E2S D2 C2X05DC024 Series User manual

__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D211-00-601-IS-SC Issue: F 02-03-2020 Sheet 1 of 9
INSTRUCTION & SERVICE MANUAL
D2xC2 ALARM HORN AND STROBE
For Use In Hazardous Locations
1) Warnings
DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
DO NOT OPEN WHEN ENERGISED
POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
HIGH VOLTAGE SHOCK HAZARD. WAIT 5
MINUTES AFTER REMOVING POWER
BEFORE OPENING THE ENCLOSURE
DO NOT PAINT
Avertissement:
NE PAS OUVRIR UN PRESENCE
D’ATMOSPHERE EXPLOSIVE
NE PAS OUVRIR ENERGIE
DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
HAUT TENSION, RISK DE CHOC. ATTENDEZ
5 MINUTES APRES AVOIR DEBRANCHE
L’ALIMENTATION AVANT D’OUVRIR LA
BOITIER
NE PAS PEINTURER
2) Rating & Marking Information
2.1 Fire Alarm Ratings
The Following models are certified for use an Audible &
Visual Appliance for use in Fire Alarm Systems Private Mode
in accordance with UL464 Tenth Edition & UL1638 Fifth
Edition.
D2xC2X05DC024
D2xC2X10DC024
On-axis light output per UL1638 at 1Hz:
Model Lens cover colour Light output in cd
D2xC2X05DC024 clear 17.4
red 5.4
D2xC2X10DC024 clear 53.4
red 17.4
For Fire Alarm applications, the Sounder Volume must be at
the highest setting, (see volume control section).
The sounder section produces a sound pressure level above
75dB(A) at 10 feet.
For fire alarm use, the temporal pattern tone No. 12 as per the
tone table provided in these instructions must be selected. This
tone produces a minimum sound pressure level of:
CAN/ULC-S525: 100.4dB(A)* at 10 feet.
(*anechoic room)
UL464: 92.2dB(A)†at 10 feet.
(†reverberation room)
2.2 surge current ratings for use in fire alarm systems
Model Peak Surge
current RMS surge current
Beacon Sounder Beacon Sounder
D2xC2X05DC024 1.04A 3.18A 437mA 1.3A
D2xC2X10DC024 0.99A 3.18A 620mA 1.3A
2.3 NEC & CEC Class / Division Ratings for US / Canada
The D2xC2 combined sounder beacon complies with the
following standards:
ANSI/ISA 12.12.01-2015
CSA C22.2 No. 213-16
The D2xC2X05DC024 Combined unit is rated as follows:
Class I Div 2 ABCD T3 Ta -40°C to +50°C
Class II Div 2 FG T6 Ta -40°C to +50°C
Class III Div 1&2 Ta -40°C to +50°C
The D2xC2X10DC024 Combined unit is rated as follows:
Class I Div 2 ABCD T2A Ta -40°C to +50°C
Class II Div 2 FG T6 Ta -40°C to +50°C
Class III Div 1&2 Ta -40°C to +50°C
The D2xC2X05DC048 & D2xC2X05AC Combined units are
rated as follows:
Class I Div 2 ABCD T3 Ta -40°C to +50°C
Class II Div 2 FG T5 Ta -40°C to +50°C
Class II Div 2 FG T6 Ta -40°C to +40°C
Class III Div 1&2 Ta -40°C to +50°C
The D2xC2X10DC048 & D2xC2X10AC Combined units are
rated as follows:
Class I Div 2 ABCD T2B Ta -40°C to +50°C
Class II Div 2 FG T5 Ta -40°C to +50°C
Class II Div 2 FG T6 Ta -40°C to +40°C
Class III Div 1&2 Ta -40°C to +50°C
Installation must be carried out in compliance with the National
Electric Code / Canadian Electric Code
2.4 NEC Class / Zone ratings US
The D2xC2X05 and D2xC2X10 Xenon beacons comply with the
following standards:
UL 60079-0-2013
UL 60079-15-2013
UL 60079-31-2015
The D2xC2X05DC024 Combined unit is rated as follows:
Class I Zone 2 AEx nA IIC T3 Gc Ta -40°C to +50°C
Zone 22 AEx tc IIIC 75°C Dc Ta -40°C to +50°C

