manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Emerson
  6. •
  7. Controllers
  8. •
  9. Emerson Dixell XR44CX Wiring diagram

Emerson Dixell XR44CX Wiring diagram

1598024001 XR44CX ISA GB r2.0 21.06.2012.doc XR44CX 1/4
Digital controller with defrost and fan management
XR44CX
1. GENERAL WARNING........................................................................................................... 1
2. GENERAL DESCRIPTION .................................................................................................... 1
3. CONTROLLING LOADS ....................................................................................................... 1
4. FRONT PANEL COMMANDS ............................................................................................... 1
5. MAX & MIN TEMPERATURE MEMORIZATION .................................................................... 1
6. MAIN FUNCTIONS ............................................................................................................... 2
7. PARAMETERS..................................................................................................................... 2
8. DIGITAL INPUTS.................................................................................................................. 3
9. TTL SERIAL LINE – FOR MONITORING SYSTEMS ............................................................. 3
10. INSTALLATION AND MOUNTING......................................................................................... 3
11. ELECTRICAL CONNECTIONS.............................................................................................. 3
12. USE THE HOT KEY.............................................................................................................. 3
13. ALARM SIGNALS ................................................................................................................. 3
14. TECHNICAL DATA ............................................................................................................... 4
15. CONNECTIONS ................................................................................................................... 4
16. DEFAULT SETTING VALUES............................................................................................... 4
1. GENERAL WARNING
1.1 PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick
reference.
The instrument shall not be used for purposes different from those described hereunder. It
cannot be used as a safety device.
Check the application limits before proceeding.
Dixell Srl reserves the right to change the composition of its products, even without notice,
ensuring the same and unchanged functionality.
1.2 SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding
sudden temperature changes with high atmospheric humidity to prevent formation of
condensation
Warning: disconnect all electrical connections before any kind of maintenance.
Fit the probe where it is not accessible by the End User. The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.”
(see address) with a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough
from each other, without crossing or intertwining.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in
parallel with inductive loads could be useful.
2. GENERAL DESCRIPTION
Model XR44CX, format 32 x 74 mm, is microprocessor based controller, suitable for applications on
low temperature refrigerating units. It has four relay outputs to control compressor 1 and 2, defrost 1
and 2, which can be either electrical or reverse cycle (hot gas). It is also provided with up to three
NTC or PTC probe inputs, the first one for temperature control, the second and third one, to be
located onto the evaporator, to control the defrost termination temperature on the evaporator 1 and 2.
It allows to program the controller by means the HOT KEY programming keyboard.
3. CONTROLLING LOADS
3.1 COMPRESSOR
The regulation is performed according to
the temperature measured by the
thermostat probe with a positive
differential from the set point: if the
temperature increases and reaches set
point plus differential the compressor is
started and then turned off when the
temperature reaches the set point value
again.
Time
Temper.
Compr.
SET
ON
In case of fault in the thermostat probe the start and stop of the compressor are timed through
parameters Con and CoF.
3.2 SECOND COMPRESSOR MANAGEMENT
The relay of the second compressor is activated in parallel with the relay of the first compressor, with
a possible delay set in the AC1 parameter. Both the compressors are switched off at the same time.
3.3 DEFROST
Two defrost modes are available through the tdF parameter: defrost through electrical heater
(tdF=EL) and hot gas defrost (tdF=in).
Other parameters are used to control the interval between defrost cycles (idF), its maximum length
(MdF) and two defrost modes: timed or controlled by the evaporator’s probe (P2P).
At the end of defrost dripping time is started, its length is set in the Fdt parameter. With Fdt=0 the
dripping time is disabled.
3.4 CONTROL OF EVAPORATOR FANS
The fan control mode is selected by means of the FnC parameter:
FnC=C_n, fans will switch ON and OFF with the compressor and not run during defrost.
FnC=o_n, fans will run even if the compressor is off, and not run during defrost.
After defrost, there is a timed fan delay allowing for drip time, set by means of the Fnd parameter.
FnC=C_Y,fans will switch ON and OFF with the compressor and run during defrost.
FnC=o_Y, fans will run continuously also during defrost.
