Cosel PLA100F User manual

PLA-10
Basic Characteristics Data
*1The value of input current is at ACIN 100V and 90% load.
*2Burst mode frequency is changed by the used condition. Please contact us about detail.
*3Available by option -W. Please refer to instruction manual "5. Option and Others".
Basic Characteristics Data
Model Circuit method
Switching
frequency
[kHz]
Input
current
[A]
*1
Rated
input fuse
Inrush
current
protection
circuit
PCB/Pattern
Series/Parallel
operation availability
Material
Single
sided Double
sided Series
operation Parallel
operation
PLA100F Active filter 40 to 160 1.2 250V 3.15A Thermistor CEM-3 Yes Yes No
Flyback converter 20 to 150
*2
PLA150F Active filter 40 to 160 1.7 250V 4A Thermistor CEM-3 Yes Yes No
Flyback converter 20 to 150
*2
PLA300F Active filter 60 3.4 250V 10A Thermistor CEM-3 Yes Yes No
Forward converter 140
PLA600F Active filter 60 6.7 250V 16A SCR FR-4 Yes Yes *3
Forward converter 220
PLA
mepla.inddPLA-10me pla indd PLA-10 2014/03/0410:32:272014/03/04 10:32:27

3 Assembling and Installation Method PLA-14
3.1 Installation Method
3.2 Derating
3.3 Expected Life and Warranty
4 Ground PLA-16
PLA-14
PLA-15
PLA-16
1 Function PLA-12
2Series Operation and Parallel Operation PLA-13
1.1 Input Voltage Range
1.2 Inrush Current Limiting
1.3 Overcurrent Protection
1.4 Overvoltage Protection
1.5 Thermal Protection
1.6 Output Ripple and Ripple Noise
1.7 Output Voltage Adjustment
1.8 Isolation
1.9 Low Power Consumption
1.10 Remote ON/OFF
1.11 Remote Sensing
1.12 LV Alarm
PLA-12
PLA-12
PLA-12
PLA-12
PLA-12
PLA-13
PLA-13
PLA-13
PLA-13
PLA-13
PLA-13
PLA-13
5.1 Outline of Options
5.2 Others
PLA-16
PLA-21
5 Option and Others PLA-16
2.1 Series Operation
2.2 Parallel Operation
PLA-13
PLA-14
AC-DC Power Supplies Enclosed type
PLA-11
Instruction Manual
PLA
mepla1.indd1me pla1 indd 1 2014/03/0410:34:422014/03/04 10:34:42

1.1 Input Voltage Range
¡Input voltage range of the power supplies is from AC85V to
AC264V (please see SPECIFICATIONS for details).
¡To comply with safety standards, input voltage range is AC100-
AC240V(50/60Hz).
¡If input value doesn’t fall within above range, a unit may not oper-
ate in accordance with specifications and/or start hunting or fail.
If you need to apply a square waveform input voltage, which is
commonly used in UPS and inverters, please contact us.
¡When the input voltage changes suddenly, the output voltage
might exceed the specification. Please contact us.
¡When DC input voltage is applied, external DC fuse is required for
the protection. Please contact us about detail.
¿ PLA100F, PLA150F
¡Power factor correction circuit will be stopped at AC250Vin
or more. The operation is normal except decreasing the power
factor. Please contact us about detail.
¡Operation stop voltage is set at a lower value by output power de-
rating.
-Use Conditions Maximum output power
PLA100F 40W
PLA150F 60W
Input AC50V (DC70V)
Duty 1s/30s
*Please avoid using continuously for more than 1 second
under above conditions. Doing so may cause a failure.
¿ PLA300F, PLA600F
¡By using -U option, it is possible to operate at input voltage dip
condition that is lower than AC85V. Output derating is required
(Refer to 5. Option and Others). Please contact us for details.
1.2 Inrush Current Limiting
¡An inrush current limiting circuit is built-in.
¡If you need to use a switch on the input side, please select one
that can withstand an input inrush current.
¿ PLA100F, PLA150F, PLA300F
¡Thermistor is used in the inrush current limiting circuit. When you
turn the power ON/OFF repeatedly within a short period of time,
please have enough intervals so that a power supply cools down
before being turned on.
¿ PLA600F
¡Thyristor technique is used in the inrush current limiting circuit.
When you turn the power ON/OFF repeatedly within a short period
of time, please have enough intervals so that the inrush current
limiting circuit becomes operative.
1 Function ¡When the switch of the input is turned on, the primary inrush cur-
rent and secondary inrush current will be generated because the
thyristor technique is used for the inrush current limiting circuit.
1.3 Overcurrent Protection
¡An overcurrent protection circuit is built-in and activated at 105%
of the rated current. An unit automatically recovers when a fault
condition is removed.
Please do not use a unit in short circuit and/or under an overcur-
rent condition.
¡Intermittent Operation Mode
When the overcurrent protection circuit is activated and the output
voltage drops to a certain extent, the output becomes intermittent
so that the average current will also decrease.
¡When used with overcurrent at start-up, power supply may not
start-up by Intermittent operation mode. See the characteristics
below. (PLA100F, PLA150F)
100%
0%
Vo
Intermittent operation
start voltage
Not Intermittent
operation
Intermittent
operation
100 105min Io
Load factor [%]
Fig.1.1 Overcurrent protection characteristics
1.4 Overvoltage Protection
¡An overvoltage protection circuit is built-in. If the overvoltage pro-
tection circuit is activated, shut down the input voltage, wait more
than 3 minutes and turn on the AC input again to recover the out-
put voltage. Recovery time varies depending on such factors as
input voltage value at the time of the operation.
Remarks :
Please avoid applying a voltage exceeding the rated voltage to an
output terminal. Doing so may cause a power supply to malfunc-
tion or fail. If you cannot avoid doing so, for example, if you need
to operate a motor, etc., please contact us for details.
1.5 Thermal Protection
¿ PLA100F, PLA150F
¡PLA100F and PLA150F do not have thermal protection.
¿ PLA300F, PLA600F
¡A thermal protection circuit is built-in.
The thermal protection circuit may be activated under the follow-
ing conditions and shut down the output.
1
When a current and a temperature continue to exceed the val-
ues determined by the derating curve.
2
When a fan stops or air flow is blocked from the fan and weak-
ens.
If the thermal protection circuit is activated, shut off the input volt-
age and eliminate all the overheating conditions. To recover the
output voltage, have enough time to cool down the unit before
turning on the input voltage again.
AC-DC Power Supplies Enclosed type Instruction Manual
PLA-12
PLA
mepla1.inddPLA-12me pla1 indd PLA-12 2014/03/0410:34:422014/03/04 10:34:42

¡When power consumption is measred, please measure it by average
mode. The value is changed by environment.
1.10 Remote ON/OFF
¡Option -R is available to provide a remote ON/OFF function.
Please see ”5. Option and Others” for details.
1.11 Remote Sensing
¿ PLA100F, PLA150F, PLA300F
¡These models do not have this function.
¿ PLA600F
¡Option -W is available to provide a remote sensing function.
Please see ”5. Option and Others” for details.
1.12 LV Alarm
¿ PLA100F, PLA150F, PLA300F
¡These models do not have this function.
¿ PLA600F
¡Option -W is available to provide an alarms function. Please see
”5. Option and Others” for details.
2 Series Operation and
Parallel Operation
2.1 Series Operation
¡You can use a power supply in series operation. The output cur-
rent in series operation should be lower than the rated current of a
power supply with the lowest rated current among power supplies
that are serially connected. Please make sure that no current ex-
ceeding the rated current flows into a power supply.
Load
Power
Supply
+
-
+
-
Power
Supply
LoadLoad
Power
Supply
+
-
+
-
Power
Supply
Fig.2.1 Examples of connecting in series operation
1.6 Output Ripple and Ripple Noise
¡Output ripple noise may be influenced by measurement environ-
ment, measuring method Fig.1.2 is recommended.
+Vout
-Vout
Load
150mm
C
2
C
1
Osiloscope/
Ripple noise meter
Bw:20MHz
Differential probe
+
C1 : Film capacitor 0.1μF
C2 : Aluminum electrolytic capacitor 22μF
Fig.1.2 Measuring method of Ripple and Ripple Noise
Remarks :
When GND cable of probe with flux of magnetic force from power
supply are crossing, ripple and ripple noise might not measure
correctly.
Please note the measuring environment.
Bad example Good example
Fig.1.3 Example of measuring output ripple and ripple noise
1.7 Output Voltage Adjustment
¡To increase an output voltage, turn a built-in potentiometer clock-
wise. To decrease the output voltage, turn it counterclockwise.
¡When output voltage is adjusted, it should be turned slowly.
¿ PLA300F, PLA600F
¡We are offering an Option -V, which doesn’t have a built-in poten-
tiometer but instead enables you to adjust the output voltage by
using an external potentiometer (please see 5 Option and Others).
1.8 Isolation
¡For a receiving inspection, such as Hi-Pot test, gradually increase
(decrease) the voltage for the start (shut down). Avoid using Hi-
Pot tester with the timer because it may generate voltage a few
times higher than the applied voltage, at ON/OFF of a timer.
1.9 Low Power Consumption
¿ PLA100F, PLA150F
¡Low power consumption function is built-in in PLA100F and PLA150F.
(No load power consumption: 1.5W typ)
¡In 0 to 30% load, switching power loss is reduced by burst operation.
By this function, ripple and ripple noise specification are changed.
¡Ripple and ripple noise are changed by used condition. Please con-
tact us about detail.
AC-DC Power Supplies Enclosed type Instruction Manual
PLA-13
PLA
mepla1.inddPLA-13me pla1 indd PLA-13 2014/03/0410:34:422014/03/04 10:34:42

