EMKO ESM-3722 User manual

ESM-3722 77x35 DIN Size Hatcher Controller
Instruction Manual. ENG ESM-3722 01 V06 03/19
- 4 Digits for Temperature Display
- 4 Digits for Humidity Display
- Temperature Sensor Input
NTC, PTC, PT-100, 0/2..10V, 0/4..20mA or ProNem Mini PMI-P
(Must be determined in order.)
- Humidity Sensor Input
0/2..10V, 0/4..20mA or ProNem Mini PMI-P
(Must be determined in order.)
- 4 Output
Heating Control Output
Egg tray rotator Output
Humidification Control Output
Alarm Control Output
- Relay or SSR Outputs (Must be determined in order.)
- Selectable Temparature Control ( PID or ON / OFF )
- Auto-Tune PID
- Set value boundaries
- Manual Start of tray rotator from front panel
- Alarm parametreters
- Adjustable internal buzzer according to the alarm situations
- Password protection for programming mode,
ESM-3722 77 x 35 DIN Size
Digital Hatcher Controller
ENGLISH

c
1.2. General Specifications
1.Preface
ESM 3722 series Hatcher controllers are designed for controlling hatcher process. Device
can be used easily with PID or On-Off control form and manual start of egg tray rotator properties.
ESM-3722
Power Supply
Input
Output
Output
Output
2
Humidification
Egg Tray Rotator Output
Alarm
1.1 Environmental Ratings
230V ( %15)50/60HzV ±
Optional Supply
Voltage
- 30 V Z
115 V (±%15)50/60Hz
24 V (±%15)50/60Hz
24 V (±%15)50/60Hz
10
V
V
W
Standard
Output Heating
Operating Temperature : -20 to 70 °C
Max. Operating Humidity : 90% Rh (non-condensing)
Altitude : Up to 2000 m.
Forbidden Conditions:
Corrosive atmosphere
Explosive atmosphere
Home applications (The unit is only for industrial applications)
Temperature Sensor
Input
Humidity Sensor Input
0/2..10V, 0/4..20mA or
ProNem Mini PMI-P
PTC, NTC, PT-100
0/2..10V,0/4..20mA or
ProNem Mini PMI-P

3
A visual inspection of this product for possible damage occurred during shipment is recommended
before installation.
It is your responsibility to ensure that qualified mechanical and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power off the system
and separate the electrical connection of the device from the system.
The unit is normally supplied without a power supply switch or a fuse. Use power switch and fuse as
required.
Be sure to use the rated power supply voltage to protect the unit against damage and to prevent failure
Keep the power off until all of the wiring is completed so that electric shock and trouble with the unit can
be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may results in
malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During putting equipment in hole on the metal panel while mechanical installation some metal burrs can
cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s fixing clamps. Do not do the montage of the
device with inappropriate fixing clamp. Be sure that device will not fall while doing the montage.
It is your responsibility if this equipment is used in a manner not specified in this instruction manual.
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from the
delivery date. This warranty is in force if duty and responsibilities which are determined in warranty
document and instruction manual performs by the customer completely.
Repairs should only be performed by trained and specialized personnel. Cut power to the device before
accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of these
solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl alcohol or
water to clean the external plastic case.
1.3 Installation
1.4 Warranty
1.5 Maintenance
1.6 Manufacturer Company
Manufacturer Information:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
Repair and maintenance service information:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912

2.2 Panel Cut- Out
2. General Description
2.1 Front View and Dimensions of ESM-3722 Hatcher Controller
76 mm / 3 inch
34,5 mm / 1.36 inch
4
Mounting Clamp
Panel Surface
(maximum thickness 15 mm / 0.59 inch)
Front panel
IP65 Protection
65 mm / 2.56 inch
6 mm / 0.24 inch
110 mm / 4.33 inch (min)
71 mm / 2.79 inch
29 mm / 1.14 inch
50 mm / 1.97 inch (min)
Maximum 15 mm / 0.59 inch
ü

2.3 Panel Mounting and Removing
3. Electrical Wiring Diagram
3.1 Supply Voltage Input Connection of the Device
5
1-Before mounting the device in your panel, make
sure that the cut-out is of the right size.
2-Insert the device through the cut-out. If the
mounting clamps are on the unit, put out them
before inserting the unit to the panel.
3- Insert the mounting clamps to the fixing sockets
that located left and right sides of device and
make the unit completely immobile within the
panel
1-Pull mounting clamps from left and right
fixing sockets.
2-Pull the unit through the front side of the
panel
Before starting to remove the unit
from panel, power off the unit and
the related system.
c
Make sure that the power supply voltage is the same indicated on
the instrument.
Switch on the power supply only after that all the electrical
connections have been completed.
Supply voltage range must be determined in order. While installing
the unit, supply voltage range must be controlled and appropriate
supply voltage must be applied to the unit.
c
There is no power supply switch on the device. So a power supply
switch must be added to the supply voltage input.
Power switch must be two poled for seperating phase and neutral,
On/Off condition of power supply switch is very important in
electrical connection.
External fuse that on Vpower supply inputs must be on phase
connection.
External fuse that on Z power supply inputs must be on (+)
connection.
c
Power Supply Input
c
a
External
Fuse
(1A T)
Note-1
Supply
Switch
78
L
N
Supply Voltage
230V ( %15) 50/60Hz ,
115V ( %15) 50/60Hz ,
24V ( %15)50/60Hz ,
24V ( %15) 50/60Hz ,
Z
V ±
V ±
V ±
W ±
10...30 V 1.5 W
Must be determined in order.
Relay Outputs
2
13 54 6 87 9 10
P/N : ESM-3722
L
N
a
Power Supply Voltage
230V ( %15) 50/60Hz ,
115V ( %15) 50/60Hz,
24V ( %15) 50/60Hz ,
24V ( %15) 50/60Hz ,
Z
V ±
V ±
V ±
W ±
10...30 V 1.5 W
11 12
Temperature Sensor Input
NTC, PTC, PT-100 or
ProNem Mini PMI-P
Humidity Sensor Input
0/2..10V, 0/4..20mA or
ProNem Mini PMI-P
Must be determined in order.
3
2
1
1
2
Must be determined in order.
Must be determined in order.
Note-1: External Fuse is recommended

6
3.2 Device Label and Connection Diagram
230VV CONNECTION DIAGRAM
N
L
78910
a
3x3A@ 250V V
5A @250VV
L
N
230 VV ± 15%
50/60Hz - 1.5VA
2341
ALARM
HUM.
56 11 12
14A T Fuse
+
-
ENGINE
HEAT
N
L
78910
a
3x3A@ 250V V
5A @250VV
L
N
230 VV ± 15%
50/60Hz - 1.5VA
2341
ALARM
HUM.
56 11 12
14A T Fuse
+
-
ENGINE
HEAT
PTC Temperature and 0/4..20mA Humidity Sensor Input connection
VCC
GND
SCL
SDA
ProNem Mini PMI-P Temperature and Humidity Sensor Input Connection
WHITE
YELLOW
BROWN
GREEN
ProNem Mini
PMI-P
BLACK
Shield
Note : (Black) pin must be connected to number 10 (GND) of the terminal block.Shield
P/N : ESM-3722 - 5.2.5.0.1/01.01/1.0.0.0
78
a
3x3A@ 250V V
5A @250VV
L
230 VV ± 15%
50/60Hz - 1.5VA
2341
ALARM
PTC
56
ENGINE
HEAT
L N NNN N
0/4-20mA
HUM.
HUM.
INPUT
TEMP.
INPUT
910 11
P/N : ESM-3722 - 5.6.6.0.1/01.01/1.7.7.0
78910
a
3x3A@ 250V V
5A @250VV
L
230 VV ± 15%
50/60Hz - 1.5VA
234
1
ALARM
56
ENGINE
11 12
HEAT
L N NNN N
HUM.
ProNem Mini PMI-P
WHITE
BROWN
YELLOW
GREEN
VCC
GND
SCL
SDA

