DINUY S.A. c/Auzolan 2, 20303 Irun (SPAIN)
Tel.: +34 943627988 – E-mail: knx@dinuy.com – Web: www.dinuy.com 9
Sets the 'Constant Light Control Enable' object behavior after a power failure of the Bus.
After recovering the bus can be enabled or not to consult the state of this object.
Origin of light sensor
Is necessary to select if the light sensor is internal (built-in sensor) or external (a separate sensor):
•External: Enables the object 'External sensor value' in order to receive the value of an external light sensor. In
addition, it must selected whether the set point is parameterized by the ETS ('Origin of Requested lux level = Via ETS
parameter’) or via the communication object ‘Lux Level Requested’ ('Origin of Requested lux level = Via
communication object').
In case of choosing the parameterization by ETS, it must entered the value of lux to keep through 'Lux Level
Requested' parameter. Can be set values between 100 lux and 1200 lux, in steps of 100.
•Built-in: four new parameters will be enabled in Advanced Settings (access to these settings only if really necessary):
•It is necessary to measure with a light meter in the sensor:
oAt night only with lamps (lux): lighting value measured in the sensor (ceiling) without daylight contribution
and the lamps regulated to obtain the desired lighting in workplace.
oAt max. external light and lamps regulated to have requested level (lux): lighting value measured in the
sensor (ceiling) to the maximum value of daylight and the lamps regulated to obtain the desired value of
lighting in the workplace.
•The adjustment of the lamps is:
oAt night only with lamps (%): light level at which the lamps are regulated at night with only the lamps only.
oAt max. external light and lamps regulated to have requested level (%): level at which lamps are regulated
with maximum daylight and lamps to the desired level.
Constant light control
Allows conditioning the constant light control to the motion detection or to a communication object:
•Only when movement detected: The dimming will become operational only when motion is detected. If people is not
present, the system will send an OFF (or whatever programmed) through the Bus after the set time delay ('Lag time').
•Always: the constant light control will operate every time, regardless of whether or not presence of people. The
turning-on or turning-off of the lights can be made by a higher-level object.
•Depending object mode value: in case of selecting this option is enabled other communication object No. 10
'Permanent Constant light control', which allows to control remotely the system commissioning.
Enable Object for manual dimming
Allows enabling the dimming and manual switching from an external sensor (pushbutton, switch,...).
Enabled Object:
Constant light object number
Allows to control several lighting lines (up to 4) with an adjustable percentage of increase: ‘2nd constant light object
attenuation’.
Enabled Object: