EMKO ESM-3712-CN User manual

ESM-3712-CN 77x35 DIN Size Cooling Controller
ENGLISH
- 4 Digits Display
- NTC Input or PTC Input (Must be determined in order.)
- Adjustable temperature offset
- Set value boundaries
- Operation selection of compressor operates continuously,
stops or operates periodically in case of sensor defect
- Compressor protection delays
- Defrost time easily changeable from front panel
- Manual defrost capability from front panel
- Defrost parameters
- Alarm parameters
- Adjustable internal buzzer according to the defrost, sensor
defect and alarm status
- Defrost time and/or manual defrost and/or temperature set
value protection
- Password protection for programming section
- Installing parameters using Prokey
- Remote access, data collecting and controlling with Modbus RTU
- Having CE mark according to European Norms
ESM-3712-CN 77 x 35 DIN Size
Digital , ON / OFF Cooling Controller
Instruction Manual. ENG ESM-3712-CN 01 V06 11/15

ENGLISH
Operating Temperature : 0 to 50 °C
Max. Operating Humidity : 90% Rh (non-condensing)
Altitude : Up to 2000 m.
Forbidden Conditions
Corrosive atmosphere
Explosive atmosphere
Home applications (The unit is only for industrial applications)
c
1.2 General Specifications
1.Preface
Application Fields
Food
Machine production industries
etc...
ESM-3712-C
Applications
Refrigerators
Air Conditioning
Storages
Freezers
etc...
2
Cooling Function
ON/OFF Operation
1.1 Environmental Ratings
Digital Input
Power Supply
Input
NTC, PTC
230V ( %15) 50/60HzV ±
Optional Supply Voltage
- 30 V Z
115 V (±%15) 50/60Hz,
24 V (±%15) 50/60Hz,
10
V
V
Standard
ESM-3712-CN series cooling controllers are designed for controlling cooling process. They
can be used in many applications with their easy-use, On / Off control form and defrost
properties. Some application and application fields which they are used are below:
Evaporator
Sensor Input
NTC,PTC
Cabinet
Sensor Input
Configurable Digital
Input
- Stopping fan
- Stopping compressor
- Stopping fan and
compressor
- Manual defrost
- Alarm
Compressor Input
Defrost Output
Fan Output
Defrost Function
ON/OFF Operation
Fan Control Output
ON/OFF Operation

3
A visual inspection of this product for possible damage occurred during shipment is
recommended before installation. It is your responsibility to ensure that qualified mechanical
and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power off the
system and separate the electrical connection of the device from the system.
The unit is normally supplied without a power supply switch or a fuse. Use power switch and fuse
as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to prevent
failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble with the
unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may results in
malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During putting equipment in hole on the metal panel while mechanical installation some metal
burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s fixing clamps. Do not do the montage
of the device with inappropriate fixing clamp. Be sure that device will not fall while doing the
montage.
It is your responsibility if this equipment is used in a manner not specified in this instruction
manual.
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts
from the delivery date. This warranty is in force if duty and responsibilities which are determined
in warranty document and instruction manual performs by the customer completely.
Repairs should only be performed by trained and specialized personnel. Cut power to the
device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in
ethyl alcohol or water to clean the external plastic case.
1.3 Installation
1.4 Warranty
1.5 Maintenance
1.6 Manufacturer Company
Manufacturer Company Name :
Emko Elektronik A.S .DOSAB Karanfil Sk.No:6 16369 BURSA/TURKEY
Phone: +90 224 261 19 00
Fax: +90 224 261 19 12
Repair and maintenance service information:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
ENGLISH

ENGLISH
2.2 Panel Cut-Out
2. General Description
2.1 Front View and Dimensions of ESM-3712-CN Cooling Controller
Mounting Clamp
Panel Surface
(maximum thickness 15 mm / 0.59 inch)
Front Panel
IP65 protection
NEMA 4X
4
76 mm / 3 inch
34,5 mm / 1.36 inch
65 mm / 2.56 inch
6 mm / 0.24 inch
Maximum 15 mm / 0.59 inch
110 mm / 4.33 inch (min)
71 mm / 2.79 inch
29 mm / 1.14 inch
50 mm / 1.97 inch (min)
ü
OF
OCP
S
ESM-3712CNESM-3712CN