An additional parameter FSt provides the setting of temperature, detected by the evaporator probe,
above which the fans are always OFF. This is used to make sure circulation of air only if his
temperature is lower than set in FSt.
3.4.1 Forced activation of fans
This function managed by the FCt parameter is designed to avoid short cycles of fans, that could
happen when the controller is switched on or after a defrost, when the room air warms the evaporator.
How it works: if the temperature difference between evaporator probe and room probe is higher than
the FCt parameter value, fans will be switched on. With FCt=0 the function is disabled.
3.4.2 Cyclical activation of the fans with compressor off.
When FnC=C-n or C-Y (fans working in parallel with the compressor), by means of the Fon and FoF
parameters the fans can carry out on and off cycles even if the compressor is switched off. When the
compressor is stopped the fans go on working for the Fon time. With Fon=0 the fans remain always
off, also when the compressor is off.
4. FRONT PANEL COMMANDS
To display target set point; in programming mode it selects a parameter or confirm
an operation.
(DEF) To start a manual defrost.
(UP) To see the max stored temperature; in programming mode it browses the
parameter codes or increases the displayed value.
(DOWN) To see the min stored temperature; in programming mode it browses the
parameter codes or decreases the displayed value.
To switch the instrument on and off (when onF=oFF).
To switch on and off the light output (if present).
KEY COMBINATIONS:
+ To lock & unlock the keyboard.
+To enter in programming mode.
+To return to the room temperature display.
4.1 USE OF LEDS
Each LED function is described in the following table.
LED MODE FUNCTION
ON Compressor enabled
Flashing
Anti-short cycle delay enabled
ON Defrost enabled
Flashing
Drip time in progress
ON An alarm is occurring
ON Continuous cycle is running
°C/°F
ON Measurement unit
Flashing
Programming phase
5. MAX & MIN TEMPERATURE MEMORIZATION
5.1 HOW TO: SEE THE MIN TEMPERATURE
1. Press and release the DOWN key.
2. The “Lo” message will be displayed followed by the minimum temperature recorded.
3. By pressing the DOWN key again or by waiting 5 sec the normal display will be restored.
5.2 HOW TO: SEE THE MAX TEMPERATURE
1. Press and release the UP key.
2. The “Hi” message will be displayed followed by the maximum temperature recorded.
3. By pressing the UP key again or by waiting 5 sec the normal display will be restored.
5.3 HOW TO: RESET THE MAX AND MIN TEMPERATURE RECORDED
1. Keep the SET key pressed more than 3 sec, while the max or min temperature is displayed.
(“rSt” message will be displayed)
2. To confirm the operation the “rSt” message will start blinking and the normal temperature will be
displayed.
1598024001 XR44CX ISA GB r2.0 21.06.2012.doc XR44CX 2/4
6. MAIN FUNCTIONS
6.1 HOW TO: SEE THE SET POINT
1. Push and immediately release the SET key: the display will show the Set
point value.
2. Push and immediately release the SET key or wait for 5 sec to display
the probe value again.
6.2 HOW TO CHANGE THE SET POINT
1. Push the SET key more than 2 sec to change the Set point value.
2. The value of the set point will be displayed and the “°C” or “°F”LED will start blinking.
3. To change the Set value push the UP or DOWN arrows within 10 sec.
4. To save the new set point value, push the SET key again or wait for 10 sec.
6.3 HOW TO START A MANUAL DEFROST
Push the DEF key for more than 2 sec and a manual defrost will start.
6.4 HOW TO: CHANGE A PARAMETER VALUE
To change a parameter value, operate as follows:
1. Enter the Programming mode by pressing the SET+DOWN buttons for 3s (the °C or °F LED will
start blinking).
2. Select the required parameter. Press the SET button to display its actual value.
3. Use UP or DOWN buttons to change its value.
4. Press SET button to store the new value and move to the following parameter.
To exit: Press SET + UP buttons or waiting for 15s without pressing any key.
NOTE: the set value is stored even when the procedure is exited by waiting for the time-out to expire.
6.5 THE HIDDEN MENU
The hidden menu includes all the parameters of the instrument.
6.5.1 HOW TO: ENTER THE HIDDEN MENU
1. Enter the Programming mode by pressing the SET+DOWN buttons for 3 sec (the °C or °F LED
will start blinking).
2. Released the buttons and then push again the SET+DOWN buttons for more than 7s. The Pr2
label will be displayed immediately followed from the HY parameter.
Now it is possible to browse the hidden menu.
3. Select the required parameter.
4. Press the SET button to display its value.
5. Use UP or DOWN to change its value.
6. Press SET to store the new value and move to the following parameter.
To exit: Press SET+DOWN or wait 15 sec without pressing a key.
NOTE1: if no parameter is present in Pr1 menu, after 3 sec the “noP” message will be displayed.
Keep the buttons pushed till the Pr2 message will be displayed.
NOTE2: the set value is stored even when the procedure is exited by waiting for the time-out to
expire
6.5.2 HOW TO: MOVE A PARAMETER FROM THE HIDDEN MENU TO THE
FIRST LEVEL AND VICEVERSA.
Each parameter present in the hidden menu (Pr2) can be moved into the user level (Pr1) by pressing
SET+DOWN buttons. If a parameter is part of the user level, when showed in the hidden menu the
decimal point will be lit.
6.6 HOW TO: LOCK THE KEYBOARD
1. Keep both UP and DOWN buttons pressed for more than 3 sec.
2. The “PoF” message will be displayed and the keyboard will be locked. At this point it will be
possible only to see the set point or the MAX o Min temperature stored