4.Front Panel Definition and Accessing to the Menus
7
BUTTON DEFINITIONS
1. Increment Button :
** In main operation screen, press this button to change display temperature and humidity sensor
value.
** It is used to increase the value in the Temperature and Humidity Set screens and Programming mode.
2. Decrement, Silencing Buzzer Button :
** It is used to decrease the value in the Set screen and Programming mode.
** It is used to silence the buzzer.
3. Manual Start of Egg Tray Rotator Operation Button:
** When the button is released the
engine start will be passive and engine stops.
4. Set Button:
** In the main operation screen; if this button pressed for the first time, Temperature set value will be
displayed. Value can be changed using increment and decrement buttons. When Set button is pressed
again, value is saved and Humidty set value will be displayed next. Value can be changed using
increment and decrement buttons. When Set button pressed again, value is saved and returns back to
main operating screen.
** To access the programming screen; in the main operation screen, press and hold this button for 5
seconds.
** It is used to save value in the Set screens (Temperature or Humidity) and programming screen.
5.Alarm led :
**
6. Heating Output Led :
** This led indicates that heating output is active.
7.Celcius led :
o
** Indicates that device is in C mode.
8.Fahrenheit led :
o
** Indicates that device is in F mode.
9. Led :
** This led indicates that is active.
10. Output Led :
** This led indicates that output is active.
11.Precent Sign ledi :
12.Program led :
** Indicates that device is in programming mode .
In the main operation screen, if this button pressed engine starts.
LED DEFINITIONS
It is active when alarm statuses.
Egg Tray Rotator Output
Egg Tray Rotator Output
Humidificating
Humidity
** Indicates that device is in Humidity Set screen.
ü
3
4
1
2
56
910
78
11
12

5. Changing and Saving Temperature and Humidity Set Value
5.1 Changing and Saving Humidity Set Value
Main Operating Screen
When SET button pressed ‘’S’’ led will
be active and temperature set value will
be displayed.
Temperature Set Value Screen
Temperature set value can
be changed with increment
and decrement buttons.
When SET button pressed
temperature set value can be saved.
Goes Humidity SET
value screen.
Temperature set value parameter ( Default =37.7 )
Temperature set value, can be programmed between minimum temperature set value and
maximum temperature set value .
°C
When SET button pressed
set value can be saved.
Humidity
Goes back to
main operation screen.
Humidity Set Value Screen
If no operation is performed in Humidity set value changing mode and temperature set value
changing mode for 20 seconds, device turns to main operation screen automatically.
i
Humidity Set Value Screen
8
Humidity set value parameter (Default = 60%)
Humidity set value, can be programmed between minimum Humidity set value and maximum
temperature set value .
Temperature Set Value Screen Humidity Set Value Screen
Humidity set value can be
changed with increment and
decrement buttons.
5.1 Programming Mode Parameter List
Decimal Seperator Enabling Parameter ( Default = 0 )
None.
Only Temperature parameters with decimal seperator.
Temperature Unit Selection Parameter ( Default = 0 )
°C selected.
°F selected.
Only Humidity parameters with decimal seperator.
Only Temperature and Humidity parameters with decimal seperator.
Note : When value of or parameters are changed , the values of , , , ,
, , , , , , , , , , , , and parameters
should be changed accordingly.
ESM-3722
ü ü
ESM-3722
ESM-3722
ü ü
ESM-3722
ü
ESM-3722 ESM-3722
ü

PID -Temperature Protection Parameter ( Default = )
When PID operation is performed, the heating output is switched off if the
temperature value goes above the value defined by . When the value is 0 or
0.0, if the value decrease button is pressed, appears and this function is
disabled.From 1 to 10°C for NTC,PTC, PT-100 (0°C, 100°C) ,From 1 to 18°F for
NTC,PTC ,PT-100 (32°F, 212°F),From 0.1 to 10.0°C for NTC, PTC, PT-100
(0.0°C,100.0°C), From 0.1 to 18.0°F for NTC, PTC, PT-100 (32.0°F,212.0°F) ,From
1 to 10°C for ProNem Mini PMI-P (-20°C, 80°C) ,From 1 to 18°F for ProNem Mini
PMI-P (-4°F,176°F), From 0.1 to 10.0°C for ProNem Mini PMI-P (-20.0°C,80.0°C),
From 0.1 to 18.0°F for ProNem Mini PMI-P (-4.0°F,176.0°F).
5.1 Programming Mode Parameter List
9
Temperature Control Selection Parameter On/Off or PID ( Default = 0 )
On - Off selected.
PID selected.
PID - Proportional Control Parameter ( Default =1.0 )
This parameter value can be adjusted form 0.1 to 100.0
PID - Integral Parameter( Default = 300 )
This parameter value can be adjusted form 0 to 3600.
PID - Derivative Parameter ( Default = 60 )
This parameter value can be adjusted form 0 to 999.9
PID -Period Time Parameter ( Default = 1 )
This parameter value can be adjusted form 1 to 150 second.
Note: If this parameter is select 0, PID parameters ( , , , , ) will be not observed.
If this parameter select 1, parameter will be not observed.
Self Tune (Step Response Tuning) Selection Parameter ( Default = )
Device does not do ( ) operation.Step Response Tuning
Device does operation.
0..10V veya 0..20mA Z Z
2..10V veya 4..20mA Z Z
Temperature Sensor Scale Selection Parameter ( Default = 0 )
(1) (2)
(2)(1)
Analogue (T input range is determined with this parameter.emperature)
Temperature
or
or
Sensor Scale Low Limit Parameter : ( Default = 0 )
It can be adjusted from -1999 to ( -1). At this value analogue input becomes;
If =0, according to the device type 0V 0mA
If =1, according to the device type 2V 4mA
Z Z
Z Z
(1) (2)
(1) (2)
Temperature
or
Sensor Scale High Limit Parameter : ( Default = 100 )
It can be adjusted from ( +1) to 9999. At this value analogue input becomes;
According to the device type10V
20mA
Z Z
(1) (2)
Note : , parameters are shown, if the Temperature sensor analogue input type is selected .
Note : , and parameters are shown, if the Temperature sensor input type
( 0/2..10V or 0/4..20mA ) is selected.
analogue

