© DICTATOR TECHNIK GMBH • Gutenbergstr. 9 • D - 86356 Neusäß • Germany
Tel. (0821)24673 - 0 • Fax (0821) 24673 - 90 • E-Mail info@dictator.de • 0052 Page 05.041.00
Semi-automatic Fire Protection
Sliding Door Drives
DICTAMAT 650
2
2
2
L2 -R
L1 in
spareL1
out
L2 -R
L1 in
spareL1
out
L2 -R
L1 in
spareL1
out
24VDC
230 VAC
50Hz
_
+
_
+
24VDC
230VAC
40
80
120
160
012345678910111213
[n]
N
0 0,6 1,3 1,9 2,5 3,2 3,8 4,4 5,0 5,7 6,3
[m]
After the door drive unit has been
installed the integrated electromagnet of
the drive unit and the hand release switch
need to be connected to the RM 3000
smoke detectors (see diagram).
Once the motor and idler pulley are in
place, the rope tensioner, with its fixing
bracket, need to be fixed to the door.
Make sure the rope runs exactly parallel
to the rail. It is fixed with its lower part to
the rope tensioner. Make sure that the
drive unit opens in the same direction as
the door. It is also possible to use the
DICTAMAT 650 for the opposite opening direction by connecting the upper half of
the rope to the rope tensioner.
We recommend you put the rope in place when the door is completely closed. Once all
components have been properly aligned and fixed the rope needs to be tensioned. To make
sure the force of the spring is sufficient to close the door completely, open the door
slightly. The closing force is increased by turning the tensioning screw in the direction
indicated by the arrow. Turning in the opposite direction will reduce the force.
DICTAMAT 650
Economic drive unit for closing fire protection sliding doors
Due to its compact design the DICTAMAT 650 is very easy to install. The door is kept
open in the desired position by the integrated electromagnet until the power supply is
interrupted by the smoke detector or the hand switch. Please use a push-to-lock key
(part no. 700 132) to make sure the door closes completely.
When the spring closes the door the closing speed is controlled by the magnetic
brake system.
Move the door to the OPEN position and adjust the closing speed while the door is
closing. This is achieved by lifting the locking spring and turning the adjustment ring
(see diagram on preceding page). Turning it clockwise will reduce the closing speed.
Please observe the relevant safety regulations of your country.
The force acting on an obstacle must not exceed 150 N
This can be achieved by a slower closing speed and by installing additional dampers in
the final positions (e.g. DICTATOR EDH damper). If the operating equipment is lower than
3m, the covers on the drive unit pulley and the idler pulley must not be removed to
avoid trapped fingers in the workings of the equipment.
Installing Rope Tensioner
with Fixing Bracket
Electrical Connection
Installing Steel Rope
Force of Closing Spring
Adjustment
Hand Release Switch
Power Pack
DICTAMAT 650
RM 3000 Smoke Detectors
Pretension