3. If a button is pressed more than 3 sec the “PoF” message will be displayed
6.7 HOW TO: UNLOCK THE KEYBOARD
Keep pressed together for more than 3 sec the UP and DOWN keys till the “Pon” message will be
displayed.
6.8 THE CONTINUOUS CYCLE
When defrost is not in progress, it can be activated by holding the UP key pressed for about 3 sec.
The compressor operates to maintain the CCS set point for the time set through the CCt parameter.
The cycle can be terminated before the end of the set time using the same activation key UP for 3
sec.
6.9 THE ON/OFF FUNCTION
With “onF = oFF”, pushing the ON/OFF key, the instrument is switched off. The “OFF”
message is displayed. In this configuration, the regulation is disabled.
To switch the instrument on, push again the ON/OFF key.
WARNING: Loads connected to the normally closed contacts of the relays are always
supplied and under voltage, even if the instrument is in stand by mode.
7. PARAMETERS
REGULATION
HY Differential: (0.1 to 25.5°C; 1 to 45°F) intervention differential for set point.
Compressor Cut IN is Set Point + differential (HY). Compressor Cut OUT is when the
temperature reaches the set point.
LS Minimum set point: (-55°C to SET; -67°F to SET) sets the minimum value for the set
point.
US Maximum set point: (SET to 150°C; SET to 302°F) set the maximum value for set
point.
ot Thermostat probe calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust possible
offset of the thermostat probe.
P2P First evaporator probe presence: (n; Y) n= not present, the defrost stops by time;
Y= present, the defrost stops by temperature.
oE First evaporator probe calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust
possible offset of the evaporator probe.
P3P Second evaporator probe presence (P3): (n; Y) n= not present, the terminals
operate as digital input; Y= present, the terminals operate as third probe.
o3 Second evaporator probe calibration (P3): (-12.0 to 12.0°C; -21 to 21°F) allows to
adjust possible offset of the third probe.
odS Outputs activation delay at start up: (0 to 255min) this function is enabled at the
initial start up of the instrument and inhibits any output activation for the period of time
set in the parameter.
AC Anti-short cycle delay for first compressor: (0 to 50 min) minimum interval between
the compressor stop and the following restart.
AC1
Anti-short cycle delay for second compressor: (0 to 50 min) minimum interval
between the compressor stop and the following restart.
CCt Compressor ON time during continuous cycle: (0.0 to 24h00min, res. 10 min)
allows to set the length of the continuous cycle. Compressor stays on without
interruption during CCt time. This is useful, for instance, when the room is filled with
new products.
CCS Set point for continuous cycle: (-55 to 150°C; -67 to 302°F) it sets the set point
used during the continuous cycle.
Con Compressor ON time with faulty probe: (0 to 255min) time during which the
compressor is active in case of faulty thermostat probe. With Con=0 compressor is
always OFF.
CoF Compressor OFF time with faulty probe: (0 to 255min) time during which the
compressor is OFF in case of faulty thermostat probe. With CoF=0 compressor is
always active.
DISPLAY
CF Temperature measurement unit: (°C; °F) °C = Celsius; °F = Fahrenheit.
WARNING: When the measurement unit is changed the SET point and the values of
the parameters HY, LS, US, ot, ALU and ALL have to be checked and modified (if
necessary).
rES Resolution (for °C): (in=1°C; dE=0.1°C) allows decimal point display.
Lod Instrument display: (P1; P2, P3, P4, SET, dtr) it selects which probe is displayed by
the instrument. P1 = Thermostat probe; P2 = Evaporator probe; P3 = Third probe (only
for model with this option enabled); P4 = Fourth probe, SET = set point; dtr =
percentage of visualization.
DEFROST
tdF Defrost type: (EL; in) EL = electrical heater; in = hot gas.
dtE First defrost termination temperature: (-55 to 50°C; -67 to 122°F) (enabled only
when EdF=Pb) sets the temperature measured by the evaporator probe, which causes
the end of defrost.
dtS Second defrost termination temperature: (-55 to 50°C; -67 to 122°F) (enabled only
when EdF=Pb) sets the temperature measured by the evaporator probe, which causes
the end of defrost.
idF Interval between defrost cycles: (0 to 120 hours) determines the interval of time
between two defrost cycles.
MdF
(Maximum) length for first defrost: (0 to 255 min) when P2P=n, (not evaporator
probe: timed defrost) it sets the defrost duration. When P2P=Y (defrost end based on
temperature) it sets the maximum length for defrost.
MdS
(Maximum) length for second defrost: (0 to 255 min) when P2P=n, (not evaporator
probe: timed defrost) it sets the defrost duration. When P2P=Y (defrost end based on
temperature) it sets the maximum length for defrost.
dSd Start defrost delay: (0 to 99 min) this is useful when different defrost start times are
necessary to avoid overloading the plant.
dFd Temperature displayed during defrost: (rt; it; SEt; dEF) rt = real temperature;
it = temperature at defrost start; SEt = set point; dEF = “dEF” label.
dAd MAX display delay after defrost: (0 to 255 min) sets the maximum time between the
end of defrost and the restarting of the real room temperature display.
Fdt Drip time: (0 to 120 min) time interval between reaching defrost termination
temperature and the restoring of the control’s normal operation. This time allows the
evaporator to eliminate water drops that might have formed due to defrost.
dPo First defrost after start-up: (n; Y)
n= after the idF time,