In ON/OFF control algorithm, temperature
value is tried to keep equal to set value by
opening or closing the last control element.
ON/OFF controlled system, temperature
value oscillates continuously. Temperature
value’s oscillation period or amplitude around
set value changes according to controlled
system. For reducing oscillation period of
temperature value, a threshold zone is formed
below or around set value and this zone is
named hysteresis.
ON
OFF
Temperature
Control
Output
Set
thSt
Time
thSt
Time
Hysteresis Parameter for Temperature ( Default = 0.1 °C )
From 1 to 10°C for NTC,PTC, PT-100 (0°C, 100°C) ,From 1 to 18°F for NTC,PTC ,PT-100
(32°F, 212°F),From 0.1 to 10.0°C for NTC, PTC, PT-100 (0.0°C,100.0°C), From 0.1 to
18.0°F for NTC, PTC, PT-100 (32.0°F,212.0°F) ,From 1 to 10°C for ProNem Mini PMI-P
(-20°C, 80°C) ,From 1 to 18°F for ProNem Mini PMI-P (-4°F,176°F), From 0.1 to 10.0°C for
ProNem Mini PMI-P (-20.0°C,80.0°C), From 0.1 to 18.0°F for ProNem Mini PMI-P
(-4.0°F,176.0°F).
10
Temperature Sensor Offset Parameter ( Default = 0 )
Humidity Sensor Scale Selection Parameter ( Default = 0 )
Minimum Temperature Set Value Parameter ( Default = 10.0°C)
Temperature set value can not be lower than this value. This parameter value can be
adjusted from minimum value of device scale to maximum temperature set value
parameter
Maximum Temperature Set Value Parameter ( Default = 40.0 °C )
Temperature set value can not be greater than this value.
This parameter value can be adjusted from minimum temperature set value parameter
to maximum value of the device scale.
From -10 to 10°C , NTC,PTC , PT-100 (0°C, 100°C)
From -18 to 18°F, NTC,PTC , PT-100 (32°F, 212°F)
From -10.0 to 10.0°C , NTC ,PTC , PT-100 (0.0°C,100.0°C)
From -18.0 to18.0°F NTC, PTC , PT-100 (32.0°F,212.0°F)
From -10 to 10°C ,ProNem Mini PMI-P ( -20°C, 80°C )
From -18 to 18°F,ProNem Mini PMI-P ( -4°F, 176°F )
From -10.0 to 10.0°C, ProNem Mini PMI-P ( -20.0°C, 80.0°C )
From -18.0 to18.0°F, ProNem Mini PMI-P ( -4.0°F,176.0°F )
0..10V 0..20mA Z or Z
2..10V 4..20mA Z or Z
(1) (2)
(2)(1)
Analogue input range is determined with this parameter.
Note : parameter ProNem Mini PMI- type device are not observed.P
Hysteresis Parameter for Humidity ( Default = 1 )
From 1 to 10 for Humidity Sensor (0%RH, 100%RH)
From 0.1to 10.0 for Humidity Sensor (0.0%RH,100.0%RH)
In ON/OFF control algorithm,
value is tried to keep equal to set value by
opening or closing the last control element.
ON/OFF controlled system, temperature
value oscillates continuously. Temperature
value’s oscillation period or amplitude
around set value changes according to
controlled system. For reducing oscillation
period of temperature value, a threshold
zone is formed below or around set value
Humidity
ON
Humidity
Control
Output
Set
hhSt
Time
hhSt
Time

11
Maximum Humidity Set Value Parameter (Default = Maximum Value of Device Scale)
This parameter value can be
adjusted from minimum humidity set value parameter to maximum value of the
device scale.
Humidity set value can not be greater than this value.
Minimum Humidity Set Value Parameter (Default = Minimum Value of Device Scale)
set value can not be lower than this value. This parameter value can be adjusted
from minimum value of device scale to maximum set value parameter
Humidity
Humidity
Humidity Sensor Offset Parameter ( Default = 0.0 )
From -10 to 10 for Humidity Sensor (0%RH, 100%RH)
From -10.0 to 10.0 for Humidity Sensor (0.0%RH,100.0%RH)
Humidity Decrease Amount Parameter for Door Opened Control ( Default = )
To detect that the door is opened, the humidity must be reduced in the amount defined by
the parameter in the time defined by the parameter. From -5 to 20 for
Humidity Sensor (0%RH, 100%RH) From 5.0 to 20.0 for Humidity Sensor
(0.0%RH,100.0%RH)
If the value decrease button is pressed while the parameter value
is 5 or 5.0, is displayed and this function is disabled and the parameters and
are not observed.
Humidity Decrease Amount Control Time Parameter for Door Opened Control
( Default = 20)
To detect that the door is opened, the humidity must be reduced in the amount defined
by the parameter in the time defined by the parameter.
Off Time of Humidity Output Parameter for Door Opened Control ( Default = 60 )
When it is detected that the door is opened, the humidity output is switched off for the time
defined by the parameter.
This parameter can be between 10 seconds and 999 seconds.
It is valid, if the device type 0/2...10V
It is valid, if the device type 0/4...20mA
Z Humidity Sensor Input.
Z Humidity Sensor Input .
(1)
(2)
i
Time of Automatic Egg Tray Rotator ( Default = 00:00 )
This parameter value can be adjusted form 00:00 to 99:59 minute/second.
Repeat cycle of Automatic Egg Tray Rotator ( Default = 00:00 )
This parameter value can be adjusted form 00:00 to 24:00 hour/minute.
Alarm Output Function Selection Parameter ( Default = 0 )
Alarm is inactive.
Alarm-Temperature sensor failures.
Alarm-Humidity sensor failures.
Alarm-Temperature or Temperature sensor failures.
Alarm-Humidity or Humidity sensor failures.
Alarm-Temperature sensor failures or Humidity sensor failures.
Alarm-Temperature or Humidity or Temperature sensor failures or Humidity
sensor failures.
Note : if parameter value is 3 or 6 , , , , , or parameters are
observed.
Note : if parameter value is 4 or 6 , , , , , or parameters are
observed.