Ambient temperature around each power supply should not ex-
ceed the temperature range shown in the derating curve.
¿ PLA300F
F
A
N
Air flow
Terminal block
side
Vent hole
side
Fan side
More than
30mm
More than
30mm
More than
30mm
Terminal block
Terminal block
(A)
Vent hole
side
More than
30mm
Terminal block Terminal block
(B) (C) (D)
(E)
Terminal block
Not available
¿ PLA600F
F
A
N
Air flow
Terminal block
side Fan side
More than
30mm
More than
30mm
More than
30mm
Terminal
block
Terminal block
(A)
Vent hole
side
Vent hole
side
More than
30mm
Terminal block
side
Terminal block
(B) (C) (D)
(E)
Terminal block
Not available
¡Avoid installation method (E), which can cause stress on the
mounting holes.
¡Fan for forced cooling is built-in. Do not block the ventilation at
suction side (terminal block and vent hole side) and its opposite
side.
¡When unit operates at dusty place, attach air-filter to dust into the
unit. In this case, avoid poorly ventilated environments.
¡When internal fan stops, thermal protection circuit works which
stops the output. To keep reliability of the unit, periodic mainte-
nance of the fan is required.
¡Expected life of fan (R(t) = 90%) is different by the used condition.
2.2 Parallel Operation
¡Redundancy operation is available by wiring as shown below.
I2
I1I3
-
+
+
-
Load
Power
Supply
Power
Supply
Fig.2.2 Example of redundancy operation
¡Even a slight difference in output voltage can affect the balance
between the values of I1and I2.
Please make sure that the value of l3 does not exceed the rated
current of a power supply.
l3[the rated current value
¿ PLA100F, PLA150F, PLA300F
¡Parallel operation is not possible.
¿ PLA600F
¡Available by option -W. Please refer to instruction manual “5. Op-
tion and Others”.
3 Assembling and
Installation Method
3.1 Installation Method
¡Do not insert a screw more than 6mm away from the outside of
a power supply to keep enough insulation distance between the
screw and internal components.
6mm max
C
hassis o
f
PBA series
Chassis of
customer system
Mounting Screw
PLAseries
Fig.3.1 Mounting screw
¿ PLA100F, PLA150F
(A) (B) (C)
Terminal block
Terminal block More than
20mm
¡If you use two or more power supplies side by side, please keep
a sufficient distance between them to allow enough air ventilation.
AC-DC Power Supplies Enclosed type Instruction Manual
PLA-14
PLA
mepla1.inddPLA-14me pla1 indd PLA-14 2014/03/0410:34:432014/03/04 10:34:43