5
1.Switch off the device.
2.Put in PROKEY then energize the device.
3.When the device is energized, the parameter values in PROKEY, start downloading to the device
automatically. At first, message is shown on the display, when loading has finished,
message is shown.
4.After 10 seconds device starts to operate with new parameter values.
5.Remove the PROKEY.
1-Before mounting the device in your panel, make
sure that the cut-out is of the right size.
2-Insert the device through the cut-out. If the
mounting clamps are on the unit, put out them before
inserting the unit to the panel.
3- Insert the mounting clamps to the fixing sockets
that located left and right sides of device and make
the unit completely immobile within the panel
1-Pull mounting clamps from left and
right fixing sockets.
2-Pull the unit through the front side of
the panel
Before starting to remove the unit
from panel, power off the unit and
the related system.
c
2.3 Panel Mounting
3. Using Prokey
DOWNLOADING FROM DEVICE TO PROKEY
1.The device is programmed by using the parameters.
2.Energize the device then put in PROKEY and press button. Message is shown on the
display. When the loading has finished, message is shown.
3.Press any button to turn back to main operation screen.
4.Remove the PROKEY.
DOWNLOADING FROM PROKEY TO DEVICE
NOTE: message is shown when an error occurs while programming. If you want to reload, put
in PROKEY and press button. If you want to quit, remove PROKEY and press button. The
device will turn back to main operation screen.
NOTE: message is shown when an error occurs while programming. If you want to reload,
switch off the device and put in PROKEY then energize the device. If you want to quit remove
PROKEY and press button. The device will turn back to main operation screen.
TO USE PROKEY, VALUE OF THE PrC PARAMETER MUST BE ‘0’.
IF PrC=1 AND BUTTON IS PRESSED MESSAGE WILL BE SHOWN. 10s. LATER
DEVICE TURNS BACK TO THE MAIN OPERATION SCREEN OR YOU CAN PRESS SET
BUTTON TO TURN BACK TO MAIN OPERATION SCREEN.
1
2
3.Optinal Accessories
RS-485 Communication
Interface
1.RS-485 Module 2.PROKEY Programming Module
The device is programmed (Upload or
Download) by using the parameters.
and Removing
3
1
2
ESM-3712CN
ESM-3712CN
ENGLISH

ENGLISH
PROKEY
RS-485
or
5678 9 10
a
16(8)A
@250VV1HP
LN
230 VV ± 15%
50/60Hz - 1.5VA
2341
COMP.
NTC
L
N
16A T Sigorta
4.2 Device Label and Connection Diagram
4. Electrical Wiring Diagram
4.1 Supply Voltage Input Connection of the Device
Note-1 : External fuse is recommended.
Make sure that the power supply voltage is the same
indicated on the instrument.
Switch on the power supply only after that all the electrical
connections have been completed.
Supply voltage range must be determined in order. While
installing the unit, supply voltage range must be controlled
and appropriate supply voltage must be applied to the unit.
c
There is no power supply switch on the device. So a power
supply switch must be added to the supply voltage input.
Power switch must be two poled for seperating phase and
neutral, On/Off condition of power supply switch is very
important in electrical connection.
External fuse that on Vpower supply inputs must be on
phase connection.
External fuse that on Zpower supply inputs must be on (+)
connection.
c
Relay Output
21 3 54 6 87 9 10
L N
a
Power Supply Input Cabinet and Evaporator Temperature
Sensor Input (NTC or PTC)
230VV CONNECTION DIAGRAM
6
Power Supply Connection
c
a
EXTERNAL
FUSE
(1A T)
Note-1
Supply
Switch
Supply Voltage
56
LN
230V ( %15) 50/60Hz ,
115V ( %15) 50/60Hz ,
24V ( %15) 50/60Hz ,
Z
V ±
V ±
V ±
10...30 V - 1.5 W
230V ( %15) 50/60Hz ,
115V ( %15) 50/60Hz ,
Z
V ±
V ±
10...30 V - 1.5 W
Must be determined in order.
Must be determined in order.
Digital Input
24V ( %15) 50/60Hz ,V ±
NTC
2x5A@ 250VV

5.Front Panel Definition and Accessing to the Menus
BUTTON DEFINITIONS
1. Increment Button :
** It is used to increase the value in the Set screen, Defrost screen and Programming mode.
2. Decrement, Silencing Buzzer and Downloading to Prokey Button :
** It is used to decrease the value in the Set screen, Defrost screen and Programming mode.
** It is used to silence the buzzer.
** If Prc =0, it is used to download from device to prokey.
3. Defrost Button :
** In the main operation screen; if this button pressed, defrost time value will be displayed.
**In the main operation screen; if this button pressed for 3 seconds, manual defrost starts.
4. Set Button :
** In the main operation screen; if this button pressed, set value will be displayed. Value can be
changed using increment and decrement buttons. When Set button pressed again, value is
saved and returns back to main operating screen.
** To access the programming screen; in the main operation screen, press this button for 5
seconds.
** It is used to saving value in the Set screen, Defrost screen and programming screen.
LED DEFINITIONS
5. Compressor output led :
** This led indicates that compressor output is active. If any of compressor protection time
active, this led blinks.
6.Defrost led :
** This led indicates that defrost output is active.
** Blinks once in a second while Defrost delay time.
** Blinks (5 Hz) while entering Defrost time value.
7.Alarm led :
** It is active when low alarm and high alarm statuses.
8.Celcius led :
o
** Indicates that device is in C mode.
9.Fahrenheit led :
o
** Indicates that device is in F mode.
10.Set led :
** Indicates that device is in Set value changing mode.
11.Program led :
**Blinks in programming mode .
7
ENGLISH