12
Humidity Alarm Function Selection Parameter ( Default = 0 )
Temperature Alarm Set Parameter
This parameter value can be programmed between temperature minimum alarm set
parameter and temperature alarm set maximum parameter.
( Default = 50.0 °C )
Alarm Set Maximum Parameter ( Default = Maximum Value of Device Scale)
if temperature alarm is active, this parameter value can be adjusted from temperature
alarm set value parameter to maximum value of the device scale.
Alarm Set Minimum Parameter (Default = Minimum Value of Device Scale)
if temperature alarm is active, this parameter value can be adjusted from minimum value of
device scale to temperature alarm set maximum parameter value.
Temperature Alarm Parameter
This parameter value can be adjusted form 0 to %50 of the device scale.
Hysteresis ( Default = 0)
Temperature Alarm On Delay Time Parameter
Temperature Alarm On Delay Time can be defined with this parameter. It can be
adjusted from 0 to 99 minutes.
( Default = 0)
Temperature Alarm Delay After Power On Parameter
It can be adjusted from 0 to 99 minutes.
( Default = 0)
When power is first applied to the device, this time delay must be expired for activation of
temperature alarm.
Process High alarm selected.
Process Low alarm selected.
Deviation Band alarm selected.
Deviation Range alarm selected.
Humidity Alarm Set Parameter
This parameter value can be programmed between humidity minimum alarm set
parameter and humidity alarm set maximum parameter.
( Default = 50 )
Humidity (Default = 0)
When power is first applied to the device, this time delay must be expired for activation of
Humidity alarm.
Alarm Delay After Power On Parameter
It can be adjusted from 0 to 99 minutes.
Humidity Set Maximum Parameter(Default =Maximum Value of Device Scale)
if humidity alarm is active, this parameter value can be adjusted from humidity alarm set
minimum parameter to maximum value of the device scale.
Alarm
Humidity (Default = 0)
Humidity
Alarm On Delay Time Parameter
Alarm On Delay Time can be defined with this parameter. It can be adjusted
from 0 to 99 minutes.
Humidity Set Minimum Parameter(Default =Minimum Value of Device Scale)
if humidity alarm is active, this parameter value can be adjusted from minimum value of
device scale to humidty alarm set maximum parameter value.
Alarm
Humidity Alarm Parameter
This parameter value can be adjusted form 0 to %50 of the device scale.
Hysteresis ( Default = 0)
Temperature Alarm Function Selection Parameter ( Default = 1 )
Process High alarm selected.
Process Low alarm selected.
Deviation Band alarm selected.
Deviation Range alarm selected.