3.2 Derating
¡Input Voltage Derating Curve
Input voltage derating curve is shown in Fig.3.2.
85 115
80
100
[%]
[AC V
]
Load
100
90
Fig.3.2 Input voltage derating curve
¡Ambient Temperature Derating Curve
Derating curve depending on an ambient temperature is shown in
Fig.3.3 to Fig.3.6.
*Specifications for ripple and ripple noise change in the shaded
area.
¿ PLA100F, PLA150F
(1) Temperature of point Aand point B
When using it,it is necessary to radiate heat by the heat of the pow-
er supply.
Table 3.1 shows the relation between the upper limit temperature
(Point A and Point B).
Please consider the ventilation so that the convection which is
enough for the whole power supply is provided.
And temperature of Point A and Point B please become lower than
upper limit temperature.
The expectancy life in the upper bound temperature (Point A and
Point B) is three years.
Please refer to External View for the position of PointA and Point B.
Table 3.1 Temperature of point Aand point B
Model All direction
Point A Point B
PLA100F 81Cmax
-
PLA150F 85Cmax 78Cmax
(2) Derating curve in ambient temperature
-20 -10
0080706055504030
12 3
)3Forced air (0.5m3/min
1Convection (A mount)
2Convection (B, C mount)
08
010
06
0405
02
2010
Load factor [%]
[C]Ambient temperature
Fig.3.3 Ambient temperature derating curve for PLA100F/150F-12, -15
-20 -10
008070605535 45 504030
12 3
)3Forced air (0.5m3/min
1Convection (A mount)
2Convection (B, C mount)
08
010
06
0405
02
2010
Load factor [%]
[C]Ambient temperature
Fig.3.4 Ambient temperature derating curve for PLA100F/150F-24, -36, -48
Ambient temperature should be measured in 5 to 10cm from
power supply to avoid own heat-up. About detail of ambient tem-
perature, please contact us.
¿ PLA300F
Ambient temperature [C]
02010-20 -10
100
80
60
50
40
20
08060 70504030
Load factor [%]
Fig.3.5 Ambient temperature derating curve for PLA300F
Ambient temperature should be measured in front of terminal
block. Please note about temperature raise of the input and output
cable. About detail of ambient temperature, please contact us.
¿ PLA600F
02010-20 -10
100
80
60
40
20
08060 70504030
Ambient temperature [C]
Load factor [%]
Fig.3.6 Ambient temperature derating curve for PLA600F
Ambient temperature should be measured in front of terminal
block. Please note about temperature raise of the input and output
cable. About detail of ambient temperature, please contact us.
AC-DC Power Supplies Enclosed type Instruction Manual
PLA-15
PLA
mepla1.inddPLA-15me pla1 indd PLA-15 2014/03/0410:34:432014/03/04 10:34:43

3.3 Expected Life and Warranty
¡Expected Life
Please see the following tables for expected life.
¿ PLA100F, PLA150F
Table 3.2 Expected lifetime (PLA100F/PLA150F)
Mounting
Method
Cooling
Method
Average ambient
temperature
Expected lifetime
[years]
Io[50% Io[100%
A Convection
Ta = 30C10 5
Ta = 40C53
B, C Convection
Ta = 20C10 5
Ta = 30C53
A, B , C
Forced air cooling Ta = 40C10 5
Ta = 55C53
¿ PLA300F, PLA600F
Table 3.3 Expected lifetime (PLA300F/PLA600F)
Mounting
Cooling method Average ambient
temperature
Expected lifetime
[years]
Io<=50% Io<=100%
All
direction Forced air cooling
(internal fan)
Ta = 30C10 7
Ta = 40C75
Ta = 50C53
*This lifetime includes a built-in fan lifetime.
¡Fans should be exchanged on a regular basis. Their expected life-
time (R (t) = 90%) depends on use conditions as shown in Fig.3.7.
4020 30 50 60 70 80
10,000
100,000
500,000
Temperature of measurement point [C]
Expected Lifetime [H]
Fig.3.7 Expected lifetime of fan
AIR FLOW
20mm
Measurement point
Power supply
Terminal
block
F
A
N
(Side)
AIR FLOW
20mm
Measurement point
Power supply
Terminal
block
F
A
N
(Top)
Fig.3.8 Temperature of measurment point for fan lifetime
¡Warranty
Please see the following table for warranty. The warranty period is
5 years maximum.
¿ PLA100F, PLA150F
Table 3.4 Warranty (PLA100F/PLA150F)
Mounting
Cooling method Average ambient
temperature
Warranty [years]
Io<=50% Io<=100%
A Convection
Ta = 30C55
Ta = 40C53
B, C Convection
Ta = 20C55
Ta = 30C53
A, B , C
Forced air cooling Ta = 40C55
Ta = 55C53
¿ PLA300F, PLA600F
Table 3.5 Warranty (PLA300F/PLA600F)
Mounting
Cooling method Average ambient
temperature
Warranty [years]
Io<=50% Io<=100%
All
direction Forced air cooling
(internal fan) Ta = 40C55
Ta = 50C53
4 Ground
¡When installing the power supply with your unit, ensure that the
input FG terminal is connected to safety ground of the unit.
5 Option and Others
5.1 Outline of Options
¿ -C
(PLA100F, PLA150F, PLA300F, PLA600F)
-Option -C units have coated internal PCB for better moisture
resistance.
AC-DC Power Supplies Enclosed type Instruction Manual
PLA-16
PLA
mepla1.inddPLA-16me pla1 indd PLA-16 2014/03/0410:34:432014/03/04 10:34:43

