EMKO EZM-4950 User manual

- 6 digits Process (PV) and 6 digits Set (SV) Value Display
- Operation with 2 Set Value
- Reset , Pause and ChA-ChB Counting Inputs
- Configurable Counter / “Totalizer Counter”, Batch Counter ,
Timer, Chronometer , Frequencymeter and Tachometer Functions
- Programmable Time Bases for Timer and Chronometer (Second ,
Minute , Hour )
- Operation with Automatic and Manual Reset
- Output Module System
- NPN/PNP Type Operation
- INC , DEC , INC / INC , INC / DEC , UP / DOWN , x1 / x2 / x4
Counting with Phase Shifting Property in Counter Function
- Multiplication Coefficient and Decimal Point Position
- Different Alarm Alternatives in Frequencymeter and Cycle
Measuring Functions
- Absolute or Offset Operation in Counter Function
- RS-232 (standard) or RS-485 (optional) Serial Communication
with Modbus ASCII or RTU Protocol
EZM-4950 96 x 48 1/8 DIN
Universal Input Programmable Timer &
Counter with Output Module System
EZM-4950 96x48 1/8 DIN Programmable Timer & Counter
Instruction Manual. ENG EZM-4950 02 V03 07/14

2
a
c
i
Instruction manual of EZM-4950 Programmable Timer&Counter consists of two main
sections. Explanation of these sections are below. Also, there are other sections which include
order information and technical specifications of the device. All titles and page numbers in
instruction manual are in “CONTENTS” section. User can reach to any title with section number.
Installation:
In this section, physical dimensions of the device, panel mounting, electrical wiring,
module mounting in the device, physical and electrical installation of the device to the system are
explained.
Operation and Parameters:
In this section, user interface of the device, how to access to the parameters, description
of parameters are explained.
Also in these sections, there are warnings to prevent serious injury while doing the
physical and electrical mounting or using the device.
Explanation of the symbols which are used in these sections are given below.
This symbol is used to determine the dangerous situations as a result of an electric
shock. User must pay attention to these warnings definitely.
This symbol is used for safety warnings. User must pay attention to these
warnings.
This symbol is used to determine the important notes about functions and usage of
the device.
ABOUT INSTRUCTION MANUAL

CONTENTS
3
Page 6
Page 9
Page 15
Page 22
Page 27
Page 29
Page 32
1.PREFACE..................................................................................................................
1.1 GENERAL SPECIFICATIONS
1.2 ORDERING INFORMATION
1.3 WARRANTY
1.4 MAINTENANCE
2.INSTALLATION.........................................................................................................
2.1 GENERAL DESCRIPTION
2.2 DIMENSIONS
2.3 PANEL CUT-OUT
2.4 ENVIRONMENTAL RATINGS
2.5 PANEL MOUNTING
2.6 INSTALLATION FIXING CLAMP
2.7 REMOVING FROM THE PANEL
2.8 SELECTION OF OPERATION FUNCTION AND INPUT TYPE WITH DIP
SWITCH
3.ELECTRICAL WIRINGS...........................................................................................
3.1 TERMINAL LAYOUT AND CONNECTION INSTRUCTION
3.2 ELECTRICAL WIRING DIAGRAM
3.3 CONNECTION OF DEVICE SUPPLY VOLTAGE INPUT
3.4 COUNTING INPUT CONNECTION
3.4.1 PROXIMITY & SWITCH CONNECTION
3.4.2 INCREMENTAL ENCODER & SWITCH CONNECTION
3.4.3 SWITCH CONNECTION
3.5 GALVANIC ISOLATION TEST VALUES OF EZM-4950 PROGRAMMABLE
TIMER&COUNTER AND OUTPUT MODULES
4.DEFINITIONS AND SPECIFICATIONS OF OUTPUT MODULES...........................
4.1 EMO-400 RELAY OUTPUT MODULE
4.2 EMO-410 SSR DRIVER MODULE
4.3 EMO-420 DIGITAL (TRANSISTOR) OUTPUT MODULE
4.4 INSTALLING AND PULLING OUT OUTPUT MODULES
4.5 TO STICK OUTPUT MODULES’ LABELS TO THE DEVICE
5.CONNECTION TERMINALS OF OUTPUT MODULES AND CONNECTION
WIRING.....................................................................................................................
5.1 EMO-400 RELAY OUTPUT MODULE CONNECTION
5.2 EMO-410 SSR DRIVER MODULE CONNECTION
5.3 EMO-420 DIGITAL (TRANSISTOR) OUTPUT MODULE CONNECTION
6.CONNECTIONS FOR RS-232 / RS-485 SERIAL COMMUNICATION.....................
6.1 CABLE CONNECTION BETWEEN RS-232 TERMINAL OF THE DEVICE
AND PC
6.2 CONNECTION FOR RS-485 SERIAL COMMUNICATION
6.3 INSTALLING RS-232 / RS-485 SERIAL COMMUNICATION MODULES TO
THE DEVICE
7.DEFINITION OF FRONT PANEL AND ACCESSING TO THE PARAMETERS.......
7.1 DEFINITION OF FRONT PANEL
7.2 POWER ON OBSERVATION OF EZM - 4950 PROGRAMMABLE TIMER &
COUNTER AND SOFTWARE REVISION ON THE DISPLAY