Y= immediately.
dAF Defrost delay after continuous cycle: (0.0 to 24h00min, res. 10min) time interval
between the end of the fast freezing cycle and the following defrost related to it.
FANS
FnC Fans operating mode: (C-n; o-n; C-Y; o-Y) C-n = runs with the compressor, OFF
during defrost; o-n = continuous mode, OFF during defrost; C-Y = runs with the
compressor, ON during defrost; o-Y = continuous mode, ON during defrost.
Fnd Fans delay after defrost: (0 to 255min) interval between end of defrost and evaporator
fans start.
FCt Temperature differential to avoid fan short cycles: (0 to 59°C; 0 to 90°F) (N.B.: if
FCt=0 function disabled) if the difference of temperature between the evaporator and
the room probes is higher than FCt value, the fans will be switched on.
FSt Fans stop temperature: (-55 to 50°C; -67 to 122°F) setting of temperature, detected
by evaporator probe, above which fans are always OFF.
ALARMS
ALU MAXIMUM temperature alarm:
If ALC=Ab: [ALL to 150.0°C or ALL to 302°F]
If ALC=rE: [0.0 to 50.0°C or 0 to 90°F]
when this temperature is reached the alarm is enabled, after the ALd delay time.
1598024001 XR44CX ISA GB r2.0 21.06.2012.doc XR44CX 3/4
ALL Minimum temperature alarm:
If ALC=Ab: [-55°C to ALU; -67 to ALU]
If ALC=rE: [0.0 to 50.0°C or 0 to 90°F]
when this temperature is reached the alarm is enabled, after the ALd delay time.
AFH Differential for temperature alarm recovery: (0.1 to 25.5°C; 1 to 45°F) intervention
differential for recovery of temperature alarm.
ALd
Temperature alarm delay: (0 to 255 min) time interval between the detection of an
alarm condition and alarm signalling.
dAo Exclusion of temperature alarm at start-up: (0.0 to 24h00min, res. 10min) time
interval between the detection of the temperature alarm condition after instrument power
on and alarm signalling.
OUTPUT RELAYS
oA1 First relay configuration AUX1: (dEF; FAn; ALr; LiG; AUS; onF; db; CP2; dEF2) dEF
= defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay; onF =
always on when instrument on; CP2 = second compressor; dEF2 = second defrost.
oA2 Second relay configuration AUX2: (dEF; FAn; ALr; LiG; AUS; onF; db; CP2; dEF2)
dEF = defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay;
onF = always on when instrument on; CP2 = second compressor; dEF2 = second
defrost.
oA3 Third relay configuration AUX3: (dEF; FAn; ALr; LiG; AUS; onF; db; CP2; dEF2)
dEF = defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay;
onF = always on when instrument on; CP2 = second compressor; dEF2 = second
defrost.
DIGITAL INPUTS
i1P Second digital input polarity: (oP; CL) oP = the digital input is activated by opening
the contact; CL = the digital input is activated by closing the contact.
i1F Second digital input configuration: (EAL; bAL; PAL; dor; dEF; AUS; Htr; FAn; ES)
EAL = external alarm: “EA” message is displayed; bAL = serious alarm “CA” message
is displayed; PAL = pressure switch alarm, “CA” message is displayed; dor = door
switch function; dEF = activation of a defrost cycle; AUS = auxiliary relay activation with
oAx=AUS; Htr = type of inverting action (cooling or heating); FAn = fan; ES = energy
saving.
did Digital input 1 alarm delay: (0 to 255 min) delay between the detection of the external
alarm condition and its signalling.
When i1F= PAL, it is the interval of time to calculate the number of pressure switch
activation.
nPS Number of pressure switch activation: (0 to 15) Number of activation, during the did
or d2d interval, before signalling an alarm event (i1F, i2F=PAL).
If the nPS activation during did or d2d time is reached, switch off and on the
instrument to restart normal regulation.
odC Compressor status when open door: (no; FAn; CPr;F_C;) no = normal;
FAn = normal; CPr = compressor OFF, F_C = compressor OFF.
rrd Outputs restart after door open alarm: (n; Y) n= outputs follow the odC parameter.