ENGLISH
6. Changing and Saving Temperature Set Value
6.1 Changing and Saving Defrost Time Set Value
Main Operation Screen
When SET button pressed ‘’S’’ led will
be active and temperature set value will
be displayed.
SET Value Screen
Temperature set value can
be changed with increment
and decrement buttons.
When SET button pressed
temperature set value can be saved.
‘’S’’ will be inactive and goes back to
main operation screen.
Main Operation Screen
Temperature set value parameter (Default=10) MODBUS ADDRESS:40001
Temperature set value, can be programmed between minimum temperature set value and
maximum temperature set value .
When defrost button is pressed, defrost
time set value is shown and defrost
output led starts to fast blink (5 Hz).
Press set button for saving the defrost
time set value
Defrost time set value is saved, defrost
output led stop the fast blink (5 Hz), main
operation screen is shown.
Main Operating Screen
Defrost Time Value Screen
Defrost Time Value Screen
If no operation is performed in defrost time set value changing mode and temperature set
value changing mode for 20 seconds, device turns to main operation screen automatically.
i
Change the defrost time set
value with increment and
decrement buttons.
Main Operating Screen
8
OF
OCP
S
ü
ESM-3712CN
OF
OCP
S
ü
ESM-3712CN
OF
OCP
S
ü
ESM-3712CN
OF
OCP
S
ü
ESM-3712CN
OF
OCP
S
ü
ESM-3712CN
OF
OCP
S
ü
ESM-3712CN
OF
OCP
S
ü
ESM-3712CN
OF
OCP
S
ü
ESM-3712CN

6.2 Programming Mode Parameter List
Hysteresis Parameter for Compressor Output ( Default = 1 )
MODBUS ADDRESS:40004
from 1 to 20°C for NTC (-50°C, 100°C) or PTC (-50°C, 150°C)
from 1 to 36°F for NTC (-58°F, 212°F) or PTC (-58°F, 302°F)
from 0.1to 10.0°C for NTC (-50.0°C,100.0°C) or PTC (-50.0°C,150.0°C)
from 0.1 to 18.0°F for NTC (-58.0°F,212.0°F) or PTC(-58.0°F,302.0°F)
Defrost Time Parameter
It can be adjusted from 0 to 999 minutes.
If it is selected 0 automatic or manual defrost is not performed.
( Default =10 ) MODBUS ADDRESS:40011
Defrost Repeat Cycle Parameter
It can be adjusted from 1 to 99 hours.
( Default = 1 ) MODBUS ADDRESS:40012
In ON/OFF control algorithm,
temperature value is tried to keep equal
to set value by opening or closing the last
control element. ON/OFF controlled
system, temperature value oscillates
continuously. Temperature value’s
oscillation period or amplitude around set
value changes according to controlled
system. For reducing oscillation period of
temperature value, a threshold zone is
formed below or around set value and
this zone is named hysteresis.
ON
OFF
Temperature
Control
Output
Set
HSt
Time
HSt
Time
Minimum Temperature Set Value Parameter(Default =Minimum Value of Device
Scale) MODBUS ADDRESS:40005
Temperature set value can not be lower than this value. This parameter value can be
adjusted from minimum value of device scale to maximum temperature set value
parameter
Maximum Temperature Set Value Parameter
(Default = Maximum Value of Device Scale) MODBUS ADDRESS:40006
Temperature set value can not be greater than this value.
This parameter value can be adjusted from minimum temperature set value parameter
to maximum value of the device scale.
Cabinet Sensor Offset Parameter ( Default = 0 ) MODBUS ADDRESS:40007
From -20 to 20 °C for NTC(-50°C, 100°C) or PTC(-50°C, 150°C),
From -36 to 36 °F for NTC(-58°F, 212°F) or PTC(-58°F, 302°F),
From -10.0 to 10.0°C for NTC(-50.0°C,100.0°C) or PTC(-50.0°C,150.0°C),
From -18.0 to 18.0°F for NTC(-58.0°F,212.0°F) or PTC(-58.0°F,302.0°F).
Defrost Type Selection Parameter ( Default =0 ) MODBUS ADDRESS:40010
Electric defrost.
Hot gas defrost.
Evaporator Sensor Selection Parameter ( Default =1 ) MODBUS ADDRESS:40008
Evaporator sensor is inactive.
Evaporator sensor is active.
Evaporator Sensor Offset Parameter ( Default = 0 ) MODBUS ADDRESS:40009
If evaporator sensor selection parameter is 1, then this parameter is observed.
From -20 to 20°C for NTC(-50°C, 100°C) or PTC(-50°C, 150°C) ,
From -36 to 36°F for NTC(-58°F, 212°F) or PTC(-58°F, 302°F),
From -10.0 to 10.0°C for NTC(-50.0°C,100.0°C) or PTC(-50.0°C,150.0°C),
From -18.0 to 18.0 °F for NTC(-58.0°F,212.0°F) or PTC(-58.0°F,302.0°F).
9
Decimal Seperator Enabling Parameter ( Default = 0 ) MODBUS ADDRESS:40003
Disable.
Enable.
Temperature Unit Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40002
°C selected.
°F selected.
ENGLISH