Page 102
Page 67
4
Page 100
7.3 ADJUSTMENT OF SET1 AND SET2 VALUES
7.4 RESETTING COUNT VALUE AND OBSERVING TOTAL COUNT VALUE IN
COUNTER / “TOTALIZER COUNTER” FUNCTION
7.5 COUNTER / “TOTALIZER COUNTER” PARAMETERS
7.5.1 COUNTER / “TOTALIZER COUNTER” APPLICATIONS EXAMPLES
7.6 BATCH COUNTER PARAMETERS
7.6.1 BATCH COUNTER APPLICATIONS EXAMPLES
7.7 TIMER PARAMETERS
7.7.1 TIMER APPLICATIONS EXAMPLES
7.8 FREQUENCYMETER / TACHOMETER PARAMETERS
7.8.1 FREQUENCYMETER / TACHOMETER APPLICATIONS EXAMPLES
7.9 CHRONOMETER PARAMETERS
7.9.1 CHRONOMETER APPLICATIONS EXAMPLES
7.10 ACCESSING TO THE PROGRAM PARAMETERS
8.PROGRAM PARAMETERS.....................................................................................
9.FAILURE MESSAGES IN EZM-4950 PROGRAMMABLE TIMER & COUNTER ..
10.SPECIFICATIONS.................................................................................................
11.OTHER INFORMATION.........................................................................................Page 103

5
Manufacturer Company Name : Emko Elektronik A.S.
Manufacturer Company Address: DOSAB, Karanfil Sokak, No:6, 16369 Bursa, Turkiye
The manufacturer hereby declares that the product conforms to the following
standards and conditions.
Product Name : Programmable Timer & Counter
Model Number : EZM-4950
Type Number : EZM-4950
Product Category : Electrical equipment for measurement, control and
laboratory use
Conforms to the following directives :
2006 / 95 / EC The Low Voltage Directive
2004 / 108 / EC The Electromagnetic Compatibility Directive
has been designed and manufactured to the following specifications:
EN 61000-6-4:2007 EMC Generic Emission Standard for Industrial Environments
EN 61000-6-2:2005 EMC Generic Immunity Standard for Industrial Environments
EN 61010-1:2001 Safety Requirements for electrical equipment for measurement, control
and laboratory use
When and Where Issued Authorized Signature
nd
16 October 2009 Name : Serpil YAKIN
Bursa-TURKEY Position : Quality Manager
EU DECLARATION OF CONFORMITY

6
EZM Series Programmable Timer & Counter can be used in package machines,
production and quality control rollers, in cutting and processing machine of glass, plastic, marble,
sheet, iron, fabric all measuring and controlling of dimension, count, total c unt, speed, cycle,
productivity, time and can be adapted easily to all mechanical construction and automation
system. They can be used in many application with their control outputs, serial communication
unit and output modules.
o
Some application fields which they are used are below:
1.Preface
Output Module-1
Supply Voltage
Input
Optional
1.1 General Specifications
EZM-4950
Optional
Standard
Standard
Universal Supply Input
100-240 VV, 50/60Hz
Output Module-2
Serial Communication RS-232
RS-485
Low Voltage (optional)
Supply Input
24VV50/60Hz ,24VZ
Application Fields
Glass
Plastic
Marble
Sheet iron
Automative
Machine production industries
Control Output
Alarm Output
Optional
Relay, SSR Driver ,Digital
(Transistor) Output
Module
Baud Rate from 1200
to 19200
Modbus ASCII or RTU
Protocol

