The range is from AC85V to AC264V.
AC input voltage must have a range from AC85V to AC264V for
normal operation. If the wrong input is applied, the unit will not op-
erate properly and/or may be damaged.
Inrush current limiting is built-in.
If a switch on the input side is installed, it has to be the one han-
dling the input inrush current.
The thermistor is used for protection from inrush current. When
power is turned ON/OFF repeatedly within a short period of time,
it is necessary to have enough time for power supply to cool
down.
The thyristor technique is used for protection from inrush current.
When power is turned ON/OFF repeatedly within a short period of
time, it is necessary to have enough time between power ON and
OFF to operate resistance circuit for inrush current.
Overcurrent protection is built-in and comes into effect at over
105% of the rated current. Overcurrent protection prevents the
unit from short circuit and overcurrent condition of less than 20
sec. The unit automatically recovers when the fault condition is
cleared.
If the output voltage drops more than 50% of the rated voltage in
an overcurrent protection mode, the average current will also be
reduced by the intermittent operation.
The overvoltage protection circuit is built-in and comes into effect
at 115 - 140% of the rated voltage(except 3V output voltage type:
it operates at 4.0 - 5.25V). The AC input should be shut down if
overvoltage protection is in operation. The minimum interval of
AC recycling for recovery is 1 1/2 minutes to 3 1/2 minutes.
In cases that conform with safety standard, input voltage range is
AC100-AC240V(50/60Hz).
The recovery time varies depending on input voltage.
l
l
l
PAA100F PAA150F
PAA300F PAA600F
PAA300F PAA600F
PAA-17
Remarks:
l
l
PAA300F PAA600F
(Optional -R”)
PAA50F PAA75F PAA100F PAA150F
”
Please avoid applying the over-rated voltage to the output termi-
nal. Power supply may operate incorrectly or fail.In case of oper-
ating a motor etc. , please install an external diode on the output
terminal to protect the unit.
Adjustment of output voltage is possible by using potentiometer.
Output voltage is increased by turning potentiometer clockwise
and is decreased by turning potentiometer counterclockwise.
Remote ON/OFF circuit (RC, RG) is isolated from input, output
and FG.
”
”
”
Option ”-R” is available for remote ON/OFF.
2.5 Output voltage adjustment range
2.6 Remote ON/OFF
n
n
n
n
Between RC and RG: Output voltage is ON at Low” level or short
circuit (0 - 0.8V).
Between RC and RG: Output voltage is OFF at High” level or
open circuit (2.7 - 5.0V).
Connection example:
When RC terminal is Low” level, fan out current is 3mA typ.
When Vcc is d, use 5V Vcc 12V. When remote ON/OFF
function is not used, please short between RC and RG terminals.
applie
Between RC(+) and RC(-)
Output
SW ON
(4.5 - 12.5V)
SW OFF
(0 - 0.5V)
ON
OFF
2 Function
PAA
Instruction Manual
AC-DC Power Supplies Enclosed type
June29,2011