Eldes ESIM364 User manual

COMPLIES WITH EN 50131-1 GRADE 3, CLASS II REQUIREMENTS
ESIM364
GSM ALARM AND MANAGEMENT SYSTEM
USER MANUAL

2
2
EN ESIM364 USER MANUAL V1.6
User Manual v1.6
Valid for ESIM364 v02.13.00 and up
Safety instructions
Please read and follow these safety guidelines in order to maintain safety of operators and people around:
• GSM alarm and management system ESIM364 (also referenced as “alarm system”, “system” or “device”) has radio transceiver operating
in GSM 850/900/1800/1900 bands.
• DO NOT use the system where it can be interfere with other devices and cause any potential danger.
• DO NOT use the system with medical devices.
• DO NOT use the system in hazardous environment.
• DO NOT expose the system to high humidity, chemical environment or mechanical impacts.
• DO NOT attempt to personally repair the system.
• System label is on the bottom side of the device.
GSM alarm system ESIM364 is a device mounted in limited access areas. Any system repairs must be done only by qualied,
safety aware personnel.
The system must be powered by main 16-24V 50/60 Hz ~1.5A max or 18-24V 1,5A max DC power supply which must be ap-
proved by LST EN 60950-1 standard and be easily accessible nearby the device. When connecting the power supply to the
system, switching the pole terminals places does not have any aect.
Any additional devices linked to the system ESIM364 (computer, sensors, relays etc.) must be approved by LST EN 60950-1
standard.
External power supply can be connected to AC mains only inside installation
room with automatic 2-pole circuit breaker capable of disconnecting circuit in
the event of short circuit or over-current condition. Open circuit breaker must
have a gap between connections of more than 3mm (0.12in) and the disconnec-
tion current 5A.
Phase
AC 230V
50HZ/60HZ/DC 24V
USB cable
Null
PE
ESIM364
AC/DC
Mains power and backup battery must be disconnected before any installation or tuning work starts. The system installation
or maintenance must not be done during stormy conditions.
Backup battery must be connected via the connection which in the case of breaking would result in disconnection of one of
battery pole terminals. Special care must be taken when connecting positive and negative battery terminals. Switching the
pole terminals places is NOT allowed.
In order to avoid re or explosion hazards the system must be used only with approved backup battery.
The device is fully turned o by disconnecting 2-pole switch o device of the mains power and disconnecting backup battery
connector.
Fuse F1 type – Slow Blown 3A. Replacement fuses have to be exactly the same as indicated by the manufacturer.
If you use I security class computer for setting the parameters it must be connected to earth.
The WEEE (Waste Electrical and Electronic Equipment) marking on this product (see left) or its documentation indicates that the
product must not be disposed of together with household waste. To prevent possible harm to human health and/or the environ-
ment, the product must be disposed on in an approved and environmentally safe recycling process. For further information on
how to dispose of this product correctly, contact the system supplier, or the local authority responsible for waste disposal in
your area.

3
3
EN
ESIM364 USER MANUAL V1.6
Terms of use
The following terms and conditions govern use of the ESIM364 device and contains important information on limitations regarding the
product’s use and function, as well as information on the limitations of the manufacturer’s liability. Please carefully read these terms and
conditions. For more information on your product, please visit eldesalarms.com
Technical support
In order to ensure continuous and proper operation of the ESIM364 device and uninterrupted service, it is the responsibility of the User to
make sure that: (I) the product is properly installed, and (II) there is constant electrical supply. If you experience diculty during the instal-
lation or subsequent use of the system, you may contact “ELDES, UAB” distributor or dealer in your country/region. For more information
see eldesalarms.com
Warranty procedures
Warranty and out of warranty service should be obtained by contacting the system integrator/dealer/retailer/e-tailer or distributor where
the customer purchased the product. When requesting for service, the proof of purchase and the product serial number must be provided.
The return of the defective product should be strictly through the original route of purchase, and the customers shall pack the product ap-
propriately to prevent the returned product from suering in the transportation.
Manufacturer Warranty
“ELDES, UAB” provides a limited warranty for its products only to the person or entity that originally purchased the product from “ELDES,
UAB” or its authorized distributor or retailer and materials under normal use of the system for a period of twenty four (24) months from the
date of shipment by the “ELDES, UAB” (Warranty Period). Warranty obligations do not cover expandable materials (power elements and/or
batteries), holders and enclosures. The warranty remains valid only if the system is used as intended, following all guidelines outlined in
this manual and in accordance with the operating conditions specied. The warranty is void if the system has been exposed to mechanical
impact, chemicals, high humidity, uids, corrosive and hazardous environments or force majeure factors. If a hardware defect arises and a
valid claim is received within the Warranty Period, at its own discretion, “ELDES, UAB” will either (a) repair a hardware defect at no charge,
using new or refurbished replacement parts, or (b) exchange the product with a product that is new or which has been manufactured from
new or serviceable used parts and is at least functionally equivalent to the original product, or (c) refund the purchase price of the product.
Limited Liability
The buyer must agree that the system will reduce the risk theft, burglary or other dangers but does not provide guarantee against such
events. “ELDES, UAB” will not assume any responsibility regarding personal or property, or revenue loss while using the system. “ELDES,
UAB” shall also assume no liability due to direct or indirect damage or loss, as well as unreceived income when using the system, including
cases, when the damages arise due to the above mentioned risks, when due to breakdown or malfunction the user is not informed in a
timely manner about a risk which has arisen. In any case, the liability of “ELDES, UAB”, as much as it is allowed by the laws in force, shall not
exceed the price of acquisition of the product.
CONSUMER PROTECTION LAWS
FOR CONSUMERS WHO ARE COVERED BY CONSUMER PROTECTION LAWS OR REGULATIONS IN THEIR COUNTRY OF PURCHASE OR, IF
DIFFERENT, THEIR COUNTRY OF RESIDENCE, THE BENEFITS CONFERRED BY THIS WARRANTY ARE IN ADDITION TO ALL RIGHTS
AND REMEDIES CONVEYED BY SUCH CONSUMER PROTECTION LAWS AND REGULATIONS. This warranty grants upon you specic
legal rights, and you may also have other rights that vary by country, state or province.
About User Manual
This document describes basic conguration and usage of alarm system ESIM364. It is very important to read the user manual before start-
ing to use the system.
Contents of Pack
Item Quantity Item Quantity
1. ESIM364.......................... ..................................1
2. Microphone.......................................................1
3. SMA antenna..................... ...............................2
4. Buzzer................................................................1
5. Back-up battery connection wire .................1
6. User manual......................................................1
7. Resistors 5,6kΩ.......... ................................... 12
8. Resistors 3,3kΩ............................................... 6
9. Plastic standos......... .................................... 4
NOTE: For complete system conguration and control, please refer to installation manual at eldesalarms.com/product/esim364