7
EzM-4950 ( 96x48 1/8 DIN)
Supply Voltage
100-240VV(- ) 50/60Hz15%;+10%
24 VV(- 50/60Hz 24VZ(-15%;+10%) 15%;+10%)
A
A
1
00
0
01
1
02
2
03
3
0
1
2
None -
Counter / “Totalizer Counter”
Relay Output Module(3A@250VVResistive Load) EMO-400
Batch Counter
SSR Driver Output Module EMO-410
Frequencymeter and Tachometer
Digital(Transistor) Output Module EMO-420
Timer
None
RS-232
RS-485
2
BC D E FG HI /
/
U V W Z/
/
Serial CommunicationD
-
EMC-400
EMC-410
Product Code
1.2 Ordering Information
0
Customer (Maximum 240VV(- ))50/60Hz15%;+10%9
c
00 0 0
4 Chronometer
0
1
NPN
PNP
Product Code
Module-1FG
00
01
02
03
None -
Relay Output Module(3A@250VVResistive Load) EMO-400
SSR Driver Output Module EMO-410
Digital(Transistor) Output Module EMO-420
Product Code
Module-2HI
Function of DeviceU
Input TypeV
VSymbol means Vac,
ZSymbol means Vdc
WSymbol means Vac and Vdc
All order information of EZM-4950
Programmable Timer&Counter are given on
the table at left. User may form appropriate
device configuration from information and
codes that at the table and convert it to the
ordering codes.
Firstly, supply voltage then output
modules and other specifications must be
determined. Please fill the order code blanks
according to your needs.
Please contact us, if your needs are
out of the standards.

8
1.3 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and responsibilities which are determined in
warranty document and instruction manual performs by the customer completely.
1.4 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device
before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.

9
In package ,
- One piece unit
- Two pieces mounting clamps
- One piece instruction manual
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified
mechanical and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power
off the system and separate the electrical connection of the device from the system.
The unit is normally supplied without a power switch or a fuse. Use power switch and fuse
as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to
prevent failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble
with the unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may
results in malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During the equipment is putted in hole on the metal panel while mechanical installation
some metal burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s fixing clamps. Do not do the
montage of the device with inappropriate fixing clamp. Be sure that device will not fall
while doing the montage.
It is your responsibility if this equipment is used in a manner not specified in this
instruction manual.
Before beginning installation of this product, please read the instruction
manual and warnings below carefully.
2.Installation
c

10
2.1 General Description
2.2 Dimensions
Maximum 15 mm / 0.59 inch
48 mm/ 1.89 inch
96 mm / 3.78 inch
76 mm / 2.99 inch
10.5 ± 1 mm /0.41 inch
Terminal protection cover
Product Label
Front Panel
IP65 protection Panel surface
(maximum thickness 15 mm / 0.59 inch)
Mounting Clamp
S1
S2
O1
O2
Timer & Counter ESM-4430
EZM-4950
SET1 SET2 TOTAL
P
RESET

11
2.3 Panel Cut-Out
92 mm / 3.62 inch
129 mm / 5.08 inch (min)
65 mm / 2.56 inch (min)
46 mm / 1.81 inch (min)

12
1
2
3
12
1
2
3
Operating Temperature : 0 to 50 °C
Max. Operating Humidity : 90% Rh (non-condensing)
Altitude : Up to 2000m.
Operating Conditions
Forbidden Conditions:
Corrosive atmosphere
Explosive atmosphere
Home applications (The unit is only for industrial applications)
During installation into a metal panel, care should be taken to avoid injury from
metal burrs which might be present. The equipment can loosen from vibration
and become dislodged if installation parts are not properly tightened. These
precautions for the safety of the person who does the panel mounting.
1-Before mounting the device in
your panel, make sure that the
cut-out is the right size.
2-Check front panel gasket
position
3-Insert the device through the
cut-out. If the mounting clamps
are on the unit, put out them
before inserting the unit to the
panel.
2.4 Environmental Ratings
2.5 Panel Mounting
c
c

13
1
2
1
2
3
c
c
Before starting to remove the unit from panel, power off the unit and the related
system.
Montage of the unit to a system must be done with it’s own fixing clamps. Do not
do the montage of the device with inappropriate fixing clamps. Be sure that
device will not fall while doing the montage.
2.6 Installation Fixing Clamp
2.7 Removing from the Panel
1-Loosen the screws.
2-Pull mounting clamps from top
and bottom fixing sockets.
3-Pull the unit through the front
side of the panel
The unit is designed for panel
mounting.
1-Insert the unit in the panel cut-out
from the front side.
2- Insert the mounting clamps to the
holes that located top and bottom
sides of device and screw up the
fixing screws until the unit
completely immobile within the
panel
1

