF’
prompt in the configuration menu.
For uni-directional flow when the flow rate falls
below the clip-off threshold, totalisation is inhibited,
the hold annunciator is activated but the flow
indicator continues to rotate until the input current
falls below 4mA.
For bi-directional flow when the positive or
negative flow rate is less than the absolute clip-off
threshold, totalisation is inhibited and the hold
annunciator is activated. The flow indicator
continues to rotate until the low rate is less than
±0.05% of flow rate display span.
6.17 L cal reset f t tal and grand t tal.
‘L C. R5Et’
This function contains two sub-functions ‘t-rE5Et’
and ‘Gt-rE5Et’ which allow the total display and the
grand total to be independently reset using the
instrument push buttons without access to the
configuration menu from the operating mode.
When enabled, ‘t-rE5Et’ allows an operator to reset
the BA358E total display to zero by operating the
▼ and ▲ push buttons simultaneously for at least
two seconds. To check the status of ‘t-rE5Et’
select 'LoC.r5Et'' from the configuration menu and
press P. Using the ▼ or ▲ button select ‘t-rE5Et’
and press P which will reveal if the function is
turned 'on' or 'oFF'. Operating the ▼ or ▲ button
will toggle the display between the two conditions.
19

When set as required pressing the E button will
enter the selection and return the display to the
‘t-rE5Et’ sub-function. The remote reset facility
described in section 4.2 of this manual is not
affected by the status of this local reset function.
When enabled, ‘Gt-rE5Et’ allows an operator to
reset the BA358E grand total to zero by operating
the E and ▲ push buttons simultaneously for at
least ten seconds. To check the status of ‘t-rE5Et’
select 'LoC.r5Et'' from the configuration menu and
press P. Using the ▼ or ▲ button select
‘Gt-rE5Et’ and press P which will reveal if the
function is turned 'on' or 'oFF'. Operating the ▼ or
▲ button will toggle the display between the two
conditions. When set as required pressing the E
button will enter the selection and return the
display to the ‘Gt-rE5Et’ sub-function.
6.18 Security c de: ‘C dE’
Access to the instrument configuration menu may
be protected by a four digit security code which
must be entered to gain access. New instruments
are configured with the default security code 0000
which allows unrestricted access to all
configuration functions.
To enter a new security code select 'CodE' from
the configuration menu and press P which will
cause the Rate Totaliser to display the existing
security code with one digit flashing. The flashing
digit can be adjusted using the ▲ and ▼ push
buttons, when set as required operating the P
button will transfer control to the next digit. When
all the digits have been adjusted press E to return
to the ‘CodE’ prompt in the configuration menu.
The revised security code will be activated when
the Rate Totaliser is returned to the display mode.
Please contact BEKA associates sales department
if the security code is lost.
6.19 Reset t fact ry defaults: ‘r5Et’
This function enables the Rate Totaliser and the
lineariser to be quickly returned to the factory
default configurations shown in sections 6.2 and
7.5
To reset the Rate Totaliser or lineariser select
‘r5Et’ from the configuration menu and press P, the
Rate Totaliser will display one of the reset options
‘ConF’ or ‘LtAb’.
‘ConF’ Resets the Rate Totaliser to defaults
‘LtAb’ Resets the lineariser to defaults
Using the ▲ or ▼ push-button select the required
sub-function and press P. To prevent accidental
resetting the request must be confirmed by
entering ‘5urE’. Using the ▲ button set the first
flashing digit to ‘5’ and press P to transfer control
to the second digit which should be set to ‘u’.
When ‘5urE’ has been entered pressing the E
button will reset the selected configuration menus
and return the display to the ‘r5Et’ function in the
configuration menu.
6.20 Over-range
Numerical over-range of the rate or total displays is
indicated by all the digits displaying ‘9’ and all the
decimal points flashing.
When the total display exceeds 99999999 or
-9999999 it will not automatically roll-over to zero
and continue counting, but the grand total will
continue to count. If it is likely that the total will
exceeds 99999999 or -9999999 the grand total,
which has a capacity of 1016 and –1015 counts,
should be reset to zero at the start of the operation.
If the total display exceeds 99999999 or -9999999
when the BA358E has been configured for bi-
directional flow, the total display will be locked and
will not record flow in the opposite direction to the
over-range, although the grand total will continue
to function.
20
Table of contents
Other BEKA Measuring Instrument manuals

BEKA
BEKA BA526C User manual

BEKA
BEKA BA507E Installation and operating instructions

BEKA
BEKA BA334ND User manual

BEKA
BEKA BA317NE User manual

BEKA
BEKA FOUNDATION BA618CF-F User manual

BEKA
BEKA BR323AL User manual

BEKA
BEKA Advisor A90-SS User manual

BEKA
BEKA BA344D User manual

BEKA
BEKA BA304NE User manual

BEKA
BEKA BA304NC User manual
Popular Measuring Instrument manuals by other brands

JingYan
JingYan TLL90S user guide

RadComm
RadComm RC2PLUS user manual

Dostmann Electronic
Dostmann Electronic P705 Operation manuals

Teledyne Analytical Instruments
Teledyne Analytical Instruments 7500ZB operating instructions

Otodynamics
Otodynamics Otoport Advance user manual

Velleman
Velleman CAMCOLBUL4 quick start guide