4
4
EN ESIM364 USER MANUAL V1.6
Contents
1. GENERAL INFORMATION .............................................................................................................................................................6
1.1. Short Description of Main Denitions ................................................................................................................................................................. 6
1.2. EKB2 Keypad Overview...........................................................................................................................................................................................7
1.3. EKB3/EKB3W Keypad Overview........................................................................................................................................................................... 8
1.4. Partitions.................................................................................................................................................................................................................. 9
2. BASIC CONFIGURATION AND USE ..............................................................................................................................................10
3. MASTER AND USER CODES.........................................................................................................................................................11
3.1. Managing User and Master Codes...................................................................................................................................................................... 11
3.2. Setting Duress and SGS Codes............................................................................................................................................................................ 12
3.3. Assigning User and Master Code Partition ....................................................................................................................................................... 12
4. SETTING UP DATE AND TIME......................................................................................................................................................13
5. ARMING, DISARMING AND TURNING OFF THE ALARM .............................................................................................................14
5.1. Free of Charge Phone Call.................................................................................................................................................................................... 14
5.2. SMS Text Message ................................................................................................................................................................................................ 15
5.3. EKB2 Keypad and User/Master Code ................................................................................................................................................................ 16
5.4. EKB3 Keypad and User/Master Code................................................................................................................................................................. 18
5.5. EKB3W Keypad and User/Master Code .............................................................................................................................................................20
5.6. iButton Key............................................................................................................................................................................................................. 21
5.7. EWK1/EWK2 Wireless Keyfob............................................................................................................................................................................. 22
6. ARMING IN STAY MODE...............................................................................................................................................................23
7. ALARM INDICATIONS AND NOTIFICATIONS FOR USER. VIEWING VIOLATED ZONES AND TAMPERS ..................................... 24
8. BYPASSING AND ACTIVATING ZONES ........................................................................................................................................25
9. VIEWING SYSTEM INFORMATION...............................................................................................................................................25
9.1. Managing Periodical System Information......................................................................................................................................................... 26
10. VIEWING ZONE AND PGM OUTPUT INFORMATION ..................................................................................................................26
11. SMS TEXT MESSAGE DELIVERY RESTRICTIONS .....................................................................................................................27
11.1. SMSC (Short Message Service Center) Phone Number................................................................................................................................ 27
11.2. SMS Forward ....................................................................................................................................................................................................... 27
12. MANAGING AND VIEWING TEMPERATURE INFORMATION..................................................................................................... 28
13. INDICATION OF SYSTEM FAULTS ..............................................................................................................................................29
14. CONTROLLING ELECTRICAL APPLIANCES ................................................................................................................................31
14.1. Turning ON/OFF the Electrical Appliances Instantly.................................................................................................................................... 31
14.2. Turning ON/OFF the Electrical Appliances for a Determined Time Period............................................................................................... 32
15. POWER CONSUMPTION MONITORING......................................................................................................................................33
16. VIEWING EVENT AND ALARM LOGS .........................................................................................................................................35
16.1. Event Log ............................................................................................................................................................................................................. 35
16.2. Alarm Log............................................................................................................................................................................................................. 35
17. IF THE ALARM SYSTEM IS CONNECTED TO A MONITORING STATION......................................................................................36
18. TECHNICAL SPECIFICATIONS...................................................................................................................................................37
18.1. Electrical and Mechanical Characteristics ..................................................................................................................................................... 37
18.2. Main Unit, LED and Connector Functionality.................................................................................................................................................38
18.3. Wiring Diagrams .................................................................................................................................................................................................39

5
5
EN
ESIM364 USER MANUAL V1.6
It is strictly forbidden to copy and distribute the information contained in this document or to pass thereof to a third party
without an a priori written authorization obtained from “ELDES, UAB”. “ELDES, UAB” reserves the right to update or modify
this document and/or related products without an a priori warning. “ELDES, UAB” hereby declares this GSM alarm and man-
agement system ESIM364 is in compliance with the essential requirements and other relevant provisions of the Directive
1999/5/EC. The declaration of conformity is available at eldesalarms.com
Changes or modications not expressly approved by the party responsible for compliance could void the user’s authority to operate
the equipment.
15.105 statement (for digital devices)
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equip-
ment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may
cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the
equipment o and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit dierent from that to which the receiver is connected.
• Consult the dealer or an experienced radio/ TV technician for help.
The antennas used for this transmitter must be installed to provide a separation distance of at least 20cm from all persons and must
not be located or operating in conjunction with any other antenna or transmitter.
Copyright © “ELDES, UAB“, 2016. All rights reserved.

6
6
EN ESIM364 USER MANUAL V1.6
1. GENERAL INFORMATION
ESIM364 is an alarm system for private houses, cottages, village houses, garages, warehouses and other buildings, also capable of turning
on/o the electrical appliances by SMS text message and alarm system keypad. This alarm system provides a simple thus eective way of use.
The system may consist of:
• ESIM364 alarm system device.
• Up to 4 EKB2/EKB3 wired keypads.
• Up to 4 EKB3W wireless keypads.
• Wired and/or wireless detection devices: movement sensors, magnetic door contacts, smoke sensors etc.
• Other devices: indoor/outdoor sirens, zone/PGM output expansion modules, heating, lighting, gates etc.
For more details on ESIM364 system, please, consult with your alarm system installer.
1.1. Short Description of Main Denitions
The following table provides the explanation of main denitions which are met in this user manual.
Denition Description
System; alarm system ESIM364 device
SMS Short Message Service text
Keypad Device with a set keys allowing to congure and control the system, view violated zones/tampers and
system faults
EKB2 Model of wired LCD keypad
EKB3 Model of wired LED keypad
EKB3W Model of wireless LED keypad
EWM1 Wireless power socket
EWK1 Model of wireless keyfob
EWK2 Model of wireless keyfob
User phone number;
User 1... 10
Phone number of the user allowed to arm/disarm the system control the electrical appliance by SMS text
message as well as to receive notications by SMS text messages from the system
System phone number Phone number of the SIM card inserted in ESIM364 device
User code Multi-digit combination intended for system arming/disarming and viewing system status temperature
and other information using a keypad. The system supports up to 29 user codes.
Master code Multi-digit combination intended for arming/disarming, viewing system status, temperature and other in-
formation as well as for electrical appliance control and minor system conguration using a keypad
iButton key Microchip containing a unique 64-bit ID code intended for system arming/disarming
Zone Alarm system input for wired and wireless sensor connection
PGM output Alarm system output for connection of electrical appliances (heating, lighting, gates etc.)
Partition Section dividing one alarm system into two or more independent parts software-wise