Y= outputs restart with a door open alarm.
HES Delta temperature during an Energy Saving cycle: (-30.0 to 30.0°C; -54 to 54°F) it
sets the increasing value of the set point [SET+HES] during the Energy Saving cycle.
OTHER
Adr Serial address: (1 to 247) identifies the instrument address when connected to a
ModBUS compatible monitoring system.
PbC Type of probe: (PtC; ntC) it allows to set the kind of probe used by the instrument:
PtC = PTC probe, ntC = NTC probe.
onF On/Off key enabling: (nU; oFF; ES) nU = disabled; oFF = enabled; ES = not set it.
dP1 Thermostat probe display.
dP2 Evaporator probe display.
dP3 Third probe display- optional.
rEL Software release for internal use.
Ptb Parameter table code: readable only.
8. DIGITAL INPUTS
The free voltage digital input is programmable by the i1F parameter.
8.1 GENERIC ALARM (I1F = EAL)
As soon as the digital input is activated the unit will wait for did time delay before signalling the EAL
alarm message. The outputs statuses don’t change. The alarm stops just after the digital input is de-
activated.
8.2 SERIOUS ALARM MODE (I1F = BAL)
When the digital input is activated, the unit will wait for did delay before signalling the CA alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.
8.3 PRESSURE SWITCH (I1F = PAL)
If during the interval time set by did parameter, the pressure switch has reached the number of
activation of the nPS parameter; the CA pressure alarm message will be displayed. The compressor
and the regulation are stopped. When the digital input is ON the compressor is always OFF. If the
nPS activation in the did time is reached, switch off and on the instrument to restart normal
regulation.
8.4 DOOR SWITCH INPUT (I1F = DOR)
It signals the door status and the corresponding relay output status through the odC parameter:
no = normal (any change); FAn = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan
OFF. Since the door is opened, after the delay time set through parameter doA, the door alarm is
enabled, the display shows the message dA and the regulation restarts is rtr=YES. The alarm
stops as soon as the external digital input is disabled again. With the door open, the high and low
temperature alarms are disabled.
8.5 START DEFROST (I1F = DEF)
It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation
will restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety
time is expired.
8.6 SWITCH THE AUXILIARY RELAY (I1F = AUS)
With oA3 = AUS the digital input switched the status of the auxiliary relay
8.7 ENERGY SAVING (I1F = ES)
The Energy Saving function allows to change the set point value as the result of the SET+ HES
(parameter) sum. This function is enabled until the digital input is activated.
8.8 ON OFF FUNCTION (I1F = ONF)
To switch the controller on and off.
8.9 DIGITAL INPUT POLARITY
The digital input polarity depends on the i1P parameter.
i1P = CL: the input is activated by closing the contact.
i1P = oP: the input is activated by opening the contact
9. TTL SERIAL LINE – FOR MONITORING SYSTEMS
The TTL serial line, available through the HOT KEY connector, allows to connect the instrument to a
monitoring system ModBUS-RTU compatible such as the XWEB500. The connection needs a special
TTL/RS485 adapter: the XJ485CX.
10. INSTALLATION AND MOUNTING
Instrument XR70CX shall be mounted on vertical panel, in a 29x71
mm hole, and fixed using the special bracket supplied.
The temperature range allowed for correct operation is 0 to 60°C.
Avoid places subject to strong vibrations, corrosive gases,
excessive dirt or humidity. The same recommendations apply to
probes. Let air circulate by the cooling holes.
11. ELECTRICAL CONNECTIONS
The instrument is provided with screw terminal block to connect cables with a cross section up to
2.5mm2. Before connecting cables make sure the power supply complies with the instrument’s