13
Buzzer Function Selection Parameter( Default = 0 )
Button Protection Parameter ( Default = 0 )
Buzzer is inactive.
Buzzer is active during temperature alarm
Buzzer is active during humidity alarm
Buzzer is active during Temperature sensor failures.
Buzzer is active during Humidity sensor failures.
Buzzer is active during Temperature sensor failures or temperature alarm.
Buzzer is active during Humidity sensor failures or Humidity alarm.
Buzzer is active during Temperature sensor failures or Humidity sensor failures
Buzzer is active during Temperature sensor failures or Humidity sensor failures
or temperature alarm or humidity alarm.
There is no protection.
Temperature set value can not be changed.
Humidity set value can not be changed.
Manual engine start is not available.
Humidity set value and Temperature set value can not be changed
Humidity set value can not be change and Manual engine start is not available.
Temperature set value can not be change and Manual engine start is not
available.
Temperature set value and Humidity set value can not be changed. Also
Manual engine start is not available.
Buzzer Active Time
If buzzer function selection parameter
Buzzer active time can be define with this parameter. It can be adjusted from 1 to 99
minutes. When this parameter is 1, if decrement button is pressed, is observed. In
this condition buzzer is active till buzzer silence button is pressed.
( Default = )
value = 0, this parameter is not observed.
Programming Mode Accessing Password
It is used for accessing to programming mode. It can be adjusted from 0 to 9999. If it is 0,
password is not entered for accessing to the parameters. When the password screen is not
set as “12” , If the user enters ‘12’ in password screen and parameters are
accessed and they can changed.
( Default = 0 )

14
5.2 Alarm Output Graphics of ESM-3722
i = Process Set Value (Temperature or Humidity)
Process High Alarm
ON
OFF
Alarm
Output
Process Value
Alarm Set
Process Low Alarm
ON
OFF
Alarm
Output
Process Value
Deviation Range Alarm
ON
OFF
Alarm
Output
Process Value
( - Alarm Set) ( +Alarm Set)
Deviation Band Alarm
ON
OFF
Alarm
Output
( - Alarm Set)
Alarm Set
( +Alarm Set)
Process Value
5.3 Egg Tray Rotator Operation Graphics of ESM-3722
Egg Tray Rotator
Output Led
Egg Tray Rotator
Output
1-
connection. While this message shown on this display,if buzzer function selection is 3, 5, 7 or 8
internal buzzer starts to operate.
Screen Blinking Temperature Sensor failure . Sensor connection is wrong or there is no sensor
5.4 Failure Messages in ESM 3722 Hatcher Controller
2Screen Blinking H Sensor failure . Sensor connection is wrong or there is no sensor
connection. While this message shown on this display,if buzzer function selection is 4, 6,7 or 8
internal buzzer starts to operate.
- umidity
3- In main operating screen if the upper display is blinking, it means that temperature alarm exits and
alarm output is active .if buzzer function selection is 1, 5 or 8 internal buzzer starts to operate.
4- In main operating screen if the lower display is blinking, it means that humidity alarm exits and alarm
output is active .if buzzer function selection is 2, 6 or 8 internal buzzer starts to operate.
5- Self Tune temperature error. Appears on the main screen.this fault occurs when the
temperature read from the sensor is closer to the Process Set value than 5% of the scale(5 ° C for the
ProNem Mini PMI-P sensor). Self tune operation is not allowed.

When SET button is pressed for 3
seconds, “P” led turn. If programming
mode entering password is different
from 0, programming mode entering
screen will be observed.
Main Operation Screen
Programming Screen
Change the value with increment
and decrement buttons.
Press SET button for accessing to the
parameter value. Press increment
button for accessing to the next
parameter, press decrement button for
accessing to the previous parameter.
Press set button for saving the
parameter. Press increment button for accessing to
the next parameter, press decrement
button for accessing to the previous
parameter.
Programming Mode
Entering Screen
Press SET button for
accessing to the
password entering
Password Entering Screen
Enter programming mode accessing
password with increment and
decrement buttons.
Note2: If programming mode accessing password is 0, only three parameters are accessible, and the
parameter values can be changed.
Press SET/OK button for
entering the password.
Note1: If programming
mode accessing password
is 0, Temperature Unit
screen is observed
instead of programming
screen
If no operation is performed in programming mode for 20 seconds, device turns to main
operation screen automatically.
i
Decimal Separator Enabling
Selection Screen
5.5 Entering To The Programming Mode, Changing and Saving Parameter
15
Password Entering Screen
Temperature Unit Selection
Parameter Value
Temperature Unit Selection
Parameter Value
ESM-3722
ü
ESM-3722
ü
ESM-3722
ü
ESM-3722
ü
ESM-3722
ü
ESM-3722
ü
ESM-3722
ü
ESM-3722
ü