7
7
EN
ESIM364 USER MANUAL V1.6
1.2. EKB2 Keypad Overview
EKB2 is an LCD keypad intended for using with ESIM364 alarm system.
Bypassed
violated zone
(-s)
System
STAY-armed
Fire-type zone
violated
System
fault (-s) is
present
GARAGE
KITCHEN
BEDROOM
CORRIDOR
00:4520,20C
GSM signal
strength
System status
and alarm
indication
Home screen
view
Custom keypad
partition title
Digital clock
Temperature 1
Main Messages & Icons
Icon Description
(by default - disabled) Partition is armed and menu is locked
(by default - disabled) Partition is disarmed and menu is unlocked
Conguration mode activated
Zone or tamper alarm in partition
Partition is ready to be armed.
Partition is not ready to be armed – one or
more zones / tampers violated.
One or more system faults present
One or more violated zones bypassed
One or more partitions STAY-armed
One or more Fire-type zones violated
Alarms in alarm log present
One menu level back / cancel
Menu navigation – up
Menu navigation – down
Conrm (enter) value
Value typing
Minus character to enter negative temp.
value
Additional menu / minus character to
enter negative temp. value
Keys Functionality

8
8
EN ESIM364 USER MANUAL V1.6
EKB2 LCD screen is intended for displaying alarm system status messages and alerts. Icon is displayed on the screen that no zones and/
or tampers are violated and the partition is prepared for arming. Icon shows up in case of zone violation or icon if system faults are
present. The partition cannot be armed until the violated zone (-s) is restored, disabled, bypassed or set up to operate under Force mode or
violated tamper (-s) is restored. By default, the following faults allow partition arming if present:
• mains power is lost.
• low battery.
• battery dead or missing.
• battery failed.
• siren failed.
• date/time not set.
• GSM connection failed.
• GSM/GPRS antenna failed.
• Keypad lost.
Audio Indication
The built-in buzzer uses two types of sound signals – three short beeps and one long beep. Three short beeps stand for successfully carried
out conguration command, one long beep – for invalid conguration command. In addition, the buzzer emits short beeps in case of alarm.
Visual Indication
EKB2 can be used even in dark premises as the LCD screen and keys are illuminated continuously. The illumination level lowers down if 3 min-
utes after the last key-touch expires while the system is disarmed. In case of alarm, the keypad illumination level is boosted and stays in this
state until the system is disarmed.
1.3. EKB3/EKB3W Keypad Overview
EKB3/EKB3W is a LED keypad intended for using with ESIM364 alarm system.
1 2 3
4 5 6
7 8 9
*0 #
2
LED Functionality
Steady ON - alarm system is armed / exit delay in progress; ashing - Conguration mode activated
Steady ON - system is ready – no violated zones and tampers
Steady ON - system faults; ashing - violated high-numbered zones
Steady ON - zone bypass mode
1-12 Steady ON - violated zone
Keys Functionality
Bypass violated zone
System fault list / violated high-numbered zone indication / violated tamper indication
*Clear typed in characters
Conrm (enter) command
0
9
Command typing
4
1Keypad partition switch (only on EKB3) / steady ON - armed partition indication (only on EKB3) / ashing - violated partition
indication (only on EKB3)
1 2 Keypad partition switch (only on EKB3W)
0
Simultaneous 4-partition arming (only on EKB3)
Manual system arming in Stay mode
1st character for Conguration mode activation/deactivation command

9
9
EN
ESIM364 USER MANUAL V1.6
The green indicator indicates that no zones and/or tampers are violated and the system is prepared for arming. Yellow indicator lights
up or ashes in case of zone violation or if system faults are present. The partition cannot be armed until the violated zone (-s) is restored,
disabled, bypassed or set up to operate under Force mode or violated tamper (-s) is restored. By default, the following faults allow partition
arming if present:
• mains power is lost.
• low battery.
• battery dead or missing.
• battery failed.
• siren failed.
• date/time not set.
• GSM connection failed.
• GSM/GPRS antenna failed.
Audio Indication
The built-in buzzer uses two types of sound signals – three short beeps and one long beep. Three short beeps stand for successfully carried
out conguration command, one long beep – for invalid conguration command. In addition, the buzzer emits short beeps in case of alarm.
Visual Indication
EKB3 keys have a LED back-light, therefore it is possible to use this keypad even in dark premises. The back-light lasts for 60 seconds after the last
key-stroke while the system is disarmed. In case of alarm, the keypad back-light turns ON and lasts until the system is disarmed.
EKB3W keys have a LED back-light, which will be activated once any key is pressed. Due to battery power saving reasons, the back-light and
LED light last for 10 seconds after the last key-stroke.
1.4. Partitions
Your alarm system may be partitioned into up to 4 partitions, known as Partition 1 through Partition 4 . Each system partition operates inde-
pendently from each other, therefor partitioning the system allows to use 1 alarm system unit to secure up to 4 dierent areas, for example:
oce and warehouse, house and garage etc. By default, the system is NOT partitioned and all user phone numbers, user codes (except for
master code, which is assigned to all 4 system partitions by default), keypads, iButton keys, zones are assigned to Partition 1.

10
10
EN ESIM364 USER MANUAL V1.6
2.BASIC CONFIGURATION AND USE
ATTENTION: System conguration described in this document is based on the default system parameter values. Your alarm system
installer may have changed those values. For more details, please contact your alarm system installer.
This chapter provides a description of basic conguration and use of ESIM364 alarm system by the following methods:
• SMS text message
• Free of charge phone call
• EKB2 LCD keypad
• EKB3 LED keypad
• EKB3W wireless keypad.
• iButton key
• EWK1 wireless keyfob
• EWK2 wireless keyfob
SMS
In order to congure and control the system using SMS text message, send the text command to the ESIM364 system phone
number from one of the listed user phone numbers. In this user manual the underscore symbol ”_” represents one space char-
acter. Every underscore symbol must be replaced by a single space character. There must be no spaces or other unnecessary
characters at the beginning and at the end of the message. ssss – 4-digit SMS password set by your alarm system installer.
EKB2
The system conguration and control by EKB2 keypad is performed by navigating throughout the menu section list displayed
on LCD screen. To navigate in the menu path, touch ↓, ↑keys to select the desired menu section and touch OK key to open the
selected section. To enter a required value, use 0... 9 keys and touch OK key for value conrmation or cancel/go one menu
section back by touching ↑key. The value can be typed in directly by touching 0... 9 keys while highlighting the desired menu
section. EKB2 menu type is “circle”, therefore when the last section in the menu list is selected, you will be brought back to the
beginning of the list after touching the ↓key. In this user manual, the menu path is provided under “tree” view by starting at
home screen view. In this user manual valid parameter range is indicated in brackets.
EKB3/
EKB3W
The system conguration and control by EKB3/EKB3W keypad is carried out by entering a valid conguration command using
the number keys
0
9
, key for conrmation and *key to cancel the characters that are being entered. Alterna-
tively, the user can wait for 10 seconds until the keypad buzzer will provide a long beep indicating that the entered characters
have been cancelled. When typing in the characters, the indication of each pressed key is provided by short beep of keypad
buzzer. Additionally, the red indicators light up when the number keys
0
9
are being pressed. Some commands require
, and keys as well. The structure of a standard conguration command is a combination of digits. The variables
are provided in lower-case letters, while a valid parameter value range is provided in brackets.
NOTE: If you have accidentally typed in an unnecessary character, please press *key or wait for 10 seconds until the keypad buzzer
will provide a long beep indicating that the typed in characters have been cleared.
ESIM364 system complies with EN 50131-1 Grade 3 security standard requirements and comes equipped with the following features:
• 6-digit SMS password, user/master and installer codes.
• Prompt for master and installer codes when conguring the system by EKB2, EKB3, EKB3W keypad or ELDES Conguration Tool
software.
• System arming is blocked if any system fault exists. The user will not be able to arm the system until all existing system faults
are solved.
• System arming is blocked until tamper fault is cleared by the installer.
By default, the EN 50131-1 Grade 3 features are disabled. To enable them, please contact your alarm system installer.