requirements. Separate the probe cables from the power supply cables, from the outputs and the
power connections. Do not exceed the maximum current allowed on each relay, in case of heavier
loads use a suitable external relay.
11.1 PROBE CONNECTION
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
infiltration. It is recommended to place the thermostat probe away from air streams to correctly
measure the average room temperature. Place the defrost termination probe among the evaporator
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during
defrost, to prevent premature defrost termination.
12. USE THE HOT KEY
12.1 HOW TO: PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1. Program one controller with the front keypad.
2. When the controller is ON, insert the “HOT-KEY” and push UP button; the “uPL”message
appears followed a by a flashing “End” label.
3. Push SET button and the “End” will stop flashing.
4. Turn OFF the instrument, remove the “HOT-KEY” and then turn it ON again.
NOTE: the “Err” message appears in case of a failed programming operation. In this case push again
button if you want to restart the upload again or remove the “HOT-KEY” to abort the operation.
12.2 HOW TO: PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a pre-programmed “HOT-KEY”into the 5-PIN receptacle and then turn the Controller
ON.
3. The parameter list of the “HOT-KEY” will be automatically downloaded into the Controller
memory. The “doL” message will blink followed a by a flashing “End” label.
4. After 10 seconds the instrument will restart working with the new parameters.
5. Remove the “HOT-KEY”.
NOTE: the message “Err” is displayed for failed programming. In this case turn the unit off and then
on if you want to restart the download again or remove the “HOT-KEY” to abort the operation.
13. ALARM SIGNALS
Message Cause Outputs
P1 Room probe failure Compressor output acc. to par. Con and CoF
P2 Evaporator probe failure Defrost end is timed
P3 Third probe failure Outputs unchanged
HA Maximum temperature alarm Outputs unchanged.
LA Minimum temperature alarm Outputs unchanged.
dA Door open Compressor and fans restarts
EA External alarm Output unchanged.
CA Serious external alarm (i2F=bAL)
All outputs OFF.
CA Pressure switch alarm (i2F=PAL) All outputs OFF
1598024001 XR44CX ISA GB r2.0 21.06.2012.doc XR44CX 4/4
13.1 ALARM RECOVERY
Probe alarms “P1”, “P2” and “P3” start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Check connections before
replacing the probe.
Temperature alarms “HA” and “LA2” automatically stop as soon as the temperature returns to normal
values.
Alarms “EA” and “CA” (with i1F=bAL)recover as soon as the digital input is disabled.
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument.
13.2 OTHER MESSAGES
Pon Keyboard unlocked.
PoF Keyboard locked
noP In programming mode: none parameter is present in Pr1
On the display or in dP2, dP3, dP4: the selected probe is nor enabled
14. TECHNICAL DATA
Housing: self extinguishing ABS.
Case: frontal 32x74 mm; depth 60mm;
Mounting: panel mounting in a 71x29mm panel cut-out
Protection: IP20; Frontal protection: IP65
Connections: Screw terminal block 2.5 mm2wiring
Power supply: 12VAC/DC, ±10%
Power absorption: 3VA max
Display: 3 digits, red LED, 14.2 mm high
Inputs: Up to 3 NTC or PTC probes
Digital inputs: free voltage contact
Relay outputs:
Compressor SPST 16(6) A 250VAC
Defrost: SPST 16(6) A, 250VAC
Buzzer: optional
Data storing: on the non-volatile memory (EEPROM)
Kind of action: 1B
Pollution degree: 2
Software class: A
Rated impulsive voltage: 2500V
Overvoltage Category: II
Operating temperature: 0 to 55°C
Storage temperature: -25 to 60°C
Relative humidity: 20 to 85% (no condensing)
Measuring and regulation range:
NTC probe: -40 to 110°C (-40 to 230°F)
PTC probe: -55 to 150°C (-67 to 302°F)
Resolution: 0.1°C or 1°C or 1°F (selectable)