¿ -G (PLA300F, PLA600F)
-Option -G units are low leakage current type.
-Differences from standard versions are summarized in Table 5.1.
Table 5.1 Low leakage current type
Leakage Current
(AC240V 60Hz) 0.15mA max
Conducted Noise N/A
Output Ripple Noise Please contact us for details about
Ripple Noise
*This is the value that measured on measuring board with capaci-
tor of 22μF and 0.1μF at 150mm from output terminal block.
Measured by 20MHz oscilloscope or Ripple-Noise meter (Equivalent
to KEISOKU-GIKEN:RM-103).
¿ -V (PLA300F, PLA600F)
-Option -V units have a connector for external potentiometer in-
stead of a built-in potentiometer.
-Appearance of Option -V units is different from that of standard
units. Please contact us for details.
-If power is turned on while CN3 is open, output voltage de-
creases significantly.
CN3
V.ADJ
+V +V
Fig.5.1 Front view of option-V (PLA600F)
¿ -U (PLA300F, PLA600F)
-Operation stop voltage of Option -U units is set at a lower value
than that of a standard version to support low input voltage.
-Use Conditions (Conditions of SEMI F-47 compliant)
Maximum output power *( ) is 5V output model.
PLA300F 120W (100W)
PLA600F 240W (200W)
Input AC50V
Duty 1s/30s
*Please avoid using continuously for more than 1 second under
above conditions. Doing so may cause a failure.
¿ -R
(PLA100F, PLA150F, PLA300F, PLA600F)
-You can control output ON/OFF in Option -R units. An external
DC power supply is connected and it should be applied a volt-
age to a remote ON/OFF connector to control it.
-Appearance is changed from standard model.
-There is a lineup of optional harnesses. Refer to option parts.
-Please contact us for details.
Table 5.2 Remote on/off operating conditions
Model Name Built-in
Resistor
Ri [ W]
Voltage between RC
and RCG [V] Input
Current
[mA]
Output ON Output OFF
PLA100F, PLA150F,
PLA300F, PLA600F 780 4.5 - 12.5 0 - 0.5 (20max)
Ri
RCG
RC
*1
RSW
External Power
Source
Remote ON/OFF connector (Optional)
Input Current
Inside of a Power
Supply
Fig.5.2 Example of using a remote ON/OFF circuit
*1 If the output of an external power supply is within the range
of 4.5 - 12.5V, you do not need a current limiting resistor R. If
the output exceeds 12.5V, however, please connect the cur-
rent limiting resistor R.
To calculate a current limiting resistance value, please use the fol-
lowing equation.
R[W]= Vcc-(1.1+RiX0.005)
0.005 Vcc : External Power Source
*
Please wire carefully. If you wire wrongly, the internal
components of a unit may be damaged.
*
Remote ON/OFF circuits is isolated from input, output and FG
circuits .
¡PLA100F, PLA150F, PLA300F Remote on/off control.
-Connector is added. Please contact us for detail.
-Start up time will be delay when on/off term is very short.
Please keep 2 seconds for on/off cycle.
CN4
Fig.5.3 Example of option -R (PLA100F, PLA150F)
AC-DC Power Supplies Enclosed type Instruction Manual
PLA-17
PLA
mepla1.inddPLA-17me pla1 indd PLA-17 2014/03/0410:34:442014/03/04 10:34:44