11
11
EN
ESIM364 USER MANUAL V1.6
3.MASTER AND USER CODES
The system supports up to 30 numeric codes, identied as Master code and User code 2 through 30, allowing to carry out system arming/
disarming as well as minor system conguration and control by the keypad.
Master code is authorized to carry out the following:
• Arm/disarm partition.
• Bypass violated zones.
• View violated zones and tampers.
• View system faults.
• Set system date and time.
• View temperature sensor information.
• View event log.
• View and clear alarm log.
• Set/delete user codes.
• Turn ON/OFF electrical appliance.
• Set an existing user code as Duress code.
• Set an existing user code as SGS code.
User code is authorized to carry out the following:
• Arm/disarm partition.
• Bypass violated zones.
• View violated zones and tampers.
• View system faults.
• Set system date and time.
• View temperature sensor information.
• View and clear alarm log.
3.1. Managing User and Master Codes
By default, only master code is listed as 1111 and assigned to Partition 1, 2, 3 and 4. For more details regarding user and master code
partition management, please refer to 3.3. Assigning User and Master Code Partition.
1. To set a new master code:
EKB2
Enter an existing master code, navigate through the following path using OK and arrow keys and enter a new master code:
OK →vvvv →OK →CODES→OK →MASTER CODE →OK →CODE →OK →mmmm →OK
Value: vvvv – 4-digit existing master code, range – [0000... 9999]; mmmm – 4-digit new master code, range – [0000...
9999].
EKB3/
EKB3W
Press ,
0
, enter and existing master code and a new master code:
0
vvvv
0
1mmmm
Value: vvvv – 4-digit existing master code; mmmm - 4-digit new master code; range - [0000... 9999].
Example: 1 11 1 1
0 0
2 2 2 2
2. To add a user code:
EKB2
Enter the master code, navigate through the following path using OK and arrow keys and enter a user code:
User code 2... 16: OK →mmmm →OK →CODES →OK →USER CODE (2-16) →OK →USER CODE 2... 16 →OK →CODE →OK →
uuuu →OK
User code 17... 30: OK →mmmm →OK →CODES →OK →USER CODE (17-30) →OK →USER CODE 17... 30 →OK →CODE →
OK →uuuu →OK
Value: mmmm – 4-digit master code; uuuu – 4-digit user code, range – [0000... 9999].
EKB3/
EKB3W
Press ,
0
, enter the master code, user code slot and a user code:
0
mmmm us uuuuu
Value: mmmm - 4-digit master code; us - user code slot, range - [02... 30]; uuuu - 4-digit user code, range - [0000... 9999].
Example: 1 1 1 1
0 0
2
9
5 5 6
3. To delete an existing user code:
EKB2
Enter the master code, navigate through the following path using OK and arrow keys and enter the user code you wish to delete:
OK →mmmm →OK →CODES →OK →REMOVE CODE →OK →uuuu →OK
Value: mmmm – 4-digit master code; uuuu – 4-digit user code.
EKB3/
EKB3W
Press ,
0
, enter the master code and the user code slot you wish to delete:
0
mmmm us
Value: mmmm - 4-digit master code; us - user code slot, range - [02... 30].
Example: 1 1 1 1
0 0
9

12
12
EN ESIM364 USER MANUAL V1.6
3.2. Setting Duress and SGS Codes
• Duress code - The Duress code is used when system arming or disarming is demanded by force. When used, the system will arm/disarm
as well as it will silently transmit an alert to the monitoring station. Only one of the user codes ranging from User code 2 through 10 can
be set as Duress code. .
• SGS code – The user codes ranging from User code 2 through 10 can be set as SGS (Security Guard Service) code, which is used as a
checkpoint by a security service guard upon his/her visit in the secured location. When used, a data message, containing a certain event
code, will be delivered to the monitoring station. However, NO system arming or disarming will be carried out after entering the SGS
code.
1. To set an existing user code as Duress code:
EKB2
Enter the master code, navigate through the following path using OK and arrow keys and select the user code you wish to set
as Duress code:
OK →mmmm →OK →CODES →OK →DURESS CODE →OK →N/A | USER CODE 2... 10 →OK
Value: mmmm – 4-digit master code; N/A – Duress code not in use.
EKB3/
EKB3W
Press , 3, enter the user code slot you wish to set as Duress code and enter the master code:
3us mmmm
Value: us - user code slot, range - [02... 10]; mmmm - 4-digit master code.
Example:
0 0
382 2 2 2
2. To set an existing user code as SGS code:
EKB2
Enter the master code, navigate through the following path using OK and arrow keys and select the user code you wish to set
as SGS code:
OK →mmmm →OK →CODES →OK →SGS CODE →OK →N/A | USER CODE 2... 10 →OK
Value: mmmm – 4-digit master code; N/A – SGS code not in use.
EKB3/
EKB3W
Press , 4, enter the user code slot you wish to set as SGS code and enter the master code:
4us mmmm
Value: us - user code slot, range - [02... 10]; mmmm - 4-digit master code.
Example:
0 0
2 2 2 2
4 4
3.3. Assigning User and Master Code Partition
User/master code partition determines which system partition (-s) can be armed/disarm using the master code or a certain user code. For
more details on how to arm/disarm the system, please refer to 5. ARMING, DISARMING AND TURNING OFF THE ALARM.
The following table reects the values used for system element assignment to partitions by EKB2/EKB3/EKB3W keypad. A sum of values is
used to assign the element to multiple partitions.
Partition Partition value (pv)
Partition 1 1
Partition 2 2
Partition 3 4
Partition 4 8
Example #1: The user wants to assign a certain user code to Partition 4 only. According to the table value 8 reects Partition 4. He would
then have to enter value 8.
Example #2: The user wants to assign a certain user code to Partition 2 and 3. According to the table value 2 reects Partition 2, while
value 4 reects Partition 3, therefore 2 + 4 = 6. He would then have to enter value 6.
Example #3: The user wants to assign the master code to Partition 1, 3 and 4. According to the table value 1 reects Partition 1, while
values 4 and 8 reect Partitions 3 and 4 respectively, therefore 1 + 4 + 8 = 13. He would then have to enter value 13.