ENGLISH
Defrost at Power On Selection and Defrost Delay Parameter
It can be adjust from 0 to 99 minutes. When tihs parameter is 0, if decrement button is
pressed, is observed. In this condition system goes through a defrost cycle at the
end of the defrost repeat cycle time after power on.If this parameter value is between
0 and 99, then system goes through a defrost cycle at the end of the this parameter time
after power on.
( Default = ) MODBUS ADDRESS:40014
Compressor Start Delay at Power On Parameter ( Default = 0 )
MODBUS ADDRESS:40019
When power is first applied to the device,This time delay must be expired for activation of
compressor. It can be adjusted from 0 to 20 minutes.
Minimum Compressor OFF Time Parameter ( Default = 0 )MODBUS ADDREDS:40021
When compressor is inactive, this time delay must be expired for activation of the
compressor. It can be adjusted from 0 to 20 minutes.
Cabinet Probe Defect Parameter ( Default = 0 ) MODBUS ADDRESS:40023
Compressor Active Time in Case of Cabinet Probe Defect Parameter (Default = 0)
MODBUS ADDRESS:40024
If cabinet probe defect parameter is 2, then this parameter is observed.
It canbe adjusted from to 99 minutes.
Compressor is OFF in case of cabinet probe defect.
Compressor is ON in case of cabinet probe defect.
Compressor operates periodically according to and time periods
in case of cabinet probe defect.
Compressor Start-Start Delay Parameter ( Default = 0 )
MODBUS ADDRESS:40020
This time delay must be expired between two activation of the compressor.
It can be adjusted from 0 to 20 minutes.
Display Status During Defrost Parameter ( Default = 3 )
MODDBUS ADRESS:40015
The cabinet temperature value is displayed during defrost.
Cabinet temperature value at the start of the defrost is displayed during defrost.
Temperature set value is displayed during defrost.
is displayed to indicate the defrost is in progress.
Dripping Time Parameter
This parameter defines for dripping time after defrost.
It
(Default = 2) MODBUS ADDRESS:40017
can be adjusted from 0 to 15 minutes.
Temperature Alarm Delay After Dripping Parameter (Default = 0) MODBUS
ADDRESS:40018
This parameter defines the delay for temperature alarm being active after dripping time
completion. It can be adjusted from 0 to 15 minutes.
Minimum Compressor ON Time Parameter ( Default = 0 )MODBUS ADRES:40022
When compressor is active, this time delay must be expired for deactivation of the
compressor. It can be adjusted from 0 to 20 minutes.
Displaying Current Temperature Delay After Defrost Parameter
This parameter defines the delay for displaying current temperature being active after
defrost.
( Default = 0 )
MODDBUS ADRESS:40016
It can be adjusted from 0 to 255 minutes.
Defrost Stopping Temperature Parameter (Default = 2°C) MODBUS ADDRESS:40013
For evaporator sensor selection parameter is 1 (evaporator sensor is active),
while defrost operation, if evaporator temperature reaches to temperature that defined at
this parameter in a shorter time than parameter, then defrost operation stops.
10
Compressor İnactive Time in Case of Cabinet Probe Defect Parameter
( Default = 0 ) MODBUS ADDRESS:40025
If cabinet probe defect parameter is 2, then this parameter is observed.
It canbe adjusted from to 99 minutes.

ENGLISH
Temperature Alarm Maximum Parameter
(Default =Maximum Value of Device Scale ) MODBUS ADRES:40028
For = 1, this parameter value can be adjusted from temperature alarm minimum
parameter value to maximum value of device scale.For = 2, this parameter
value is can be adjusted 0 to %50 of the device scale.
Temperature Alarm On Delay Time Parameter
Temperature Alarm On Delay Time can be defined with this parameter. It can be
adjusted from 0 to 99 minutes.
(Default = 0)
MODBUS ADDRESS:40029
Temperature Alarm Delay After Power On Parameter
It can be adjusted from 0 to 99 minutes.
(Default = 0)
MODBUS ADDRESS:40030
When power is first applied to the device, this time delay must be expired for activation of
temperature alarm.
Fan Operation Selection Parameter (Default = 1) MODBUS ADDRESS:40031
Fan is OFF.
Fan is ON.
Fan operates according to the evaporator sensor temperature value.
Fan Stopping Temperature Parameter
Fan stopping temperature can be defined with this parameter.
(Default = 2°C) MODBUS ADDRESS:40032
It can be adjusted from
minimum value to maximum value of device scale.
Hsyteresis Parameter for Fan Output (Default = 1 ) MODBUS ADDRESS:40033
From 1 to 20°C for NTC (-50°C, 100°C) , from 1 to 36°F for NTC (-58°F, 212°F), from
0.1 to 10.0°C for NTC (-50.0°C,100.0°C), from 0.1 to 18.0°F for NTC (-58.0°F,212.0°F)
Fan Activity Selection According to the Compressor and Defrost
(Default = 0) MODBUS ADDRESS:40034
Fan operates according to the parameter.
Fan operates according to the parameter, but fan is stopped if
commpressor is stops.
Fan operates according to the parameter, but fan is stopped during
defrost and dripping time.
Fan operates according to the parameter.If compressor stops, during
defrost and dripping operations fan stops.
Fan Delay Time After Completion of Dripping Time Parameter (Default = 2)
MODBUS ADDRESS:40035
Fan Delay Time After Completion of Dripping Time is defined with this parameter.
It can be adjusted from 0 to 15 minutes.
Fan operates according to the ( cabinet - evaporator ) temperature value.
11
Temperature Alarm Minimum Parameter
For = 1, this parameter value can be adjusted from minimum value of device
scale to temperature alarm maximum parameter value. For = 2, this
parameter value can be adjusted 0 to %50 of the device scale.
(Default = Minimum Value of Device Scale) MODBUS ADRES:40027
Relative alarm is selected. Alarm operates according to the set value. If cabinet
temperature value is below ( Set - ) or above ( Set + ), alarm ocurs.
Temperature Alarm Function Selection Parameter ( Default = 0 )
MODBUS ADRES:40026
Temperature alarm function is inactive.
Absolute alarm is selected. If temperature lower than and higher than
, then alarm is on.