14
1
1
1
1 1 1 4
4
ON
ON
ON
ON ON ON ON
ON
OFF
OFF
Counter
&
Totalizer
Batch
Counter
Timer Tachometer Chronometer
PNP
NPN
OFF
OFF OFF OFF OFF
OFF
2
2
2
2 2 2
3
3
3
3 3 3
4
DIP Switch is under cover and cover is on top side of the device
NPN PNP
Function Selection
2.8 Selection of Operation Function and Input Type with DIP Switch
Operation function and input type ( NPN / PNP ) can be changed by DIP switch
on the device.
c
Counter / “Totalizer
Counter”
1
2
3
ONOFF
1
2
3
ONOFF
1
2
3
ONOFF
1
2
3
ONOFF
1
2
3
ONOFF
4
ONOFF
4
ONOFF
Batch Counter
Timer
Frequencymeter and
Tachometer
Chronometer
Input Type Selection
13
ChA
ChB
PAUSE
RESET
1
14
2
15
3
16
4
17
5
18
6
19
7
20
8
21
9
22
10
23
N
11
24
L
12
MODULE - 1 MODULE - 2
100 to 240 VV
50/60 Hz - 6VA
12 VZ
Max.50mA
0 VZ
P/N : EZM-4950
Y
ca
m

15
1
13
2
14
3
15
4
16
5
17
6
18
7
19
8
20
9
21
10
22
11
23
12
24
0.5 Nm
You must ensure that the device is correctly configured for your application.
Incorrect configuration could result in damage to the process being controlled,
and/or personal injury. It is your responsibility, as the installer, to ensure that
the configuration is correct.
Parameters of the device has factory default values. These parameters must be
set according to the system’s needs.
Only qualified personnel and technicians should work on this equipment. This
equipment contains internal circuits with voltage dangerous to human life.
There is severe danger for human life in the case of unauthorized intervention.
Be sure to use the rated power supply voltage to protect the unit against
damage and to prevent failure.
Keep the power off until all of the wiring is completed so that electric shock and
trouble with the unit can be prevented.
3.Electrical Wirings
3.1 Terminal Layout and Connection Instructions
c
c
c
c
6 mm / 0.236 inch
Wire Size:
18 AWG / 1 mm²
Solid /Stranded
24 screws terminal
M3
Optional
Connections
Empty terminals
Torque 0.5 Nm
Screw driver
0.8x3mm

12 V Z
Max 50mA
16
1 2 3 4 5 6
MODULE-1
78 9
a
10 11 12
13 14 15 16 17 18 19 20 21 22 23 24
0 V Z
Ch A
Ch B
PAUSE
RESET
MODULE-2
Counting Inputs
Optional Output Module Terminals
Relay Output Module
SSR Driver Module
Digital (Transistor) Output Module
c
Communication
Socket
Sensor
Supply Voltage
3.2 Electrical Wiring Diagram
Electrical wiring of the device must be the same as ‘Electrical Wiring Diagram’
below to prevent damage to the process being controlled and personnel injury.
Supply Voltage Input
100-240VV(- ) 50/60Hz - 6VA
24 VV(- 50/60Hz - 6VA
24VZ(-
(It must be determined in order)
15%;+10%
15%;+10%)
15%;+10%) - 6W
P/N : EZM-4950
Y
cm

17
3.3 Connection of Device Supply Voltage Input
Note-1 :
There is internal 33R W fusible flameproof resistor in 100-240 VV50/60Hz
There is internal 4R7 W fusible flameproof resistor in 24VV50/60Hz and 24VZ
Note-2 : “L” is “+”, “N” is “-” for 24VZsupply voltage
Note-3 : External fuse is recommended.
Supply voltage range must be determined in order. While installing the unit,
supply voltage range must be controlled and appropriate supply voltage must
be applied to the unit. Controlling prevents damages in unit and system and
possible accidents as a result of incorrect supply voltage.
There is no power supply switch on the device. So a power supply switch must
be added to the supply voltage input. In accordance with the safety regulations,
the power supply switch shall bring the identification of the relevant
instrument.Power supply switch shall be easily accessible by the user.
Power switch must be two poled for seperating phase and neutral. On/Off
condition of power switch is very important in electrical connection. On/Off
condition of power switch must be signed for preventing the wrong connection.
If an external fuse is used, it must be on phase connection in Vsupply input.
If an external fuse is used, it must be on (+) line connection in Zsupply input.
Make sure that the power supply voltage is the same indicated on the
instrument.
Switch on the power supply only after that all the electrical connections have
been completed.
The instrument is protected with an internal fuse (Please refer to Note1 for
information). In case of failure it is suggested to return the instrument to the
manufacturer for repair.
c
c
c
23
N L
24
Y
23
L
24
Y
c c
aa
N
Connection of Universal
Supply Voltage Input
Connection of Low Voltage
24 VWSupply Voltage Input
Supply Voltage
100 - 240 VV(-15%;+10%)
50/60Hz
Supply Voltage
24VV(-15%;+10%) 50/60Hz
or 24VZ(-15%;+10%)
Note-1
Power
Supply
Switch
External
Fuse
(1 AVT)
External
Fuse
(24VV: 1 AVT)
(24VZ: 1 AZT)
Note-2
Note-1
Power
Supply
Switch
Fuse
Fuse
Note-3
Note-3