13
13
EN
ESIM364 USER MANUAL V1.6
To assign the master code or a certain user code to a certain partition (-s):
EKB2
Enter the master code, navigate through the following path using OK and arrow keys, select the master code or a certain user
code and enter the partition value you wish the code to assign to.
Master code: OK →mmmm →OK →CODES →OK →MASTER CODE →OK →PARTITION →OK →pv →OK
User code 2... 17: ... →CODES →OK →USER CODE (2-17) →OK →USER CODE 2... 17 →OK →PARTITION →OK →pv →OK
User code 18... 30: ... →CODES →OK →USER CODE (18-30) →OK →USER CODE 18... 30 →OK →PARTITION →OK →pv →OK
Value: mmmm – 4-digit master code; pv – partition value (see table on page 12).
EKB3/
EKB3W
Press , 5, enter 01 or user code slot, partition value you wish the code to assign to and the master code:
Master code: 501 pv mmmm
User code: 5us pv mmmm
Value: us - user code slot, range - [02... 30]; pv – partition value (see table on page 12); mmmm - 4-digit master code.
Example: 4
0
22 2 2
5
4.SETTING UP DATE AND TIME
NOTE: When the alarm system is connected to a monitoring station the date and time are set automatically. The system retrieves this
data from the monitoring station by itself.
SMS
1. Send the following SMS text message to the phone number of ESIM364 alarm system:
SMS text message content:
ssss_yyyy.mm.dd_hr:mn
Value: ssss - 4-digit SMS password; yyyy – year; mm – month, range – [01... 12]; dd – day, range - [01... 31]; hr – hours, range
– [00... 23], mn – minutes, range – [00... 59].
Example: 1111_2011.12.15_13:45
2. The system will reply with conrmation by SMS text message to user phone number who sent the SMS text message after
the date and time is set successfully.
EKB2
Navigate through the following menu path using OK and arrow keys and enter the date and time values using the number keys:
Menu path:
OK →DATE/TIME SET →OK →yyyy-mm-dd_hr:mn →OK
Value: yyyy – year; mm – month, range – [01... 12]; dd – day, range - [01... 31]; hr – hours, range – [00... 23], mn – minutes, range
– [00... 59].
Example: 2015-12-15 13:45
5
0

14
14
EN ESIM364 USER MANUAL V1.6
5.ARMING, DISARMING AND TURNING OFF THE ALARM
Before arming the system it is necessary to close all doors and windows in the secured area and move yourself away from the motion detec-
tion eld.
Close all
windows
Move away from
motion detection
eld
Close all
doors
Close all
doors
3
NOTE: Your alarm system installer may have enabled a Force attribute for certain zone (-s), thus allowing to arm the system, while the
zone with Force attribute enabled is violated. This event is identied as Partial Arm.
5.1. Free of Charge Phone Call
To arm, disarm the system and turn OFF the alarm, dial the system‘s phone number from any of 10 available user phone numbers
(contact your alarm system installer for user phone number management). The phone call is free charge as the system rejects
it and carries out arming/disarming procedure afterwards. When arming – the system rejects the phone call after 2 rings, when
disarming – the system rejects the phone call immediately. If there is more than one listed user dialling to the system at the
same time, the system will accept the incoming call from the user who was the rst to dial while other user (-s) will be ignored.
When system’s phone number is dialled for arming, the system will proceed as follows:
• Non-partitioned system:
• If ready (no violated zone/tamper), the system will arm.
• If unready (violated zone/tamper is present), the system will not arm and provide a list of violated zones/tampers by SMS text
message to user phone number. In such case the user must restore all violated zones and tampers before arming the system.
Alternatively, the violated zones can be bypassed(see 8. BYPASSING AND ACTIVATING ZONES), disabled (please contact your alarm
system installer to set up this parameter) or a Force attribute enabled (resulting in partial arm; please contact your alarm system installer
to set up this parameter), while the tampers can be disabled (please contact your alarm system installer to set up this parameter).
• Partitioned system:
• If all partitions are disarmed ready, the system will arm them.
• If one or more partitions are disarmed unready (violated zone/tamper is present), the system will arm the ready partition (-s) and
skip the unready one (-s). The system will then send an SMS text message, containing a list of violated zones/tampers, to user
phone number that the system arming was initiated from.
• If a combination of armed and disarmed ready partitions is present, the system will arm the disarmed ready partitions and skip the armed
ones.
When a user phone number is assigned to multiple partitions, the user will be able arm/disarm the corresponding system partitions by dialling the sys-
tem’s phone number. For example, if User 1 is assigned to Partition 1, 2 and 3, the user will be able to arm/disarm Partition 1, 2 and 3 by a single phone
call to the system from User 1 phone number. For more details on how to set user phone number partition, please contact your alarm system installer.
NOTE: Your alarm system installer may have disabled
system arming and/or disarming by free of charge phone
call and SMS text message for a certain user.
User ESIM364
CALL
4
By default, all listed user phone numbers are granted with permission to arm and disarm the system by free of charge phone call and SMS
text message. To disable/enable arming or disarming for certain listed user phone numbers, please refer to the following conguration
method.

15
15
EN
ESIM364 USER MANUAL V1.6
Manage arming and
disarming for listed
user phone numbers
Cong
Tool This operation may be carried out from the PC using the ELDES Conguration Tool software.
5.2. SMS Text Message
SMS
To arm the system by SMS text message, send the following text to the system‘s phone number from any of 10 available user
phone numbers.
Arm the system
SMS text message content:
ssss_ARMp or ssss_ARMp,p,p,p
Value: ssss – 4-digit SMS password; p– partition number, range – [1... 4].
Example: 1111_ARM1
User ESIM364
SMS
5
When the SMS text message for arming is sent to the system’s phone number, the system will proceed as follows:
• Non-partitioned system:
• If ready (no violated zone/tamper), the system will arm followed by SMS text message delivery to the user.
• If unready, the system will not arm and provide a list of violated zones/tampers by SMS text message to user phone
number. In such case the user must restore all violated zones and tampers before arming the system. Alternatively,
the violated zones can be bypassed (see 8. BYPASSING AND ACTIVATING ZONES), disabled (please contact your
alarm system installer to set up this parameter) or a Force attribute enabled (please contact your alarm system installer
to set up this parameter), while the tampers can be disabled (please contact your alarm system installer to set up this
parameter).
• Partitioned system:
• If all partitions are disarmed ready (no violated zone/tamper), the system will arm them.
• If one or more partitions are disarmed unready (violated zone/tamper is present), the system will arm the ready parti-
tion (-s) and skip the unready one (-s). The system will then send an SMS text message, containing a list of violated
zones/tampers, to user phone number that the system arming was initiated from.
• If a combination of armed and disarmed ready partitions is present, the system will arm the disarmed ready partitions
and skip the armed ones.
To disarm the system and turn OFF the alarm by SMS text message, send the following text to the system‘s phone number from any of 10
available user phone numbers:
Disarm the system and
turn OFF the alarm
SMS text message content:
ssss_DISARMp or ssss_DISARMp,p,p,p
Value: ssss – 4-digit SMS password; p– partition number, range – [1... 4].
Example: 1111_DISARM1,2,4
User ESIM364
SMS
6
NOTE: Your alarm system installer may have disabled system arming and/or disarming by free of charge phone call and SMS text mes-
sage for a certain user.