__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D211-00-601-IS-SC Issue: F 02-03-2020 Sheet 2 of 9
The D2xC2X10DC024 Combined unit is rated as follows:
Class I Zone 2 AEx nA IIC T2 Gc Ta -40°C to +50°C
Zone 22 AEx tc IIIC 85°C Dc Ta -40°C to +50°C
The D2xC2X05DC048 & D2xC2X05AC Combined units are
rated as follows:
Class I Zone 2 AEx nA IIC T3 Gc Ta -40°C to +50°C
Zone 22 AEx tc IIIC 95°C Dc Ta -40°C to +50°C
The D2xC2X10DC048 & D2xC2X10AC Combined units are
rated as follows:
Class I Zone 2 AEx nA IIC T2 Gc Ta -40°C to +50°C
Zone 22 AEx tc IIIC 95°C Dc Ta -40°C to +50°C
Installation must be carried out in compliance with the
National Electric Code.
2.5 CEC Class / Zone ratings Canada
The D2xS1 alarm horn complies with the following standards:
CAN/CSA C22.2 No. 60079-0:2015
CAN/CSA C22.2 No. 60079-15:2016
CAN/CSA C22.2 No. 60079-31:2015
The D2xC2X05DC024 Combined unit is rated as follows:
Ex nA IIC T3 Gc X Ta -40°C to +50°C
Ex tc IIIC 75°C Dc Ta -40°C to +50°C
The D2xC2X10DC024 Combined unit is rated as follows:
Ex nA IIC T2 Gc X Ta -40°C to +50°C
Ex tc IIIC 85°C Dc Ta -40°C to +50°C
The D2xC2X05DC048 & D2xC2X05AC Combined units are
rated as follows:
Ex nA IIC T3 Gc X Ta -40°C to +50°C
Ex tc IIIC 95°C Dc X Ta -40°C to +50°C
The D2xC2X10DC048 & D2xC2X10AC Combined units are
rated as follows:
Ex nA IIC T2 Gc X Ta -40°C to +50°C
Ex tc IIIC 95°C Dc X Ta -40°C to +50°C
Installation must be carried out in compliance with the
Canadian Electric Code
2.6 ATEX / IECEx certification
The D2xC2X05 and D2xC2X10 Combined alarm horn and
xenon beacon comply with the following standards:
EN60079-0:2012+A11:2013 / IEC60079-0: ed. 6.0 (2011-06)
EN60079-15:2010 / IEC60079-15: ed. 4.0 (2010-01)
EN60079-31:2014 / IEC60079-31:2013 ed. 2.0 (2013-11)
Certificate No. DEMKO 14 ATEX 4786493904X
IECEx ULD 14.0004X
The D2xC2X05DC024 Combined unit is rated as follows:
The D2xC2X10DC024 Combined unit is rated as follows:
The D2xC2X05DC048 & D2xC2X05AC Combined units are
rated as follows:
The D2xC2X10DC048 & D2xC2X10AC Combined units are
rated as follows:
CE Marking
Zones, Gas / Dust Groups and Temperature Classification
When connected to an approved system the D2X alarm horn
may be installed in:
Zone 2 explosive gas air mixture not likely to occur in
normal operation, and if it does, it will only exist for a
short time.
Zone 22 explosive dust air mixture not likely to occur in
normal operation, and if it does, it will only exist for a
short time.
May be used with gases in groups:
Group IIA propane
Group IIB ethylene
Group IIC hydrogen / acetylene
Having a temperature classification
(for Gas applications) of:
T1 450ºC
T2 300ºC
T3 200ºC (D2xC2X05 only)
May be used with Dust types:
Group IIIA combustible flyings
Group IIIB non-conductive dust
Group IIIC conductive dust
Maximum Surface Temperature for Dust Applications:
D2xC2X05DC024 = 75°C
D2xC2X10DC024 = 85°C
All 48VDC, 115VAC & 230VAC units = 95°C
Installation must be carried out in compliance with the latest
issue of the following standards:
EN60079-14 / IEC60079-14: Explosive atmospheres - Electrical
installations design, selection and erection
EN60079-10-1 / IEC60079-10-1: Explosive atmospheres -
Classification of areas. Explosive gas atmospheres
EN60079-10-2 / IEC60079-10-2: Explosive atmospheres –
Classification of areas. Explosive dust atmospheres
2.7 Ingress Protection Ratings
The product is rated for ingress Protection as follows:
IP rating: IP66
Type rating per UL50E / NEMA250: 4 / 4X / 3R / 13
To maintain the ingress protection rating, the two off cable
entries must be fitted with suitably rated, certified cable entry
and/or blanking devices during installation.
2813
II 3G Ex nA IIC T3 Gc Ta -40°C to +50°C
II 3D Ex tc IIIC 95°C Dc Ta -40°C to +50°C
II 3G Ex nA IIC T2 Gc Ta -40°C to +50°C
II 3D Ex tc IIIC 95°C Dc Ta -40°C to +50°C
II 3G Ex nA IIC T3 Gc Ta -40°C to +50°C
II 3D Ex tc IIIC 75°C Dc Ta -40°C to +50°C
II 3G Ex nA IIC T2 Gc Ta -40°C to +50°C
II 3D Ex tc IIIC 85°C Dc Ta -40°C to +50°C

