Analog 1 Function Options
1) Fuel Level S-W –Fuel amount, in percentage, can be measured and displayed using a
standard Stewart Warner scale sender of 240 ohms –33 ohms. 240 = Empty and 33 = Full.
Sender ground must be common with battery negative.
2) Fuel Level VDO –Fuel amount, in percentage can be measured and displayed using a VDO
scale sender of 10 ohms –180 ohms. 10 = Empty and 180 = Full. Sender ground must be
common with battery negative.
3) Oil Pressure SW 100 PSI –Oil pressure, in PSI, can be measured and displayed using a
standard Stewart Warner scale sender of 240 ohms –33 ohms. 240 = 0 PSI and 33 = 100 PSI.
Sender ground must be common with battery negative.
4) Oil Pressure SW 125 PSI –Oil pressure, in PSI, can be measured and displayed using a
standard Stewart Warner scale sender of 240 ohms –33 ohms. 240 = 0 PSI and 33 = 125 PSI.
Sender ground must be common with battery negative.
5) Oil Pressure SW bar –Oil pressure, in bar, can be measured and displayed using a standard
Stewart Warner scale sender of 240 ohms –33 ohms. 240 = 0 bar and 33 = 7 bar. Sender
ground must be common with battery negative.
6) Oil Pressure VDO PSI –Oil pressure, in PSI, can be measured and displayed using a standard
VDO scale sender of 10 ohms –180 ohms. 10 = 0 PSI and 180 = 150 PSI. Sender ground
must be common with battery negative.
7) Oil Pressure VDO bar –Oil pressure, in bar, can be measured and displayed using a standard
VDO scale sender of 10 ohms –180 ohms. 10 = 0 bar and 180 = 7 bar. Sender ground must
be common with battery negative.
8) Switch –This setting allows for a switch to be connected rather than an analog sender. Set
Analog 1 Message to assign a label to the switch device.
9) None –Set to None when no functionality is required.