ThisproductconformstoBSEN60669-2-1andBSEN55015.
Pleaseensurethemostrecenteditionoftheappropriatelocalwiringregulationsareobserved
andsuitableprotectionisprovidede.g.a10ampcircuitbreakerandvoltagesurgeprotection.
Pleaseensurethatthisdeviceisdisconnectedfromthesupplyifaninsulationtestismade.
Thisproductiscoveredbyawarrantywhichextendsto5yearsfromthedateofmanufacture.
Precautions and Warranty
Wall or ceiling mounted PIR occupancy switch
WACEPIR
DANLERS3-wirewallorceilingmountedpassiveinfra-redoccupancy
switch (WACEPIR) should be wall mounted at a location where a
neutralconnectionisavailable.
TheWACEPIRincorporatesapassiveinfra-redquadsensortodetect
movementofawarmbodywithinthedetectionzone(diagramBorC)
andaphotocelltomonitortheambientlightlevel.
Upondetectingmovement,iftheambientlightisdarkenough,the
WACEPIR switch willturn theload on.Theambient threshold can
be set by the user to between approximately 30 lux and 1000 lux
and maximum (photocell inactive) at the PIR via the LUX adjuster
(diagram A).
Ifnomoremovementisdetectedwithinapre-selectedtime,then
theWACEPIRswitchwillturntheloadoff.Thistimelagcanbeset
viatheTIMEadjusterto10seconds,20seconds,40seconds,80
seconds, 2 minutes 30 seconds, 5 minutes,10 minutes, 20 minutes
or 40 minutes (diagram A).
The WACEPIR also incorporates a sensitivity adjuster.
Turn fully
clockwiseformaximumrangeandsensitivityofthepersondetector.
SeveralWACEPIRunitscanbewiredinparallel(diagramE).
Loading limits
Theswitchshouldonlybeconnectedtoa230V50HzACsupply.
ThesePIRswitchescanswitchupto:
6amps(1500W)ofresistiveloads.
6amps(1500W)ofuorescentloads.
3amps(750W)ofelectronicandwirewoundtransformerloads.
2amps(500W)ofCFL,2Dlamps,LEDDriversandLEDlamps
andttings.
1amp(250W)offans
Minimumload2Wresistive,suitableformostenergysavinglamps,
LEDsandemergencyttings.
08/04/15 INS948 WACEPIR
Lux and Time set-up
Forconvenience,ensurethattheTIMEissettotheminimumwhen
settinguptheLUXlevel.AfterwardssettheTIMEandSENStovalues
suitablefortheapplication.
TheLUXis bestsetupwhenthelocalambient lightisclosetothe
minimumdesiredlightlevel.WiththeLUXsetfullyclockwisewaitforthe
WACEPIRtoswitchoff.RotatetheLUXadjusterslowlyanticlockwise
(- to +), whilst waving your hand approximately 1m in front of the
WACEPIR,untiltheloadswitcheson.
The load will not switch on:
• TheLUXadjusterissettoolowandisinhibitingtheswitch.
• ThemovingbodyisnotemittingmoreIRthanthebackground.
(Personwearinginsulatingclothinginawarmenvironment)
• PersonistoofarfromthePIRswitch,seedetectiondiagram.
• Personismovingunusuallyslowly(perhapswhentesting).
The load switches on when nobody is present:
• Heatercausinginfra-redvariationsinasmallcoldroom.
Reducethesensitivityadjusterorre-sitetheWACEPIR.
• PleasecontactDANLERSforfurthertechnicalsupport.
Fault nding