Accuracy (ambient temp. 25°C): ±0.7°C ±1 digit
15. CONNECTIONS
16. DEFAULT SETTING VALUES
Label
Name Range Value
Level
SEt Set point LS; US -5.0 - - -
HY Differential [0.1 to 25.5°C]
[1 to 45°F] 2.0 Pr1
LS Minimum set point [-55°C to SET]
[-67°F to SET] -40.0 Pr2
US Maximum set point [SET to 150°C]
[SET to 302°F] 110 Pr2
ot Thermostat probe calibration [-12.0 to 12.0°C]
[-21 to 21°F] 0.0 Pr1
P2P
Evaporator probe presence n; Y Y Pr2
oE Evaporator probe calibration [-12.0 to 12.0°C]
[-21 to 21°F] 0.0 Pr2
P3P
Third probe presence n; Y Y Pr2
o3 Third probe calibration [-12.0 to 12.0°C]
[-21 to 21°F] 0 Pr2
odS
Outputs delay at start up 0 to 255 min 0 Pr2
AC Anti-short cycle delay for first
compressor 0 to 50 min 1 Pr1
AC1
Anti-short cycle delay for second
compresor 0 to 50 min 5 Pr1
CCt Continuous cycle duration 0.0 to 24h00min, res. 10 min 0.0 Pr2
CCS
Set point for continuous cycle [-55 to 150.0°C]
[-67 to 302°F] 0.0 Pr2
Con
Compressor ON time with faulty probe 0 to 255 min 15 Pr2
CoF
Compressor OFF time with faulty probe 0 to 255 min 15 Pr2
CF Temperature measurement unit °C; °F °C Pr2
rES Resolution dE; in dE Pr1
Lod
Probe displayed P1; P2; P3; P4; SEt; dtr P1 Pr2
tdF Defrost type EL; in EL Pr2
Label
Name Range Value
Level
dtE First defrost termination temperature [-55 to 50.0°C]
[-67 to 122°F] 8 Pr1
dtS Second defrost termination temperature
[-55 to 50.0°C]
[-67 to 122°F] 8 Pr1
idF Interval between defrost cycles 0 to 120 hours 6 Pr1
MdF
(Maximum) length for first defrost 0 to 255 min 30 Pr1
MdS
(Maximum) length for second defrost 0 to 255 min 30 Pr1
dSd
Start defrost delay 0 to 255 min 0 Pr2
dFd
Displaying during defrost rt; it; SEt; dEF it Pr2
dAd
MAX display delay after defrost 0 to 255 min 30 Pr2
Fdt Draining time 0 to 255 min 0 Pr2
dPo
First defrost after start-up n; Y n Pr2
dAF
Defrost delay after fast freezing 0.0 to 24h00min, res. 10 min 0.0 Pr2
FnC
Fan operating mode C-n; o-n; C-Y; o-Y o-n Pr2
Fnd
Fan delay after defrost 0 to 255 min 0 Pr2
FCt Differential of temperature for forced
activation of fans
[0 to 50°C]
[0 to 90°F] 0 Pr2
FSt Fan stop temperature [-55 to 50.0°C]
[-67 to 122°F] 50 Pr2
ALC
Temperat. alarms configuration rE; Ab Ab Pr2
ALU
MAXIMUM temperature alarm Rel: [0.0 to 50.0°C] [0 to 90°F]
AbS: [ALL to 150°C] [ALL to 302°F] 110.0
Pr1
ALL
Minimum temperature alarm Rel: [0.0 to 50.0°C] [0 to 90°F]
AbS: [-55°C to ALU] [-67°F to ALU] -50.0 Pr1
AFH
Differential for temperat. alarm recovery [0.1 to 25.5°C]
[1 to 45°F] 1.0 Pr2
ALd
Temperature alarm delay 0 to 255 min 10 Pr2
dAo
Delay of temperature alarm at start up 0.0 to 24h00min, res. 10 min 1.3 Pr2
oA1
AUX1 relay configuration
dEF = defrost; FAn= do not select it;
ALr = alarm; LiG =Light; AUS =AUX;
onF=always on; db = neutral zone;
CP2 = second compressor;
dF2 = second defrost.
CP2 Pr2
oA2
AUX2 configuration
dEF = defrost; FAn= do not select it;
ALr = alarm; LiG =Light; AUS =AUX;
onF=always on; db = neutral zone;
CP2 = second compressor;
dF2 = second defrost.
dEF Pr2
oA3
AUX3 relay configuration
dEF = defrost; FAn= do not select it;
ALr = alarm; LiG =Light; AUS =AUX;
onF=always on; db = neutral zone;
CP2 = second compressor;
dF2 = second defrost.
DF2 Pr2
i1P Digital input polarity oP; CL oP Pr1
i1F Digital input configuration EAL; bAL; PAL; dor; dEF; AUS; Htr;
FAn; ES. bAL Pr1
did Digital input alarm delay 0 to 255 min 0 Pr1
nPS
Number of activation of pressure switch 0 to 15 15 Pr2
odC
Compress and fan status when open
door no; FAn; CPr; F-C no Pr2
rrd Regulation restart with door open alarm n; Y Y Pr2
HES
Differential for Energy Saving [-30 to 30°C]
[-54 to 54°F] 0 Pr2
Adr Serial address 0 to 247 1 Pr2
PbC
Kind of probe PtC; ntC ntC Pr2
dP1
Room probe display probe value - Pr1
dP2
Evaporator probe display probe value - Pr1
dP3
Third probe display probe value - Pr1
rEL Software release read only - Pr2
Ptb Map code read only - Pr2