Table 5.3 Mating connectors and terminals on CN4
Connector Housing Terminal Mfr
CN4 B2B-XH-AM XHP-2
BXH-001T-P0.6
or
SXH-001T-P0.6
J.S.T.
CN1
+V AC
CN1
V.ADJ +V -V -V FG (N)
AC AC
(L)
(G)
Fig.5.4 Example of option -R (PLA300F)
Table 5.4 Mating connectors and terminals on CN1
Connector Housing Terminal Mfr
CN1 XARR-02V XAP-02V-1
SXA-001T-P0.6
J.S.T.
¡PLA600F Remote on/off control
-CN1 is added. Please contact us for detail.
-Appearance is changed from standard model.
CN1
V.ADJ
+V -V+V -V
AC
(L)(N)
AC
FG
Fig.5.5 Front view of option -R (PLA600F)
CN1
1
2
9
10
Fig.5.6 Pin number
Table 5.5 Pin configuration and function of CN1
PIN FUNCTION
1 - :N.C.
2 - :N.C.
3 RC :Remote ON/OFF
4 RCG:Remote ON/OFF(GND)
5 - :N.C.
6 - :N.C.
7 - :N.C.
8 - :N.C.
9 - :N.C.
10 - :N.C.
Table 5.6 Mating connectors and terminals on CN1
Connector Housing Terminal Mfr
CN1
S10B-PHDSS PHDR-10VS
Reel :SPHD-002T-P0.5
Loose :BPHD-001T-P0.5
:BPHD-002T-P0.5 J.S.T.
¿ -W (PLA600F only)
-Remote sensing, low output voltage alarm (LV alarm) and paral-
lel operation function are built-in to this model.
-Appearance is changed from standard model.
-There is a lineup of optional harnesses. Refer to option parts.
-Please contact us for details.
-Differences from standard versions are summarized in Table 5.6.
Table 5.7 Specification differences of Option -W
Load regulation 1.5 times of standard spec.
Ripple 1.5 times of standard spec.
Ripple noise 1.5 times of standard spec.
CN2
FG AC
(N) (L)
AC
-V+V -V+V
CN1
H-SN-31
(install)
Fig.5.7 Front view of option -W
Table 5.8 Pin configuration and function of CN1 and CN2
CN1CN2
1
2
9
10
1
2
9
10
Fig.5.8 Pin number
PIN FUNCTION
1+M :Self sensing terminal (Don’t
wire for external function)
2 +S :+Sensing
3 - :N.C.
4 - :N.C.
5 LV :LV alarm
6 LVG :LV alarm (GND)
7 CB :Current balance
8 - :N.C.
9-M :Self sensing terminal (Don’t
wire for external function)
10 -S :-Sensing
Table 5.9 Mating connectors and terminals on CN1 and CN2
Connector Housing Terminal Mfr
CN1
CN2
S10B-PHDSS PHDR-10VS
Reel :SPHD-002T-P0.5
Loose :BPHD-001T-P0.5
:BPHD-002T-P0.5 J.S.T.
¡LV alarm
LV alarm operating conditions are shown in Table 5.10 and inter-
nal circuit is shown in Fig.5.9 LV alarm is isolated from input, out-
put and FG.
100kW0. 1 FLV
LVG
Current limiting
resistor
External power
source
Fig.5.9 LV internal circuit
AC-DC Power Supplies Enclosed type Instruction Manual
PLA-18
PLA
mepla1.inddPLA-18me pla1 indd PLA-18 2014/03/0410:34:442014/03/04 10:34:44