16
16
EN ESIM364 USER MANUAL V1.6
5.3. EKB2 Keypad and User/Master Code
icon displayed next to the partition name in the home screen view of EKB2 keypad indicates that no violated zones and/or tampers
are present, therefore the partition is ready for arming. If icon is displayed instead, the partition is unready for arming, therefore the
user must restore all violated zones and/or tampers before arming the partition. Alternatively, the violated zones can be bypassed (see 8.
BYPASSING AND ACTIVATING ZONES), disabled (please, contact your alarm system installer to set up this feature) or a Force attribute
enabled (please, contact your alarm system installer to set up this parameter), while the tampers can be disabled (please, contact your
alarm system installer to set up this feature). icon appears in the home screen view if system fault (-s) exist (see 13. INDICATION OF
SYSTEM FAULTS).
When a user/master code is assigned to multiple partitions, the user will be able arm/disarm the corresponding system partitions by EKB2
keypad using partition selection menu. However, if a user/master code is assigned to Partition 1, 2 and 4, while EKB2 keypad is assigned
to Partition 2, the user will be able to arm/disarm Partition 1, 2 and 4, but the keypad will only display Partition 2 name and the related
information in home screen view. For more details on how to set the keypad partition and user/master code partition, please refer to 3.3.
Assigning User and Master Code Partition and contact your alarm system installer.
5.3.1.Arming the System
To arm the system by EKB2 keypad, enter any out of 29 available 4-digit user codes or master code using the number keys on the keypad
(see 3. MASTER AND USER CODES for user/master code management). By default, the arming process is as follows:
• Non-partitioned system - When a valid user code is entered, the system will initiate exit delay, the keypad’s buzzer will emit short
beeps, the keypad will switch to home screen view and display the countdown timer.
Arm the system
Enter user/master code:
uumm →OK
Value: uumm – 4-digit user/master code.
• Partitioned system - arming a single partition – When a valid user or master code is entered, the keypad will display the partition
selection menu. Once a partition that is to be armed is selected, the system will initiate exit delay. During the exit delay, the keypad’s
buzzer will emit short beeps and the keypad will display ARMING part-name message for 3 seconds followed by partition selection
menu. When the keypad back-light timeout expires, the home screen view will follow. If key is touched twice during exit delay, the
keypad will return to home screen view and display the countdown timer next to the partition name that is being armed.
Arm the system
Enter user/master code and select partition:
uumm →OK →[p] part-name →OK or OK →uumm →OK →ARM/DIS PARTITION →OK →[p] part-
name →OK
Value: uumm – 4-digit user or master code; p – partition number, range – [1... 4], part-name – up to
15 characters partition name
• Partitioned system - arming multiple partitions simultaneously – When a valid user or master code is entered, the keypad will
display the partition selection menu. Once ARM ALL menu item is selected the system will proceed as follows:
• if all partitions are disarmed-ready (no violated zone/tamper), the system will initiate exit delay. During the exit delay, the keypad’s
buzzer will emit short beeps and the keypad will display multiple ARMING part-name messages for 3 seconds reecting each
partition the user/master code is assigned to, followed by partition selection menu.
• if one or more partitions are disarmed-unready (contains violated zone/tamper), the system will initiate exit delay. During the exit
delay, the keypad’s buzzer will emit short beeps and the keypad will display ARMING part-name message (-s) reecting ready
partition (-s), while the unready partition (-s) will be skipped indicated by part-name NOT READY message (-s) followed by
partition selection menu. Each message will be displayed for 2 seconds and corresponds to the partition (-s) the user/master code
is assigned to.
• if a combination of armed and disarmed-ready partitions exists, the system will initiate exit delay. During the exit delay, the keypad’s
buzzer will emit short beeps and the keypad will display ARMING part-name message (-s) seconds reecting ready partition (-s),
while the pre-armed partition (-s) will be skipped. Each message will be displayed for 2 seconds and corresponds to the partition (-s)
the user/master code is assigned to.
When the keypad back-light timeout expires, the home screen view will follow. If key is touched twice during exit delay, the keypad will
return to home screen view and display the countdown timers next to the partition names the keypad is assigned to.
Arm all partitions
simultaneously
Enter user/master code:
uumm →OK →ARM ALL →OK or OK →uumm →OK →ARM/DIS PARTITION →OK →ARM ALL →OK
Value: uumm – 4-digit user/master code
When successfully armed:
• the countdown timers will disappear.
• user will be notied by SMS text message
• in addition, the keypad may display icon next to the partition name that has been armed (by default – disabled).

17
17
EN
ESIM364 USER MANUAL V1.6
NOTE: If the user fails to enter a correct user/master code 10 times in a row, the system will block the keypad for 2 minutes and the
keypad will display KEYPAD BLOCKED message. While the keypad is blocked, the system prevents from entering any user/master code.
The keypad will automatically unblock once the 2-minute time period has expired and display KEYPAD UNBLOCKED message
5.3.2. Cancelling System Arming
To cancel the arming process:
• Non-partitioned system – Enter the user/master code again during exit delay countdown.
• Partitioned system – Select the partition again, that is currently being armed, from the partition selection menu during exit delay
countdown. The keypad will display part-name ARMING TERMINATED message for 2 seconds followed by partition selection menu.
5.3.3. Disarming the System and Turning OFF the Alarm
To disarm and turn OFF the alarm, enter any out of 29 available 4-digit user codes or master code using the number keys on the keypad. By
default, the system disarming process is as follows:
• Non-partitioned system – When a valid user or master code is entered, the keypad will switch to home screen view.
Disarm the system and
turn OFF the alarm
Enter user/master code:
uumm →OK
Value: uumm – 4-digit user/master code.
• Partitioned system - disarming a single partition – When a valid user or master code is entered, the keypad will display the
partition selection menu. Once a partition that is to be disarmed is selected, the keypad will display part-name DISARMED message
for 2 seconds and return to partition selection menu followed by home screen view after the keypad back-light timeout expires.
Alternatively, the key may be touched in order to instantly return to home screen view.
Disarm the system and
turn OFF the alarm
Enter user/master code and select partition:
uumm →OK →[p] part-name →OK or OK →uumm →OK →ARM/DIS PARTITION →OK →[p] part-name
→OK
Value: uumm – 4-digit user or master code; p– partition number, range – [1... 4], part-name – up to 15
characters partition name.
• Partitioned system - disarming multiple partitions simultaneously – When a valid user or master code is entered, the keypad will
display the partition selection menu. Once DISARM ALL menu item is selected, the keypad will display multiple part-name DISARMED
messages for 2 seconds reecting each partition the user/master code is assigned to and return to partition selection menu followed
by home screen view after the keypad back-light timeout expires. Alternatively, the key may be touched in order to instantly return
to home screen view.
Disarm all partitions
and turn OFF the alarm
simultaneously
Enter user/master code:
uumm →OK →DISARM ALL →OK or OK →uumm →OK →ARM/DIS PARTITION →OK →DISARM ALL →OK
Value: uumm – 4-digit user/ master code
When successfully disarmed, the keypad may display icon next to the partition name that has been disarmed (by default - disabled) and
notify the user by SMS text message.
NOTE: If the user fails to enter a correct user/master code 10 times in a row, the system will block the keypad for 2 minutes and the
keypad will display KEYPAD BLOCKED message. While the keypad is blocked, the system prevents from entering any user/master code.
The keypad will automatically unblock once the 2-minute time period has expired and display KEYPAD UNBLOCKED message.