__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D211-00-601-IS-SC Issue: F 02-03-2020 Sheet 3 of 9
147,0mm [5,73in.]
116,0mm [4,52in.]
213,3mm [8,32in.]
165,6mm [6,46in.]
9,7mm [0,38in.]
6,7mm [0,26in.]
Ø6,9mm [Ø0,27in.]
310,3mm [12,10in.]
125,0mm [4,88in.]
179,2mm [6,99in.]
Beacon
Cover
M4 Screws
(4-off)
Sounder
Cover
M4
Screws
(
4-off
)
2.8 Electrical Ratings
It is important that a suitable power supply is used to run the
equipment. The power supply selected must have the
necessary capacity to provide the input current to all the units.
The input current will vary according to the voltage input level.
The current levels shown above are for the worst-case input
voltage and flash setting resulting in max. current.
Part No. Nominal
Voltage
Beacon
Current
Sounder
Current
D2xC2X05DC024 20-28Vdc 296mA 313mA
D2xC2X05DC048 48Vdc 145mA 181mA
D2xC2X05AC115 115-120Vac
50/60Hz 80mA 89mA
D2xC2X05AC230 220-230Vac
50/60Hz 30mA 52mA
D2xC2X10DC024 20-28Vdc 609mA 313mA
D2xC2X10DC048 48Vdc 260mA 181mA
D2xC2X10AC115 115-120Vac
50/60Hz 185mA 89mA
D2xC2X10AC230 220-230Vac
50/60Hz 107mA 52mA
3) Special Conditions for Safe Use
Special Condition for safe Use as stated on the Type
Examination Certificate DEMKO 14 ATEX 4786493904X /
CoC IECEx ULD 14.0004X:
When used for a Group III application, the surface of the
enclosure may store electrostatic charge and become a
source of ignition in applications with a low relative humidity
<~30% relative humidity where the surface is relatively free of
surface contamination such as dirt, dust, or oil.
Guidance on protection against the risk of ignition due to
electrostatic discharge can be found in EN TR50404 and IEC
TR60079-32.
End user shall adhere to the manufacturer’s installation and
instruction when performing housekeeping to avoid the
potential for hazardous electrostatic charges during cleaning,
by using a damp cloth.
To maintain the ingress protection rating and mode of
protection, the cable entries must be fitted with suitably rated,
certified cable entry and/or blanking devices during
installation. If conduit is used for installation, seal conduit
within 18 inches from the enclosure.
4) Location and Mounting
The location of the combined alarm horn and beacon should
be made with due regard to the area over which the warning
signal must be visible and audible. It should only be fixed to
services that can carry the weight of the unit.
DxC2 Alarm Horn and Strobe to a flat surface via the two 9.7
x 6.7mm, 147mm pitch fixing holes in the mounting feet of the
sounder section and the two 7mm fixing holes in the feet of
the base.
The equipment is not to be mounted with the horn facing
upwards.
Fig. 1 Fixing locations.
5) Access to the Enclosure
To access the enclosures, loosen the four M4 posi pan head
screws for beacon and/or the four M4 posi pan head screws for
the sounder and withdraw the cover/s.
Fig. 2 Accessing Enclosures.
To replace cover, check that the ‘O’ ring seal is in place.
Carefully push the cover in place. Insert M4 screws with fiber
washers and tighten to 3Nm torque.
6) Selection of Cable, Cable Glands, Blanking
Elements & Adapters
When selecting the cable size, consideration must be given to
the input current that each unit draws (see Table 1), the number
of beacons on the line and the length of the cable runs. The
cable size selected must have the necessary capacity to provide
the input current to all of the sounders connected to the line.
If a high IP (Ingress Protection) rating is required then a suitable
sealing washer must be fitted under the cable glands or
blanking plugs.
For use in explosive dust atmospheres, a minimum ingress
protection rating of IP6X must be maintained.
Warning – High voltage may be present,
risk of electric shock. DO NOT open when
energised, disconnect power before
opening.
Warning – Hot surfaces. External surfaces
and internal components may be hot after
operation, take care when handling the
equipment.

__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D211-00-601-IS-SC Issue: F 02-03-2020 Sheet 4 of 9
S2
S3
L
N
E
C
STAGE 4 = S2 + S3
(Customer
Supplied Switches
)
STAGE 4 = S2 + S3
(Customer
Supplied Switches
)
STAGE 4 = S2 + S3
(Customer
Supplied Switches)
For use in explosive gas atmospheres, a minimum ingress
protection rating of IP54 must be maintained.
NPT stopping plugs should be greased before insertion.
7) Cable Connections
Electrical connections are to be made into the terminal blocks
on the PCBA located in the enclosure. See section 5 of this
manual for access to the enclosure.
Wires having a cross sectional area between 0.5 mm² to
2.5mm² can be connected to each terminal way. If an
input and output wire is required the 2-off Live/Neutral or
+/- terminals can be used. If fitting 2-off wires to one
terminal way the sum of the 2-off wires must be a
maximum cross sectional area of 2.5mm². Strip wires to
8mm. Wires may also be fitted using ferrules. Terminal
screws need to be tightened down with a tightening
torque of 0.56 Nm / 5 Lb-in. When connecting wires to
the terminals great care should be taken to dress the
wires so that when the cover is inserted into the chamber
the wires do not exert excess pressure on the terminal
blocks. This is particularly important when using cables
with large cross sectional areas such as 2.5mm².
8) AC Wiring
8.1 Wiring Diagram
Fig 3a. AC Simplified Block Diagram, powering
sounder and beacon simultaneously
L
N
CS2
NLLL N N S3
C
LL NN
S2
S3
CS2
NLLL N N S3 LL NN
L
N
Fig 3b. AC Simplified Block Diagram, powering
sounder and beacon independent
8.2 Unit’s First Stage Tones
Stage one (S1) operation: Simply connect the supply voltage
to the L and N supply terminals, (see fig. 3). The Strobe is
powered via factory installed wires connected to the sounder.
The wires connecting the alarm horn and strobe can be
removed if the user wishes to power the strobe separately.
8.3 Second, Third and Fourth Stage Tone Selection
To select the second, third and fourth stage tones on the D2xS1
AC alarm horns.
Stage two (S2) operation: Power L and N, link the common (C)
and S2 terminal.
Stage three (S3) operation: Power L and N, link the common (C)
and S3 terminals.
Stage four (S4) operation: Power L and N, link the common (C)
and both the S2 and S3 terminals.
Strobe will continue to flash during alarm horn S2, S3 & S4
stages.
9) DC Wiring
Fig. 5a DC Simplified Block Diagram, powering
sounder and beacon simultaneously
LL NN EE
L
N
CS2
NLLL N N S3
C
LL NN
S2
S3
CS2
NLLL N N S3 LL NN
+
-
S2
-+++- - S3
S2
S3
--++ S2
-+++- - S3 --++
Fig. 4 AC Terminals

__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D211-00-601-IS-SC Issue: F 02-03-2020 Sheet 5 of 9
- +
+
-
S2
-+++- - S3
S2
S3
--++ S2
-+++- - S3 --++
+
-
DC Sounder Terminals
10 -15mm
4 - 7mm
10 -15mm
5 - 10mm
Fig. 5b DC Simplified Block Diagram, powering
sounder and beacon independently
9.1 Units First Stage Tones
Stage one (S1) operation: Simply connect the supply voltage
to the + and - supply terminals, (see fig. 8). The Strobe is
powered via factory installed wires connected to the alarm
horn. The wires connecting the alarm horn and strobe can be
removed if the user wishes to power the strobe separately.
9.2 Second, Third and Fourth Stage Tone Selection
Stage two (S2) operation: Power +ve and –ve, link a -ve
supply line to the S2 terminal.
Stage three (S3) operation: Power +ve and –ve, link a -ve
supply line to the S3 terminal.
Stage four (S4) operation: Power +ve and –ve, link a -ve
supply line to both the S2 & S3 terminals.
Strobe will continue to flash during alarm horn S2, S3 & S4
stages.
S2
S3
+
-
E
24VDC Strobe Terminals 48VDC Strobe Terminals
Fig. 6b DC Terminals
10) Earthing
The unit has both internal and external earth terminals, (please
see fig 3).
Internal earthing connections should be made to the internal
earth terminal on the PCBA, (please see fig 4 for AC, fig 6 for
DC). The earth conductor should be at least equal in size and
rating to the incoming power conductors. The internal earth
bonding wire connects the PCBA earth terminal to the internal
earth terminal in the enclosure back box.
External earth connections should be made to the M5 earth
stud, using a ring crimp terminal to secure the earth conductor
to the earth stud. The external earth conductor should be at
least 4mm2in size. The external earth crimp ring should be
located between the two M5 plain washers provided and
securely locked down with the M5 spring washer and M5 nut.
11) End Of Line Monitoring (DC Units Only)
On D2xC2 DC units, dc reverse line monitoring can be used if
required. All DC units have a blocking diode fitted in their supply
input lines. An end of line monitoring resistor can be connected
across the +ve and –ve terminals. If an end of line resistor is
used it must have the following values:-
24V DC Alarm Horn and Strobe
Minimum Resistance 3k9 ohms Minimum wattage 0.5W
Minimum Resistance 1k ohms Minimum wattage 2.0W
48V DC Alarm Horn and Strobe
Minimum Resistance 15k ohms Minimum wattage 0.5W
Minimum Resistance 3k9 ohms Minimum wattage 2.0W
The resistor must be connected directly across the +ve and
-ve terminals as shown in the following drawing. Form the
resistor legs as shown in Fig. 7, remove the +ve and –ve
terminal plugs and fit the resistor across the two terminal plugs
before refitting them to the PCBA as shown in Fig. 8a or 8b. A
spacing of at least 1/16” (1.58mm) must be provided through air
and over surfaces between uninsulated live parts.
Sounder EOL Resistor Beacon EOL Resistor
Fig. 7 End of Line Resistor Forming
Fig. 8a 48VDC Beacon End of Line Resistor Placement
End of Line Resistor
- - + + E E - - + + E E

__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D211-00-601-IS-SC Issue: F 02-03-2020 Sheet 6 of 9
Fig. 8b 24VDC Beacon End of Line Resistor
Placement
Fig. 9 Sounder End Of Line Resistor Placement
12) Settings
12.1 Volume Control
The alarm horn output level of the DxC2 unit can be set by
adjusting the volume control potentiometer (see Fig 10). For
maximum output, set the potentiometer fully clockwise.
Fig. 10 Location of field controls
12.2 Tone Selection
.
The DxC2 alarm horns have 64 different tones. The tones are
selected by operation of the tone setting DIP switches (see
Fig. 10) on the PCB. The alarm horns can also be switched to
sound the second, third and fourth stage alarm tones. The
tone table (Table 1) shows the switch positions for the 64 tone
and which tones are available for the second, third and fourth
stages.
13) Interchangeable & Spare Parts
The Beacon lens cover is interchangeable, contact E2S Ltd for
a replacement lens cover available in various colours.
To change the lens cover, unscrew the 4-off M5 posi pan head
screws, spring and flat washers using a screwdriver. Remove
the wire guard and replace the old lens cover with the new lens
cover.
Fig. 11 Replacement of beacon lens cover
Fit the wire guard back onto the housing, over the new lens
cover aligning the fixing holes of the guard, lens cover and
housing. Refit the fixings to hold into place, the fixings MUST be
fitted in the order shown above.
14) DIP Switch
Please note that the D2xC2X05DC024 & D2xC2X10DC024
beacon PCBAs have a DIP Switch that is NOT customer
configurable. This should only ever be set to ‘00’.
Fig. 7 DIP Switch setting ‘00’
15) Maintenance, Overhaul & Repair
Maintenance, repair and overhaul of the equipment should only
be carried out by suitably qualified personnel in accordance with
the current relevant standards:
EN60079-19
IEC60079-19
Explosive atmospheres - Equipment repair,
overhaul and reclamation
EN 60079-17
IEC60079-17
Explosive atmospheres - Electrical
installations inspection and maintenance
To avoid a possible ELECTROSTACTIC CHARGE the unit must
only be cleaned with a damp cloth.
Units must not be opened while an explosive atmosphere is
present.
If opening the unit during maintenance operations a clean
environment must be maintained and any dust layer removed
prior to opening the unit.
Warning – Hot surfaces. External surfaces
and internal components may be hot after
operation, take care when handling the
equipment.
Volume
Control Tone Setting
Switches 1-6
(See tone
selection table
)
M5 screw
M5 spring washer
M5 flat washer
EOL
Resistor

__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D211-00-601-IS-SC Issue: F 02-03-2020 Sheet 7 of 9
16) Sound Directional Characteristics for Canadian Fire CAN/ULC-S525
Horizontal Axis
Vertical Axis
An
g
le OSPL An
g
le OSPL
Reference
(
90°
)
101.2 dB
(
A
)
Reference
(
90°
)
101.2 dB
(
A
)
115° -3 dB
(
A
)
68° -3 dB
(
A
)
129° -6 dB
(
A
)
55° -6 dB
(
A
)
180° 92.4 dB
(
A
)
0° 92.4 dB
(
A
)
An
g
le OSPL An
g
le OSPL
Reference
(
90°
)
101.5 dB
(
A
)
Reference
(
90°
)
101.5 dB
(
A
)
123° -3 dB
(
A
)
65° -3 dB
(
A
)
137° -6 dB
(
A
)
50° -6 dB
(
A
)
180° 91 dB
(
A
)
0° 88.5 dB
(
A
)

__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D211-00-601-IS Issue: F 02-03-2020 Sheet 8 of 9
1600Hz
1400Hz 1s
0.5s
17) Tone Table
Tone Selection – To select the required first stage tone set the tone switches 1 to 6 (see Fig 10) to the tone setting shown in the table below. The table also shows
which 2nd, 3rd and 4th stage tones are available for use with the selected first stage tone if more than one tone output stage is required.
Stage 1
Tone No Tone Description Tone Visual Switch Settings
1 2 3 4 5 6
Stage 2
Tone
(S2)
Stage 3
Tone
(S3)
Stage 4
Tone
(S2 + S3)
1 1000Hz PFEER Toxic Gas 0 0 0 0 0 0 3 2 44
2 1200/500Hz @ 1Hz DIN /
PFEER P.T.A.P. 1 0 0 0 0 0 1 3 44
3 1000Hz @ 0.5Hz(1s on, 1s
off) PFEER Gen. Alarm 0 1 0 0 0 0 1 2 44
4 1.4KHz-1.6KHz 1s, 1.6KHz-
1.4KHz 0.5s NF C 48-265 1 1 0 0 0 0 44 24 1
5 544Hz(100mS)/440Hz
(400mS) NF S 32-001 0 0 1 0 0 0 52 19 1
6 1500/500Hz - (0.5s on , 0.5s
off) x3 + 1s gap AS4428 1 0 1 0 0 0 7 44 1
7 500-1500Hz Sweeping 2 sec
on 1 sec off AS4428 0 1 1 0 0 0 6 44 1
8
500/1200Hz @ 0.26Hz(3.3s
on, 0.5s off) Netherlands -
NEN 2575
1 1 1 0 0 0 44 24 35
9 1000Hz (1s on, 1s off)x7 + (7s
on, 1s off) IMO Code 1a
0 0 0 1 0 0 18 34 1
10 1000Hz (1s on, 1s off)x7 + (7s
on, 1s off
)
IMO Code 1a 1 0 0 1 0 0 21 34 1
11
420Hz(0.5s on, 0.5s off)x3 +
1s gap ISO 8201 Temporal
Pattern
0 1 0 1 0 0 44 1 8
12
1000Hz(0.5s on, 0.5s off)x3 +
1s gap ISO 8201 Temporal
Pattern
1 1 0 1 0 0 44 1 8
13
422/775Hz - (0.85 on, 0.5
off) x3 + 1s gap NFPA -
Temporal Coded
0 0 1 1 0 0 44 1 8
14 1000/2000Hz @ 1Hz
Sin
g
apore 1 0 1 1 0 0 23 3 35
15 300Hz Continuous 0 1 1 1 0 0 44 24 35
16 440Hz Continuous 1 1 1 1 0 0 44 24 35
17 470Hz Continuous 0 0 0 0 1 0 44 24 35
18 500Hz Continuous IMO code
2
(
Low
)
1 0 0 0 1 0 44 24 35
19 554Hz Continuous 0 1 0 0 1 0 64 24 35
20 660Hz Continuous 1 1 0 0 1 0 44 24 35
21 800Hz IMO code 2 (High) 0 0 1 0 1 0 44 24 35
22 1200Hz Continuous 1 0 1 0 1 0 44 24 35
23 2000Hz Continuous 0 1 1 0 1 0 15 3 35
24 2400Hz Continuous 1 1 1 0 1 0 48 20 35
25 440 @0.83Hz (50
c
y
cles/minute
)
Intermittent 0 0 0 1 1 0 1 44 8
26 470 @0.9Hz - 1.1s
Intermittent 1 0 0 1 1 0 1 44 8
27 470Hz @5Hz - (5
cycles/second) Intermittent 0 1 0 1 1 0 1 44 8
28 544Hz @ 1.14Hz - 0.875s
Intermittent 1 1 0 1 1 0 44 24 8
29 655Hz @ 0.875Hz
Intermittent 0 0 1 1 1 0 1 44 8
30 660Hz @0.28Hz - 1.8sec on,
1.8sec off Intermittent 1 0 1 1 1 0 44 24 8
31 660Hz @3.34Hz - 150mS on,
150mS off Intermittent 0 1 1 1 1 0 30 24 8
1000Hz
1000Hz 1s
1s
544Hz
440Hz
0.1s
0.4s
1500Hz
500Hz 0.5s 0.5s 1.5s
0.5s 0.5s 0.5s
1500Hz
500Hz 2s 1s
1200Hz
500Hz 3.3s 0.5s
1s 1s 1s 7s
7s
1s 1s 1s 1s 1s 1s 1s
1000Hz 1s 1s 1s 1s
0.5s
0.5s
0.5s
1.5s
420Hz 0.5s
0.5s
1000Hz 0.5s
0.5s
0.5s
0.5s
0.5s
1.5s
775Hz
422Hz 0.85s 0.5s 0.85s 0.5s 0.85s 1.5s
2000Hz
1000Hz 1s
300Hz
440Hz
470Hz
500Hz
554Hz
660Hz
800Hz
1200Hz
2000Hz
2400Hz
440Hz 0.6s
0.6s
470Hz 0.55s
0.55s
470Hz 0.1s
0.1s
470Hz 0.43s
0.44s
655Hz 0.57s
0.57s
660Hz 1.8s
1.8s
660Hz 0.15s
0.15s
500Hz 1s
1200Hz

__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH [email protected] Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D211-00-601-IS-SC Issue: F 02-03-2020 Sheet 9 of 9
32 745Hz @ 1Hz Intermittent 1 1 1 1 1 0 44 24 8
33 800Hz - 0.25sec on, 1 sec off
Intermittent 0 0 0 0 0 1 53 24 8
34 800Hz @ 2Hz IMO code 3.a
(High) Intermittent 1 0 0 0 0 1 56 24 8
35 1000Hz @ 1Hz Intermittent 0 1 0 0 0 1 44 24 8
36 2400Hz
@
1Hz Intermittent 1 1 0 0 0 1 21 24 8
37 2900Hz @ 5Hz Intermittent 0 0 1 0 0 1 53 24 8
38 363/518Hz
@
1Hz Alternatin
g
1 0 1 0 0 1 1 8 19
39 450/500Hz @ 2Hz Alternating 0 1 1 0 0 1 1 8 19
40 554/440Hz
@
1Hz Alternatin
g
1 1 1 0 0 1 44 24 19
41 554/440Hz @ 0.625Hz
Alternating 0 0 0 1 0 1 1 8 19
42 561/760Hz @0.83Hz (50
c
y
cles/minute
)
Alternatin
g
1 0 0 1 0 1 1 8 19
43 780/600Hz @ 0.96Hz
Alternating 0 1 0 1 0 1 1 8 19
44 800/1000Hz @ 2Hz
Alternating 1 1 0 1 0 1 5 24 19
45 970/800Hz
@
2Hz Alternatin
g
0 0 1 1 0 1 1 8 19
46 800/1000Hz @ 0.875Hz
Alternating 1 0 1 1 0 1 53 24 19
47 2400/2900Hz @ 2Hz
Alternatin
g
0 1 1 1 0 1 57 24 19
48 500/1200Hz @ 0.3Hz
Sweeping 1 1 1 1 0 1 44 24 12
49 560/1055Hz @ 0.18Hz
Sweepin
g
0 0 0 0 1 1 44 24 12
50 560/1055Hz @ 3.3Hz
Sweeping 1 0 0 0 1 1 44 24 12
51 600/1250Hz @ 0.125Hz
Sweepin
g
0 1 0 0 1 1 44 24 12
52 660/1200Hz @ 1Hz
Sweeping 1 1 0 0 1 1 64 24 12
53 800/1000Hz
@
1Hz Sweepin
g
0 0 1 0 1 1 56 24 12
54 800/1000Hz
@
7Hz Sweepin
g
1 0 1 0 1 1 57 24 12
55 800/1000Hz @ 50Hz
Sweeping 0 1 1 0 1 1 54 24 12
56 2400/2900Hz @ 7Hz
Sweepin
g
1 1 1 0 1 1 57 24 12
57 2400/2900Hz @ 1Hz
Sweeping 0 0 0 1 1 1 47 24 12
58 2400/2900Hz @ 50Hz
Sweepin
g
1 0 0 1 1 1 54 24 12
59 2500/3000Hz @ 2Hz
Sweeping 0 1 0 1 1 1 44 24 12
60 2500/3000Hz @ 7.7Hz
Sweepin
g
1 1 0 1 1 1 44 24 12
61 800Hz Motor Siren 0 0 1 1 1 1 44 24 12
62 1200Hz Motor Siren 1 0 1 1 1 1 44 24 12
63 2400Hz Motor Siren 0 1 1 1 1 1 44 24 12
64 Simulated Bell 1 1 1 1 1 1 44 21 12
745Hz 0.5s
0.5s
800Hz 0.25s
1s
800Hz 0.25s
0.25s
1000Hz 0.5s
0.5s
2400Hz 0.5s
0.5s
2900Hz 0.1s
0.1s
1250Hz
600Hz 8s
1450Hz 0.25s
0.69ms
1200Hz
500Hz 3.34s
1055Hz
560Hz 5.47s
1055Hz
560Hz 0.3s
1200Hz
660Hz 1s
1000Hz
800Hz 1s
1000Hz
800Hz 0.14s
1000Hz
800Hz 0.02s
2900Hz
2400Hz 0.14s
2900Hz
2400Hz 1s
2900Hz
2400Hz 0.02s
3000Hz
2500Hz 0.5s
3000Hz
2500Hz 0.13s
800Hz
1.6s
1200Hz
2s
2400Hz
1.7s
363Hz
518Hz
0.5s
0.5s
500Hz
0.25s
0.25s
450Hz
554Hz
0.5s
0.5s
440Hz
554Hz
0.8s
0.8s
440Hz
760Hz
0.6s
0.6s
561Hz
780Hz 0.52s
0.52s
600Hz
1000Hz
0.25s
0.25s
800Hz
970Hz 0.25s
0.25s
800Hz
2900Hz
0.25s
0.25s
2400Hz
1000Hz
0.57s
0.57s
800Hz
This manual suits for next models
1
Table of contents
Other E2S Security System manuals

E2S
E2S GNExS1FDC024-S User manual

E2S
E2S D2xC2LD2 Series User manual

E2S
E2S Appello A121APPX User manual

E2S
E2S D2xC2LD2 Series User manual

E2S
E2S D1xB2X05-S User manual

E2S
E2S D1xC3 User manual

E2S
E2S SONFL1H-HO Series User manual

E2S
E2S GNExB2LD2 User manual

E2S
E2S STExB2X05-S Series User manual

E2S
E2S SONFL1XDC012 User manual

E2S
E2S STExB2X05DC012 User manual

E2S
E2S D1xS2FDC024-S User manual

E2S
E2S GNExCP6B-PB User manual

E2S
E2S D1xC2 Series User manual

E2S
E2S D1xB2LD2 Series User manual

E2S
E2S BExBG05D-P-SIL User manual

E2S
E2S IS-mA1M User manual

E2S
E2S D2xB1X05 Series User manual

E2S
E2S IS-L101L-R/Y User manual

E2S
E2S BExCBL2-L2D-P User manual