Table 5.10 LV alarm operating conditions
Alarm Output of alarm
LV
If the output voltage drops below
the rating, the alarm signal is out-
put from LV and LVG terminal.
Note : 1This becomes unstable
in the event of output
overcurrent (intermit-
tent overcurrent).
2The alarm signal is not
output for parallel op-
eration that does not
use OR diodes.
Open collector method
Good : Low
(0 - 0.8V, 10mA max)
Fail : High or Open
50V 10mA max
¡Parallel operation
In case of parallel operation, please make the following process.
1Before wiring, output voltage should be set to the required
voltage at first to each power supply. Each output voltage dif-
ferences must be less than 0.1V or 1% of the rated output volt-
age, whichever smaller.
2Please connect each wire refer to Fig.5.10. And please use
same length and same type wire to connect each load line.
3As variance of output current drew from each power supply is
maximum 15%, the total output current must not exceed the
value determined by the following equation.
The rated
current per unit
= X(Number of unit) X0.85
Output current in
parallel operation
*
Please confirm that each output current is within the rated cur-
rent.
-
When the output voltage adjustment is required after wiring, retry
the above process from 1again.
-
When the number of units in parallel operation increases, input
current increases at the same time. Adequate wiring design for in-
put circuitry is required, such as circuit pattern, wiring and current
capacity for equipment.
-In parallel operation, the maximum operative number of units is 5.
-It is not possible to work as master and booster operation.
CB CB CB
-S -S -S
Load
(+) (
-
)
Fig.5.10 Parallel operation condition
-
When the output current is less than 10% of rated output current,
the output voltage fluctuates occasionally. The minimum current
is different depending on the model and the number of parallel
operation. Please contact us.
-
When output cable is not same length from each power supplies,
output current value will not be balanced at each units. Please
set the cable length as same as possible.
¡Remote sensing
-These models have a built-in remote sensing function.
If you do not use the remote sensing function, you can short out
between +S and +M and between -S and -M on CN1.
When the power supplies are shipped from a factory, they come
with a dedicated harness (H-SN-31) being mounted on CN1. If
you do not use the remote sensing function, you can use the
power supplies as they are.
-Please see Fig.5.10 if you do not use the remote sensing function.
Please see Fig.5.11 if you use the remote sensing function.
-When you use the remote sensing function, please wire from +S
and -S on CN1. Harnesses are available for your purchase.
Please contact us for details.
When you use the remote sensing, please note the followings.
1Wire carefully. When a connection of a load line becomes loose
(due to such factors as loose screw), the load current flows to
the sensing line and internal circuits of the power supply may be
damaged.
2Use a sufficiently thick wire to connect between the power supply
and the load and keep the line drop at 0.3V or below.
3If the sensing line is long, connect C1 and R1.
4Use a twisted pair wire or a shielded wire as the sensing line.
5Do not draw the output current from +M, -M, +S or -S.
6When the remote sensing function is used, the output voltage of
the power supply may show an oscillating waveform or the output
voltage may dramatically fluctuate because of an impedance of
wiring and load conditions.
Please check and evaluate carefully before using the remote
sensing function.
If the output voltage becomes unstable, we suggest you to try the
followings.
- Remove the remote sensing line on the minus side and short
out between -S and -M.
- Connect C1, R1 and R2.
Please contact us for details.
AC-DC Power Supplies Enclosed type Instruction Manual
PLA-19
PLA
mepla1.inddPLA-19me pla1 indd PLA-19 2014/03/0410:34:442014/03/04 10:34:44

+MShort at CN1
(H-SN-31)
+S
-S
CN1
-M
+V
-VLoad
C1
Fig.5.11 When not using remote sensing function
+M
Wire the sensing lines as close
as possible
+S
-S
CN1
-M
+V
-VLoad
C1R2
R1
Fig.5.12 When using remote sensing function
¿ -T (PLA100F, PLA150F)
-Option -T units have vertically positioned screws on a terminal
block.
-Please contact us for details about appearance.
Output
terminal(
+
)
Output
terminal(
-
)
FG( )
AC(N)
AC(L)
M3.5
V.ADJ
Fig.5.13 Example of option -T(PLA100F)
¿ -T2 (PLA300F, PLA600F)
-Option -T2 units have terminal block form changed.
-Please contact us for details about appearance.
+V +V -V -V AC (L)
V.ADJ AC
(N)FG
FG( )
AC(L)
AC(N)
M4
Output
terminal(
+
)
Output
terminal(
-
)
Fig.5.14 Example of option -T2(PLA300F)
¿ -J (PLA100F, PLA150F)
-
Option -J units have AMP connectors instead of a terminal
block.
-
Dedicated harnesses are available for your purchase. Please
see Optional Parts for details.
-
Please contact us for details about appearance.
-
Please do not apply more than 5A per 1 pin.
-
Option -J can not meet UL508.
V.ADJ
AC(L)
AC(N)
FG
-
V
+
V
CN1
CN2
Fig.5.15 Example of option -J (PLA100F)
Table 5.11 Mating connectors and terminals on CN1 and CN2 in option -J
I/O Connector Matching Housing Terminal
CN1 1-1123724-3 1-1123722-5 Reel : 1123721-1
Loose : 1318912-1
CN2 1-1123723-6 1-1123722-6 Reel : 1123721-1
Loose : 1318912-1
(Mfr. Tyco electronics AMP)
¿ -L (PLA100F, PLA150F)
¡In this Option -L unit, no load power consumption is smaller than
standard model.
[No load power consumption]
Option -L : 0.5W max
Standard model (Reference) : 1.5W typ
Condition: AC240V input, Io=0A
¡When the ambient temperature is from -10 degree C to -20 de-
grees, input voltage range of the power supplies is from AC115V
to AC264V.
¡-L model requires 1 second interval for restart from power OFF to
power ON.
In the short interval, output voltage hunting may occur.
¡Output voltage change by dynamic load response (Io=0%-100%)
is different from standard model.
Please confirm the actual voltage change in final application be-
fore use.
AC-DC Power Supplies Enclosed type Instruction Manual
PLA-20
PLA
mepla1.inddPLA-20me pla1 indd PLA-20 2014/03/0410:34:442014/03/04 10:34:44

¿ -F4 (PLA300F, PLA600F)
-Option -F4 units have a low-speed low-noise fan instead of a
standard fan.
-Differences from standard versions are summarized in Fig.5.16
and Fig.5.17.
02010-20 -10
100
80
60
40
50
20
060 70504030
Ambient temperature [C]
Load factor [%]
Fig.5.16
Ambient temperature derating curve for PLA300F (Option-F4)
02010-20 -10
100
80
60
40
50
20
060 70504030
2PLA600F-12,15,24,36,48-F4
1PLA600F-5-F4
1
2
Ambient temperature [C]
Load factor [%]
Fig.5.17
Ambient temperature derating curve for PLA600F (Option-F4)
¿ -N1 (PLA100F, PLA150F)
-Option -N1 units come with dedicated DIN rail attachment.
-Please contact us for details about appearance.
-Option -N1 units has its own vibration and shock specification.
Please contact us for details.
-Please contact us for about safety approvals.
Fig.5.18 Power supply installed on a DIN rail (PLA100F)
5.2 Others
¡While turning on the electricity, and for a while after turning off,
please don’t touch the inside of a power supply because there are
some hot parts in that.
¡When a mass capacitor is connected with the output terminal
(load side), the output might become the stop or an unstable oper-
ation. Please contact us for details when you connect the capaci-
tor.
¡In case of input voltage stop at no load, output voltage is kept for
several minutes because of low power consumption. Please be
careful in maintenance, to avoid electrical shock.
¡In PLA300F and PLA600F, thermal protection will be activated by
internal fan stop. Please have the regularly maintenance for im-
proving reliability.
¡When these power supplies are connected to the input terminal in
parallel, the total capacitance between line and line becomes big.
Therefore, the electrical discharge resistance on the safety stan-
dard might become necessary.
Please contact us for details when safety standard is necessary at
multiple units usage.
AC-DC Power Supplies Enclosed type Instruction Manual
PLA-21
PLA
mepla1.inddPLA-21me pla1 indd PLA-21 2014/03/0410:34:442014/03/04 10:34:44
This manual suits for next models
6
Table of contents
Other Cosel Power Supply manuals

Cosel
Cosel AD240 User manual

Cosel
Cosel PBA300F User manual

Cosel
Cosel GHA300F User manual

Cosel
Cosel KL Series User manual

Cosel
Cosel MMB50A User manual

Cosel
Cosel UAW125S User manual

Cosel
Cosel LFP100F User manual

Cosel
Cosel STA5000T-R User manual

Cosel
Cosel PLA30F User manual

Cosel
Cosel LCC30A User manual