18
18
EN ESIM364 USER MANUAL V1.6
5.4. EKB3 Keypad and User/Master Code
ATTENTION: EKB3 keypad can operate either in 2-partition or in 4-partition mode. The description of the following procedure is based on
4-partition mode operation on EKB3 keypad. The arming/disarming procedure in 2-partition mode using EKB3 keypad would be carried out
identically to EKB3W wireless keypad. For more details on 2-partition mode, please contact your alarm system installer.
Illuminated indicator on EKB3 keypad indicates that no violated zones and/or tampers are present, therefore the partition is ready for
arming. If the indicator is not illuminated, the partition is unready for arming, therefore the user must restore all violated zones and/or
tampers before arming the partition. Alternatively, the violated zones can be bypassed (see 8. BYPASSING AND ACTIVATING ZONES),
disabled (please contact your alarm system installer to set up this parameter) or a Force attribute enabled (please contact your alarm
system installer to set up this parameter), while the tampers can be disabled (please contact your alarm system installer to set up this
parameter). Indicator will illuminate or ash if system fault (-s) exist (see 13. INDICATION OF SYSTEM FAULTS).
The system will arm/disarm the partition corresponding to the one that user/master code and the keypad are assigned to. For example,
if User code 4 is assigned to Partition 2, 3 and 4, while EKB3 keypad is assigned to Partition 2, the user will be able to arm/disarm only
Partition 2 by entering User code 4. For more details on how to set the keypad partition and user/master code partition, please refer to 3.3.
Assigning User and Master Code Partition and contact your alarm system installer.
5.4.1. Arming the System
To arm the system by EKB3 keypad, enter any out of 29 available 4-digit user codes or master code using the number keys on the keypad
(see 3. MASTER AND USER CODES for user/master code management). By default, the arming process is as follows:
• Non-partitioned system – When a valid user/master code is entered, the system will initiate exit delay, the keypad’s buzzer will emit
short beeps and the indicator along with the number 4
1key, indicating the partition that is to be armed, will light ON. When
the system is successfully armed, the keypad’s buzzer will silent down.
Arm the system
Enter user/master code:
uumm
Value: uumm – 4-digit user or master code.
Example: 2 2 2 2
• Partitioned system – arming a single partition – To arm a dierent partition than the keypad is assigned to, use keypad partition
switch feature (by default – disabled; please, contact your alarm system installer to set up this parameter) before the arming process.
Switch keypad parti-
tion
Hold the 4
1key and release it after 3 short beeps:
Value: 4
1key – partition number 1... 4 respectively.
Once the partition is switched and a valid user/master code is entered, the system will initiate exit delay, the keypad’s buzzer will emit short
beeps and the indicator along with the number 4
1key, indicating the partition that is to be armed, will light ON. When the system
is successfully armed, the keypad’s buzzer will silent down and the user will be notied by SMS text message.
Arm the system
Enter user/master code:
uumm
Value: uumm – 4-digit user or master code.
Example: 2 2 2 2
• Partitioned system - arming all 4 partitions simultaneously – If a user/master code assigned to all 4 partitions exists, user can
arm all partitions simultaneously. When this feature is used, the system will proceed as follows:
• if all partitions are disarmed-ready (no violated zone/tamper), the system will initiate exit delay. During the exit delay, the keypad’s
buzzer will emit short beeps and indicator along with number 1, 2, 3and 4keys will light ON followed by SMS text
message delivery to the user. When the system is successfully armed, the keypad’s buzzer will silent down.
• if one or more partitions are disarmed-unready (keypad number 4
1key ashing, indicating the partition that contains
violated zone/tamper), the system will initiate exit delay. During the exit delay, the keypad’s buzzer will emit short beeps and keypad
indicator (if the keypad is switched to a non-violated partition) along with the number 4
1key, indicating the partition that
is to be armed, will light ON followed by SMS text message delivery to the user. The ready partition (-s) will be armed and the unready
one (-s) will be skipped.
• if a combination of armed and disarmed ready partitions is present, the system will initiate exit delay. During the exit delay, the
keypad’s buzzer will emit short beeps and keypad indicator (if the keypad is switched to a disarmed partition) along with the
number 4
1key, indicating the partition that is to be armed, will light ON followed by SMS text message delivery to the user.
The disarmed-ready partitions will be armed and the pre-armed ones will be skipped.
Arm all 4 partitions
simultaneously
Hold the
0
key, release it after 3 short beeps and enter user/ master code:
0
uumm
Value: uumm – 4-digit user or master code.
Example: 2 2 2 2
0