ENGLISH
Digital Input Contact Selection Parameter ( Default = 1 ) MODBUS ADDRESS:40036
Digital input is inactive.
NO “normally open” digital input is active when the contact is closed.
NC “normally close” digital input is active when the contact is opened.
Digital Input Function Selection Parameter
If digital input contact selection parameter
( Default = 0 ) MODBUS ADDRESS:40037
value = 0, this parameter is not observed.
When the digital input is active, fan is stopped. screen will be displayed.
When the digital input is active, compressor is stopped. screen will be
displayed and defrost operation will be disabled. If Buzzer function selection
parameter = 2 or 4 buzzer is active.
When the digital input is active, first fan stops, 10 seconds later compressor
stops. will be displayed at main operation screen.
When the digital input is active, defrost starts.
When the digital input is active, alarm will be active. will be displayed at
main operation screen. If Buzzer function selection parameter = 2 or 4
buzzer is active.
12
Buzzer Function Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40039
Buzzer is inactive.
Buzzer is active during defrost operation.
Buzzer is active if an alarm occurs.
Buzzer is active during cabinet sensor failures.
Buzzer is active during defrost, alarm or cabinet sensor failures.
Button Protection Parameter ( Default = 0 ) MODBUS ADDRESS:40041
There is no protection.
Defrost time set value can not be changed and manual defrost is not available.
Temperature set value can not be changed.
Defrost time set value and temperature set value can not be changed and
manual defrost is not available.
Buzzer Active Time
If buzzer function selection parameter
Buzzer active time can be define with this parameter. It can be adjusted from 1 to 99
minutes. When this parameter is 1, if decrement button is pressed, is observed. In
this condition buzzer is active till buzzer silence button is pressed.
( Default = ) MODBUS ADDRESS:40040
value = 0, this parameter is not observed.
Programming Mode Accessing Password
It is used for accessing to programming mode. It can be adjusted from 0 to 999. If it is 0,
password is not entered for accessing to the parameters. If password is ‘12’ only ,
, can be accesible.
( Default = 0 ) MODBUS ADDRESS:40044
Digital Input Effect Time Parameter
If digital input contact selection parameter
( Default = ) MODBUS ADDRESS:40038
value = 0, this parameter is not observed.
For digital input function selection parameter = 0 or 2, maximum effect time of digital
input is determined with this parameter. It can be adjust from 0 to 120 minutes. When this
parameter is 0, if decrement button is pressed, is observed. In this condition the
effect will be ended when digital input is deactive.
Defrost time can not be changed,Defrost ON/OFF operation is available.
PROKEY communication selected.
Communication Mode Selection Parameter( Default = 0 ) MODBUS ADRESS:40042
RS485 communication selected.
Slave ID Parameter ( Default = 1 ) MODBUS ADDRESS=40043
Device communication address parameter (1 to 247)

ENGLISH
6.3 Operation Graphics of ESM-3712-CN Cooling Controller
Time
Time
Time
Time
Time
Compressor start delay at power on parameter value 1,
Compressor start - start delay parameter value 1,
Minimum compressor OFF time parameter value 1,
Minimum compressor ON time parameter value 1 ise;
Time
Time
Time
Time
13
Power
Defrost
Output
Led
Defrost
Output
°C
Evap.
Sensor
Temp.
4.7.1 Defrost Çıkışı Çalışma Grafiği
4.7.2 Kompresör Çıkışı Çalışma Grafiği
Power
Hst
SET
Comp.
Output
Led
°C
Comp.
Output
Cab.
Sensor
Temp.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
1-
2-
Defrost time parameter value 1,
Defrost repeat cycle parameter value 1,
Defrost at power on selection and defrost delay parameter value 1,
Dripping time parameter value 1 ise;
Manual defrost button
starts time

ENGLISH
When SET button is pressed for 5
seconds, “P” led starts to blink. If
programming mode entering
password is different from 0,
programming mode entering screen
will be observed.
Main Operating Screen
Programming Screen
Change the value with increment
and decrement buttons.
Compressor Output
Hysteresis Parameter Value
Press SET button for accessing to the parameter
value. Press increment button for accessing to
the next parameter, press decrement button for
accessing to the previous parameter
Press set button for saving
the parameter.
Press increment button for accessing to the
next parameter, press decrement button for
accessing to the previous parameter
Password Entering Screen
Programming Mode
Entering Screen
Press SET button for
accessing to the
password entering screen.
Password Entering Screen
Enter programming mode accessing
password with increment and decrement
Note-2: If programming mode accessing password is 0 parameter values can be seen.But
parameter values can not be changed.
Press SET/OK button for
entering the password.
Note1: If programming mode
accessing password is 0,
Temperature Unit Selection
Screen is observed
instead of programming
screen accessing password
Compressor Output
Hysteresis Parameter Value
If no operation is performed in programming mode for 20 seconds, device turns to main
operation screen automatically..
i
Compressor Output
Hysteresis Parameter
6.4 Entering To The Programming Mode, Changing and Saving Parameter
14
7. Failure Messages in ESM-3712-CN Cooling Controller
1- message blinking . S
no sensor connection. While this message shown on this display, if buzzer function selection
parameter is 3 or 4, internal buzzer starts to operate.
.Cabinet temperature sensor failure ensor connection is wrong or there is
OF
OCP
S
ü
ESM-3712CN
OF
OCSP
ü
ESM-3712CN
OF
OCSP
ü
ESM-3712CN
OF
OCSP
ü
ESM-3712CN
OF
OCSP
ü
ESM-3712CN
OF
OCSP
ü
ESM-3712CN
OF
OCSP
ü
ESM-3712CN
OF
OCSP
ü
ESM-3712CN