Other Emerson Controllers manuals

Emerson Fisher FIELDVUE DVC6200p Configuration guide

Emerson

Emerson Fisher FIELDVUE DVC6200p Configuration guide

Emerson FISHER 657NS User manual

Emerson

Emerson FISHER 657NS User manual

Emerson Vilter Vission 20/20 Operation manual

Emerson

Emerson Vilter Vission 20/20 Operation manual

Emerson dixell XW90LT Wiring diagram

Emerson

Emerson dixell XW90LT Wiring diagram

Emerson FISHER 657 User manual

Emerson

Emerson FISHER 657 User manual

Emerson VAREC Series Manual

Emerson

Emerson VAREC Series Manual

Emerson A36 Manual

Emerson

Emerson A36 Manual

Emerson Fisher EZR series User manual

Emerson

Emerson Fisher EZR series User manual

Emerson Dixell XR20T User manual

Emerson

Emerson Dixell XR20T User manual

Emerson REGAL 3F User manual

Emerson

Emerson REGAL 3F User manual

Emerson EC2-712 User manual

Emerson

Emerson EC2-712 User manual

Emerson Fisher 4660 User manual

Emerson

Emerson Fisher 4660 User manual

Emerson Fisher LR125 Series User manual

Emerson

Emerson Fisher LR125 Series User manual

Emerson unidrive m201 User manual

Emerson

Emerson unidrive m201 User manual

Emerson FISHER LR128 Series User manual

Emerson

Emerson FISHER LR128 Series User manual

Emerson Fisher 1301 Series User manual

Emerson

Emerson Fisher 1301 Series User manual

Emerson Sempell series User manual

Emerson

Emerson Sempell series User manual

Emerson Unidrive M700 User manual

Emerson

Emerson Unidrive M700 User manual

Emerson dixell WING XW260L Wiring diagram

Emerson

Emerson dixell WING XW260L Wiring diagram

Emerson Dixell XR70T Wiring diagram

Emerson

Emerson Dixell XR70T Wiring diagram

Emerson Bettis TEC2 User manual

Emerson

Emerson Bettis TEC2 User manual

Emerson MCi210 User manual

Emerson

Emerson MCi210 User manual

Emerson EC20 Series User manual

Emerson

Emerson EC20 Series User manual

Emerson Tartarini M Series User manual

Emerson

Emerson Tartarini M Series User manual

Popular Controllers manuals by other brands

ADB Safegate IDM 8000 user manual

ADB Safegate

ADB Safegate IDM 8000 user manual

CS-Lab SimDrive M4-H075K user guide

CS-Lab

CS-Lab SimDrive M4-H075K user guide

ONV ONV-IoT9000 product manual

ONV

ONV ONV-IoT9000 product manual

Chziri ZRMV user manual

Chziri

Chziri ZRMV user manual

Honeywell T775 Series Application guide and cross reference

Honeywell

Honeywell T775 Series Application guide and cross reference

Asparion D400T manual

Asparion

Asparion D400T manual

Halytech Illuminator user manual

Halytech

Halytech Illuminator user manual

Mitsubishi Electric MELSEC Q Series user manual

Mitsubishi Electric

Mitsubishi Electric MELSEC Q Series user manual

Heatpol H+E INSTALLATION MANUAL AND USER MANUAL

Heatpol

Heatpol H+E INSTALLATION MANUAL AND USER MANUAL

Omron NJ501 series Connection guide

Omron

Omron NJ501 series Connection guide

TyloHelo SaunaChrome Installation and user manual

TyloHelo

TyloHelo SaunaChrome Installation and user manual

Kelly KLS14801-8080N user manual

Kelly

Kelly KLS14801-8080N user manual

VIS DirectForce Pro installation manual

VIS

VIS DirectForce Pro installation manual

Data Technology 5150CRH installation guide

Data Technology

Data Technology 5150CRH installation guide

Argus Cordex CXC Setup

Argus

Argus Cordex CXC Setup

Nitto Seiko HC100 Operation manual

Nitto Seiko

Nitto Seiko HC100 Operation manual

Inventronics DALI PRO CONT-4 RTC manual

Inventronics

Inventronics DALI PRO CONT-4 RTC manual

Zamel exta ZIM-12/25 instruction manual

Zamel

Zamel exta ZIM-12/25 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.