19
19
EN
ESIM364 USER MANUAL V1.6
Alternatively, the user can arm multiple partitions one by one (see Partitioned system - arming a single partition above).
NOTE: Before arming all 4 partitions simultaneously, the user/master code must be assigned to all 4 partitions and the keypad partition
switch feature enabled (please, contact your alarm system installer to set up this parameter).
NOTE: If the user fails to enter a correct user/master code 10 times in a row, the system will block the keypad for 2 minutes. While the
keypad is blocked, the system prevents from entering any user/master code. The keypad will automatically unblock once the 2-minute
time has expired.
5.4.2. Cancelling System Arming
To cancel the arming process, enter the user/master code again during exit delay countdown.
5.4.3. Disarming the System and Turning OFF the Alarm
To disarm and turn OFF the alarm, enter any out of 29 available 4-digit user codes or master code using the number keys on the keypad. By
default, the system disarming process is as follows:
• Non-partitioned system – When a valid user/ master code is entered, indicator and the number 1key will light OFF and the user
will be notied by SMS text message.
Disarm the system and
turn OFF the alarm
Enter user/master code:
uumm
Value: uumm – 4-digit user or master code.
Example: 2 2 2 2
• Partitioned system – disarming a single partition – To disarm a dierent partition than the keypad is assigned to, use keypad
partition switch feature (by default – disabled; please, contact your alarm system installer to set up this parameter) before the disarming
process.
Switch keypad parti-
tion
Hold the 4
1key and release it after 3 short beeps:
Value: 4
1key – partition number 1... 4 respectively.
Once the partition is switched and a valid user/master code is entered, indicator and the number 4
1key, indicating the partition
that has been disarmed, will light OFF and the user will be notied by SMS text message.
Disarm the system and
turn OFF the alarm
Enter user/master code:
uumm
Value: uumm – 4-digit user or master code.
Example: 2 2 2 2
• Partitioned system - disarming all 4 partitions simultaneously – If a user/master code assigned to all 4 partitions exists, user can
disarm and turn OFF the alarm in all partitions simultaneously. When this feature is used, the system will proceed as follows:
• if all partitions are armed and a valid user/master code is entered, indicator along with the number 1, 2, 3and 4keys
will light OFF and the user will be notied by SMS text message.
• if one or more partitions are disarmed unready (keypad number 4
1key ashing, indicating the partition that contains violated
zone/tamper), the system will deny simultaneous partition disarming until the partition’s zone/tamper violation is removed.
• if a combination of armed and disarmed ready partitions is present, the system will initiate exit delay. During the exit delay, the
keypad’s buzzer will emit short beeps and keypad indicator (if the keypad is switched to a disarmed partition) along with the
number 4
1key, indicating the partition that is to be armed, will light ON. The disarmed-ready partitions will be armed and
the pre-armed ones will be skipped. In order to disarm all 4 partitions simultaneously, the user must repeat the following command:
Disarm and turn OFF
the alarm in all 4 parti-
tions simultaneously
Hold the
0
key, release it after 3 short beeps and enter user/ master code:
0
uumm
Value: uumm – 4-digit user or master code.
Example: 2 2 2 2
0
Alternatively, the user can disarm and turn OFF the alarm in multiple partitions one by one (see Partitioned system - disarming a single
partition above).
NOTE: If the user fails to enter a correct user/master code 10 times in a row, the system will block the keypad for 2 minutes. While the
keypad is blocked, the system prevents from entering any user/master code. The keypad will automatically unblock once the 2-minute
time has expired.
NOTE: Before disarming all 4 partitions simultaneously, the user/master code must be assigned to all 4 partitions and the keypad partition
switch feature enabled (please, contact your alarm system installer to set up this parameter).

20
20
EN ESIM364 USER MANUAL V1.6
5.5. EKB3W Keypad and User/Master Code
ATTENTION: The user will be able arm/disarm only the rst two system partitions using EKB3W keypad. Partition 3 and Partition 4 are
NOT supported by EKB3W keypad.
Illuminated indicator on EKB3W keypad indicates that no violated zones and/or tampers are present, therefore the partition is ready for
arming. If the indicator is not illuminated, the partition is unready for arming, therefore the user must restore all violated zones and/or
tampers before arming the partition. Alternatively, the violated zones can be bypassed (see 8. BYPASSING AND ACTIVATING ZONES),
disabled (please contact your alarm system installer to set up this parameter) or a Force attribute enabled (please contact your alarm
system installer to set up this parameter), while the tampers can be disabled (please contact your alarm system installer to set up this
parameter). Indicator will illuminate or ash if system fault (-s) exist (see 13. INDICATION OF SYSTEM FAULTS).
The system will arm/disarm the partition corresponding to the one that user/master code and the keypad are assigned to. For example, if
User code 4 is assigned to Partition 2, while EKB3W keypad is assigned to Partition 1, the user will be able to arm/disarm only Partition 2 by
entering User code 4. For more details on how to set the keypad partition and user/master code partition, please refer to 3.3. Assigning
User and Master Code Partition and contact your alarm system installer
5.5.1.Arming the System
• Non-partitioned system – When a valid user/master code is entered, the system will initiate exit delay, the keypad’s buzzer will emit
short beeps and the indicator will light ON. When the system is successfully armed, the keypad’s buzzer will silent down.
Arm the system
Enter user/master code:
uumm
Value: uumm – 4-digit user or master code.
Example: 2 2 2 2
• Partitioned system - arming a single partition – To arm a dierent partition than the keypad is assigned to, use keypad partition
switch feature (by default – disabled; please, contact your alarm system installer to set up this parameter) before the disarming process.
Switch keypad parti-
tion
Hold the 1 2 key and release it after 3 short beeps:
Value: 1 2 key – partition number 1... 2 respectively.
Once the partition is switched, indicator will light ON in EKB3W keypad’s section A (= Partition 1) or B (= Partition 2) and by entering a
valid user/master code, the system will initiate exit delay, the keypad’s buzzer will emit short beeps and the indicator will light ON in
the respective EKB3W keypad’s section. When the system is successfully armed, the keypad’s buzzer will silent down and the user will be
notied by SMS text message.
Arm the system
Enter user/master code:
uumm
Value: uumm – 4-digit user or master code.
Example: 2 2 2 2
To arm multiple partitions, please arm the partitions one by one by following the aforementioned procedure.
NOTE: If the user fails to enter a correct user/master code 10 times in a row, the system will block the keypad for 2 minutes. While the
keypad is blocked, the system prevents from entering any user/master code. The keypad will automatically unblock once the 2-minute
time has expired.
5.5.2. Cancelling System Arming
To cancel the arming process, enter the user/master code again during exit delay countdown.
5.5.3. Disarming the System and Turning OFF the Alarm
To disarm and turn OFF the alarm, enter any out of 29 available 4-digit user codes or master code using the number keys on the keypad. By
default, the system disarming process is as follows:
• Non-partitioned system – When a valid user/ master code is entered, indicator will light OFF and the user will be notied by SMS
text message.
Disarm the system and
turn OFF the alarm
Enter user/master code:
uumm
Value: uumm – 4-digit user or master code.
Example: 2 2 2 2
• Partitioned system - disarming a single partition – To disarm and turn OFF the alarm in a dierent partition than the keypad
is assigned to, use keypad partition switch feature (by default – disabled; please, contact your alarm system installer to set up this
Other manuals for ESIM364
5
Table of contents
Other Eldes Security System manuals

Eldes
Eldes EWS1 User manual

Eldes
Eldes EWS1 User manual

Eldes
Eldes ESIM364 User manual

Eldes
Eldes PITBULL ALARM Instruction Manual

Eldes
Eldes ESIM384 User manual

Eldes
Eldes ESIM264 User manual

Eldes
Eldes ME1 User manual

Eldes
Eldes PITBULL ALARM PRO User manual

Eldes
Eldes EWS2 User manual

Eldes
Eldes ESIM264 User manual
Popular Security System manuals by other brands

Pyronix
Pyronix Enforcer 64 installation guide

Senstar Stellar
Senstar Stellar 100 Operator's guide

GLOBAL ASSISTIVE DEVICES
GLOBAL ASSISTIVE DEVICES Access 4 instruction manual

Radio Shack
Radio Shack RS-1000 owner's manual

Siemens
Siemens Sensor Light owner's manual

Vimar
Vimar By-alarm 01703.DE quick start guide