ENGLISH
6- message blinking.
When the digital input is active and digital input function selection parameter value is 1 or 4
message starts to blink. If buzzer function selection parameter is 2 or 4, internal buzzer
starts to operate.
3 sn.
5- message blinking.
When the digital input is active and digital input function selection parameter value is 0 or 2
message starts to blink.
2-
Evaporator temperature sensor failure. sensor connection is wrong or there is no sensor connection.
message blinking.
15
7. Failure Messages in ESM-3712-CN Cooling Controller
3- message blinking.
For absolute alarm, if cabinet temperature sensor value is lower than temperature alarm minimum
parameter value and for relative alarm, if cabinet temperature sensor value is lower than
(Temperature Set - ), then message starts to blink.If buzzer function selection
parameter is 2 or 4, internal buzzer starts to operate.
4- message blinking.
For absolute alarm, if cabinet temperature sensor value is higher than temperature alarm maximum
parameter value and for relative alarm, if cabinet temperature sensor value is higher than
(Temperature Set + ), then message starts to blink. If buzzer function selection
parameter is 2 or 4, internal buzzer starts to operate.
While defrost time parameter value 1, button
protection parameter value = 0 or 2 and defrost output is
inactive, in main operation screen if defrost button is pressed
for 3 seconds manual defrost will be active.
While digital input function selection parameter value =3
if digital input contact selection parameter value =1
(normally open NO) and the K switch is getting closed, or if
digital input contact selection parameter value =2
(normally close NC) and the K switch is getting opened
manual defrost will be active
9.Modbus Adresses of Device Status Parameters (Read Input Register)
MODBUS ADRES:30001 Cabinet Temperature Value
MODBUS ADRES:30002 Evaporator Temperature Value
o
MODBUS ADRES:30003 Led Status : 0.bit C Led, 4.bit Fan Led, 5.bit Defrost Led,
6.bit Compressor Led, 7.bit Alarm Led
13.bit Programming Led, 14.bit Set Led
MODBUS ADRES:30004 Device Status : 0.bit Alarm Status, 1.bit Buzer Status
2.bit Cabinet Sensor Lost Status,
3.bit Evaporator Sensor Lost Status
7.bit Defrost Status
MODBUS ADRES:30005 Output Status : 0.bit Compressor Output
1.bit Defrost Output
2.bit Fan Output
MODBUS ADRES:30006 Device Type and Version
A
A
A
A
A
A
A
DIGITAL INPUT
8. Manual Defrost Operation with Defrost Button
8.1 Manual Defrost Operation with Digital Input
10. Specifications
789
K
Device Type : Cooling Controler
Housing&Mounting: 76 mm x 34.5 mm x71 mm plastic housing for panel
Panel cut-out is 71 x 29 mm
Protection Class : NEMA 4X (IP65 at front, IP20 at rear )
OF
OCP
S
ü
ESM-3712CN

ENGLISH
Weight : Approximately 0.2 Kg
Environmental Ratings : Standard, indoor at an altitude of less than 2000 meters
with none condensing humidity.
o o o o
Storage / Operating Temperature : -40 C to +85 C / 0 C to +50 C
Storage / Operating Humidity : 90 % max. (None condensing)
Installation : Fixed installation
Overvoltage Category : II.
Pollution Degree : II, office or workplace, none conductive pollution
Operating Conditions : Continuous
Supply Voltage and Power :
: 115
: 24 , 10-30
Temperature Sensor Inputs : NTC or PTC
NTC Input Type or PTC Input Type: NTC (10 kW @25 °C ) or PTC (1000 W @25 °C )
Accuracy : ±1 % of full scale for thermoresistance
Sensor Break Protection : Upscale
Sampling Cycle : 3 samples per second
Control Form : ON / OFF
Relay Outputs : 16(8) A@250 V V at resistive load(Compressor Output)
5 A@250 V V at resistive load(Defrost and Fan Output)
Display : 14 mm Red 4 digit LED Display
o o
LED : S (Green), P (Green), C (Yellow), F(Yellow),
Alarm(Red), Defrost Output (Red), Fan Output (Red)
Compressor Ouput (Red),
Internal Buzzer : 83dB
Approvals :
230V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA VZ 1.5W
V ±
V ±
V ±
10. Specifications
All order information of ESM-3712-CN Cooling
Controller are given on the table at left. User may
form appropriate device configuration from
information and codes that at the table and
convert it to the ordering codes.
Firstly, supply voltage then other
specifications must be determined. Please fill the
order code blanks according to your needs.
Please contact us, if your needs are out of the
standards.
VŞ Vac,
ZŞ Vdc
ŞVdc or Vac can be applied
W
c
11.Ordering Information
A BC D E FG HI /
/
UV W Z/
/
0 1 0 0
1Relay Output ( 16(8) A@250 V V at resistive load, 1 NO )
Compressor Output
E
Temp. Sensor which is given with ESM-3712-CN
V
Supply VoltageA
Input Type
BC Scale(°C)
ESM-3712-CN (77x35 DIN Size)
4
0None
3NTC-M5L20.K1.5 (NTC Sensor, thermoplastic moulded with
1.5 m cable for cooling application)
-50°C/-58°F ;100°C/212°F
18 NTC (Note-1)
01 Relay Output ( 5 A@250 V V at resistive load, 1 NO )
Defrost Output
FG
01 Relay Output ( 5 A@250 V V at resistive load, 1 NO )
Fan OutputHI
4NTC-M6L50.K1.5 (NTC Sensor, stainless steel housing with
1.5 m cable for cooling application)
9Customer
115V ( %15) 50/60Hz - 1.5VAV ±
Note-1:If input type is selected PTC or NTC
(BC= 12, 18), Temperature sensor is given
with the device.For this reason, if input type is
selected as PTC,sensor type (V = 0,1 or 2) or if
input type is selected as NTC, sensor type (V
=0,3 or 4) must be declared in ordering
information.
324V ( %15) 50/60Hz - 1.5VAV ±
16
810 - 30 V Z
1PTC-M6L40.K1.5 (PTC Air Probe with 1.5 mt silicon cable)
2PTCS-M6L30.K1.5.1/8” (PTC Liquid Probe with1.5 mt silicon cable)
-50°C/-58°F ;150°C/302°F
12 PTC (Note-1)
5230V ( %15) 50/60Hz - 1.5VAV ±
Your Technology Partner
www.emkoelektronik.com.tr
Thank you very much for your preference to
use Emko Elektronik products, please visit our
web page to download detailed user manual.
,

ESM-3712-CN 77x35 DIN Maß Kühlregler
DEUTCH
Bedienungsanleitung: DE ESM-3712-CN 02 V02 09/12
- 4-stellige Anzeige
- NTC Eingang oder PTC Eingang (Muss vorher festgelegt werden)
- 3 Ausgänge für Kompressor, Abtau- und Ventilatorregelung
- 2 Sensoreingänge für Kühlfach und Verdampfer
- Konfigurierbarer Digitaleingang
- EIN / AUS Schalter
- 2 getrennt einstellbare abweichende Werte für den Kühlfach-und
den Verdampfersensor
- Begrenzung der einstellbaren Werte
- Beim Ausfall des Kühlfachsensors ist ein Dauerbetrieb des
Kompressors, aber auch Kompressor-Stop oder ein periodischer
Betrieb möglich.
- Kompressor-Schutzschalter mit Verzögerung
- Wahlweise 2 Abtaufunktionen (mit heißem Gas oder elektrisch )
- Auf der Frontplatte einstellbare Abtauzeit
- Manuelles Abtauen von der Frontplatte aus
- Abtauparameter
- Alarmparameter
- Ventilator läuft abhängig vom Kompressor und vom Abtauvorgang
- Ventilator läuft abhängig von der Verdampfertemperatur oder der
Kühlfachtemperatur.
- Einstellbarer, eingebauter Summer signalisiert das Abtauen, einen
Kühlfachsensorschaden und einen Alarmstatus.
- Automatisches oder manuelles Abtauen und/oder Schutz der
eingestellten Temperaturwerte
- Programmiermodus mit Passwortschutz
- Installationsparameter von Prokey
- Fernregelung, Datenkontrolle und Regelung mit Modbus RTU
- EU-Kennzeichnung gebaut nach den europäischen Normen
ESM-3712-CN 77 x 35 DIN Maß
Digitaler EIN / AUS Kühlregler

DEUTCH
Betriebstemperatur : 0 bis 50 °C
Max. Luftfeuchtigkeit : 90% r.L. (kein Kondenswasser)
Höhe ü.M.
: Bis zu 2000 m.
Unzulässig:
Korrosive Umgebung
Explosive Atmosphäre
Verwendung im Heimbereich (Gerät ist nur für industrielle Anwendung gedacht)
1.2 Technische Daten:
1.Vorwort:
Kühlregler der Serie ESM-3712-CN sind dafür konstruiert, den Kühlprozess zu steuern. Sie sind sehr
vielfältig einsetzbar, wegen ihres einfachen Gebrauchs, ihrer EIN-und AUS-Schaltfunktion und ihrer
Abtaufunktion.Einige der Anwendungsbereiche und Anwendungen sind unten aufgelistet:
Anwendungsbereiche
Lebensmittel
Maschinen Produktion Industrie
u.s.w.
ESM-3712-CN
Sensoreingang
Verdampfer
Anschlusswerte-
Stromversorgung
Digitaler Eingang
Kompressoreingang
Ventilatorausgang
Ausgang Abtauvorgang
NTC,PTC
Konfigurierbarer
Digitaleingang
- Ventilator Stop
- Kompressor Stop
- Ventilator und
Kompressor Stop
- Manuelles Abtauen
- Alarm
Sensoreingang
Kühlfach
NTC,PTC
Anwendungen
Kühlschränke
Klimaanlagen
Kühlhäuser
Tiefkühltruhen
u.s.w.
2
Kühlfunktion
EIN/Aus-Betrieb
Abtaufunktion
EIN/Aus-Betrieb
Regelausgang-Ventilator
EIN/Aus-Betrieb
1.1 Umweltfreundlichkeit:
230V ( %15) 50/60Hz ±
Andere Spannungen:
115 V (±%15) 50/60Hz
10 - 30 V
Standard

