
1.1 Input voltage range
¡The range is from AC85V to AC264V or DC120V to DC370V
(please see SPECIFICATIONS for details).
¡In cases that conform with safety standard, input voltage range is
AC100-AC240V (50/60Hz).
¡If input value doesn’t fall within above range, a unit may not oper-
ate in accordance with specifications and/or start hunting or fail.
If you need to apply a square waveform input voltage, which is
commonly used in UPS and inverters, please contact us.
¡When the input voltage changes suddenly, the output voltage ac-
curacy might exceed the specification. Please contact us.
¿ LFA10F, LFA15F, LFA30F
¡A power factor improvement circuit (active filter) is not built-in. If
you use multiple units for a single system, standards for input har-
monic current may not be satisfied. Please contact us for details.
¿ LFA10F, LFA15F, LFA30F, LFA50F, LFA75F,
LFA100F, LFA150F, LFA240F, LFA300F
¡Operation stop voltage is set at a lower value than that of a stan-
dard version (derating is needed).
-Use Conditions Output ( ) 3.3V
LFA10F 5W (3W)
LFA15F 7.5W (5W)
LFA30F 10W (7.5W)
LFA50F 15W (10W)
LFA75F 25W (15W)
LFA100F 30W (20W)
LFA150F 50W (30W)
LFA240F 80W
LFA300F 100W (75W)
Input AC50V or DC70V
Duty 1s/30s
*Please avoid using continuously for more than 1 second
under above conditions. Doing so may cause a failure.
1.2 Inrush current limiting
¡An inrush current limiting circuit is built-in.
¡If you need to use a switch on the input side, please select one
that can withstand an input inrush current.
¿ LFA10F
¡Resistance for line filter is used for inrush current limiting.
¿LFA15F, LFA30F, LFA50F, LFA75F, LFA100F,
LFA150F
¡Thermistor is used in the inrush current limiting circuit. When you
turn the power ON/OFF repeatedly within a short period of time,
please have enough intervals so that a power supply cools down
before being turned on.
1 Function ¿LFA240F, LFA300F
¡Thyristor technique is used in the inrush current limiting circuit.
When you turn power ON/OFF repeatedly within a short period of
time, please have enough intervals so that the inrush current limit-
ing circuit becomes operative.
¡When the switch of the input is turned on, the primary inrush cur-
rent and secondary inrush current will be generated because the
thyristor technique is used for the inrush current limiting circuit.
1.3 Overcurrent protection
¡An overcurrent protection circuit is built-in and activated at 105%
of the rated current or 101% of the peak current. A unit automati-
cally recovers when a fault condition is removed.
Please do not use a unit in short circuit and/or under an overcur-
rent condition.
¡Intermittent Operation Mode
Intermittent operation for overcurrent protection is included in a
part of series. When the overcurrent protection circuit is activated
and the output voltage drops to a certain extent, the output be-
comes intermittent so that the average current will also decrease.
1.4 Overvoltage protection
¡An overvoltage protection circuit is built-in. If the overvoltage pro-
tection circuit is activated, shut down the input voltage, wait more
than 3 minutes and turn on the AC input again to recover the out-
put voltage. Recovery time varies depending on such factors as
input voltage value at the time of the operation.
¡In option -R2, overvoltage protection is removed by toggling ON/
OFF signal of remote control.
Remarks :
Please avoid applying a voltage exceeding the rated voltage to an
output terminal. Doing so may cause a power supply to malfunc-
tion or fail. If you cannot avoid doing so, for example, if you need
to operate a motor, etc., please install an external diode on the
output terminal to protect the unit.
1.5 Output voltage adjustment range
¡Adjustment of output voltage is possible by using potentiometer.
Please refer to instruction manual 5.1.
¡Option ”-Y” is recommended which can adjust the output voltage.
AC-DC Power Supplies Open Frame/ Enclosed Type
Instruction Manual
LFA-22
LFA
melfa1.inddLFA-22me lfa1 indd LFA-22 2015/06/1515:22:542015/06/15 15:22:54