18
DIP SWITCH ADJUSTMENT : PNP
1 42 53 6
0 VZ
ChA
ChB
PAUSE
PROX. PROX.
RESET
NPN NPN
1 42 53 6
12 VZ
Max. 50mA
0 VZ
ChA
ChB
PAUSE
Switch
PROX. PROX.
Switch
RESET
NOTE-1
PNP PNP
3.4.1 Proximity & Switch Connection
3.4 Counting Input Connection
DIP SWITCH ADJUSTMENT : NPN
NOTE-1 : Auxiliary power supply for external transmitter
12VZ± 10%, 50 mA maximum with short circuit protection
12 VZ
Max. 50mA
NOTE-1
Switch
Switch
NOTE-2
NOTE-2
NOTE-2 : Reset and Pause inputs have protection time against electrical contact
debounce. Protection time can be set with parameter. (2-250 msec.)

19
1 42 53 6
ChA
ChB
PAUSE
INCREMENTAL ENCODER
10 to 30VZ
RESET
1 42 53 6
ChA
ChB
PAUSE
INCREMENTAL ENCODER
10 to 30VZ
RESET
3.4.2 Incremental Encoder & Switch Connection
DIP SWITCH ADJUSTMENT : PNP
12 VZ
Max. 50mA
0 VZ
Switch
Switch
NOTE-1
DIP SWITCH ADJUSTMENT : NPN
12 VZ
Max. 50mA
0 VZ
Switch
Switch
NOTE-1
NOTE-1 : Auxiliary power supply for external transmitter
12VZ ± 10%, 50 mA maximum short circuit protection
NOTE-2
NOTE-2
NOTE-2 : Reset and Pause inputs have protection time against electrical contact
debounce. Protection time can be set with parameter. (2-250 msec.)

20
1 42 53 6
ChA
ChB
PAUSE
RESET
3.4.3 Switch Connection
DIP SWITCH ADJUSTMENT : PNP
Switch
Switch
DIP SWITCH ADJUSTMENT : NPN
NOTE-1 : Auxiliary power supply for external transmitter
12VZ± 10%, 50 mA maximum short circuit protection
1 42 53 6
ChA
ChB
PAUSE
RESET
Switch
Switch
12 VZ
Max. 50mA
0 VZ
NOTE-1
Switch
Switch
Switch
Switch
12 VZ
Max. 50mA
0 VZ
NOTE-1
NOTE-2
NOTE-2
NOTE-2 : Reset and Pause inputs have protection time against electrical contact
debounce. Protection time can be set with parameter. (2-250 msec.)
Table of contents
Other EMKO Controllers manuals

EMKO
EMKO EAOM-36 Series User manual

EMKO
EMKO ESM-3711-CL User manual

EMKO
EMKO EAOM-72F User manual

EMKO
EMKO esm-4450 User manual

EMKO
EMKO ESM-4930 User manual

EMKO
EMKO ESM-9430 User manual

EMKO
EMKO ESM-3722 User manual

EMKO
EMKO Trans-midiAUTO.MPU.232... User manual

EMKO
EMKO ESM-3721HT User manual

EMKO
EMKO EAOM-210 FLJ User manual

EMKO
EMKO ESM-1510 User manual

EMKO
EMKO ESM-3712-H User manual

EMKO
EMKO EDA-3700 User manual

EMKO
EMKO ESM-9995 User manual

EMKO
EMKO ESM-7311-H User manual

EMKO
EMKO DT-9910 User manual

EMKO
EMKO ESM-3712-CN User manual

EMKO
EMKO ESM 30 Series User manual

EMKO
EMKO ESM-4410 User manual

EMKO
EMKO PID QUADRO EPLC9600 User manual