DEUTCH
2 Jahre Garantieschutz gegen Material- und Verarbeitungsfehler.
Diese Garantie wird mit dem Vorbehalt gewährleistet, dass der Kunde den in Garantieschein und
Bedienungsanleitung erwähnten Pflichten nachkommt.
Das Gerät muss durch geschultes Personal gewartet werden. Vor dem Zugriff auf Innenteile, alle stromführenden
Leitungen trennen. Gerät nicht mit auf Kohlenwasserstoff basierenden Lösungsmitteln (wie Benzin,
Trichlorethylen etc.) reinigen. Das Reinigen mit diesen Lösungen kann die mechanische Sicherheit des Geräts
vermindern. Verwenden Sie ein mit Ethylalkohol oder Wasser benetztes Tuch um das Plastikgehäuse außen zu
reinigen.
3
Information des Herstellers:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA
Tel : +90 224 261 1900
Fax : +90 224 261 1912
Information über Reparatur und Wartungsdienst
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA
Tel : +90 224 261 1900
Fax : +90 224 261 1912
Vor Montage das Gerät visuell prüfen, ob das Gerät während der Beförderung beschädigt wurde.Die Montage
und Inbetriebnahme muss durch geschultes Personal ausgeführt werden. Dies steht unter der Verantwortung des
Käufers.
Falls aufgrund eines Fehlers oder einer Störung des Geräts eine Gefahr bestehen sollte, Spannungsversorgung
abschalten und alle elektrischen Verbindungen zum Geräts entfernen.
Standardmäßig wird das Gerät ohne Netzschalter und ohne Sicherung ausgeliefert.
Bei Bedarf müssen diese vom Anwender selbst angebracht werden.
Es muss eine zum Gerät passende Versorgungsspannung verwendet werden, um Fehlfunktionen und Schäden
zu vermeiden.
Um einen elektrischen Schock und ähnliche Unfälle zu vermeiden, darf das Gerät vor Abschluss der Verkabelung
nicht mit Spannung versorgt werden.
An dem Gerät keine Veränderungen vornehmen, und das Gerät nicht reparieren.
Eingriffe am Gerät können fehlerhafte Funktion, Beschädigung des Geräts oder angeschlossener Geräte,
elektrischen Schocks und Feuer auslösen.
Das Gerät darf unter keinen Umständen in der Nähe von brennbaren und explosiven Gasen verwendet werden.
Die Schalttafelausschnitte können scharfe Kanten aufweisen, welche bei der Montage des Geräts
Schnittverletzungen verursachen können. Bitte treffen Sie die erforderlichen Vorsichtsmaßnahmen.
Es ist wichtig, dass das Gerät mit den mitgelieferten Befestigungsteilen montiertwird.
Das Gerät nicht mit ungeeigneten montieren. Achten Siedarauf, dass das Gerät während der Montage nicht
herunterfällt.
Es unterliegt Ihrer Verantwortung, wenn das Gerät nicht wie in dieser Anleitung beschrieben, verwendet wird.
1.3 Installation
1.4 Garantie
1.5 Instandhaltung
1.6 Sonstige Angaben

DEUTCH
2.2 Schalttafelausschnitt
2. Allgemeine Beschreibung:
2.1 Vorderansicht und Abmessungen des ESM-3712-CN Kühlregelung
Halteklammern
Frontplatte
(max. Dicke 15 mm / 0.59 Zoll)
Vorderseite:
Schutzklasse IP-65
NEMA 4X
4
76 mm / 3 Zoll
34,5 mm / 1.36 Zoll
OF
OCP
S
65 mm / 2.56 Zoll
6 mm / 0.24 Zoll
Maximal 15 mm / 0.59 Zoll
110 mm / 4.33 Zoll (min)
71 mm / 2.79 Zoll
29 mm / 1.14 Zoll
50 mm / 1.97 Zoll (min)
OF
OCP
S
ESM-3712CN
Table of contents
Languages:
Other EMKO Controllers manuals

EMKO
EMKO ESM-3711-CN User manual

EMKO
EMKO ESM-3711-CL User manual

EMKO
EMKO ESM-7311-H User manual

EMKO
EMKO ESM-9995 User manual

EMKO
EMKO EAOM-36 Series User manual

EMKO
EMKO EAOM-210 FLJ User manual

EMKO
EMKO EPC-1 User manual

EMKO
EMKO ESM-4410 User manual

EMKO
EMKO ESM-3721HT User manual

EMKO
EMKO EDA-3700 User manual
Popular Controllers manuals by other brands

Sensus
Sensus 461-57S Installation and maintenance instructions

LSI
LSI 3ware 9750 user guide

Vais Technology
Vais Technology SoundLinQ SL2xD2 owner's manual

Quantum Composers
Quantum Composers 1650 Series specification

Texas Instruments
Texas Instruments TMS320 2833 Series Reference manual

Santerno
Santerno Sinus Penta Basic user manual