3 sec.
16
While button protection parameter value is 0,1,2 or
4 in main operation screen if engine button is pressed,
manual engine start will be active.When the button is
released the engine start will be passive and engine stops.
6. Manual Start of Egg Tray Rotator Operation with Engine Button
8. Specifications
Device Type : Hatcher Controller
Housing&Mounting : 76 mm x 34.5 mm x71 mm Plastic housing for panel
Panel cut out is 71 x 29 mm.
Protection Clas : Ip65 at front, Ip20 at rear.
Weight : Approximately 0.2 Kg
Enviromental Ratings : Standart,indoor at an altitude of less than 2000 meters with
none condensing humidity.
o o o o
Storage / Operating Temperature : -30 C to +80 C / -20 C to +70 C
Storage / Operating Humidity : 90 % max. (None condensing)
Installation : Fixed installation
Overvoltage Category : II.
Pollution Degree : II, office or workplace, none conductive pollution
Operating Conditions : Continuous
Supply Voltage and Power :
: 115
: 24
: 24
: 10 -30
Temperature Sensor Input : NTC, PTC, PT-100,0/2..10VZ,0/4..20mAZ or
ProNem Mini PMI-P
230V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA
VZ 1.5W
V ±
V ±
V ±
W ±
ü
7. Self Tune Metod
Starting Self Tune (Step Response Tuning) Operation by the user :
Self Tune method is used for determining PID parameters used by the device.
If Self Tune operation is finished without any problem, the device saves the new PID coefficients to
memory and continue to run. Parameter is adjusted automatically.
NOT: The temperature value read from the sensor must be less than 5% of the process set value in order
to start the self tune operation (5 ° C for the ProNem Mini PMI-P sensor).
Cancelling Self Tune(Step Response Tuning) operation :
1 - If sensor breaks;
2 - If auto tune operation can not be completed in 8 hours ;
3 - If user adjusts parameter ;
4- During self tune operation if the user changes the temperature control from pid to on/off;
5 - If process set value is changed while self tune operation is being performed;
Self tune is canceled. “Tune” is not displayed. Then, without doing any changes in PID parameters,
device continues to run with previous PID parameters.
• Adjust t
• Adjust self tune selection parameter ( = )
• In the main screen “Tune” and Temperature value are should alternately.
emperature control on/off or PID parameter
( =1)

All order information of ESM-3722 Hatcher Controller are given on the table at above. User may form
appropriate device configuration from information and codes that at the table and convert it to the
ordering codes.Firstly, supply voltage then other specifications must be determined. Please fill the order
code blanks according to your needs. Please contact us, if your needs are out of the standards.
10. Other Informations
Note-1: If input type is selected PTC or NTC (B = 2, 3), Temperature sensor is given with the
device.For this reason, if input type is selected as PTC,sensor type (V = 0,1 or 2) or if input type is
selected as NTC, sensor type (V = 0, 3 or 4) must be declared in ordering information.
8. Specifications
17
Your Technology Partner
www.emkoelektronik.com.tr
Thank you very much for your preference to
use Emko Elektronik products, please visit our
web page to download detailed user manual.
NTC input type : NTC (10 kW @25 °C )
PTC input type : PTC (1000 W @25 °C )
Termoresistance input type : PT-100 IEC751 (ITS90 )
Humidity input type : 0/2..10VZ,0/4..20mAZ or ProNem Mini PMI-P
Accuracy : ± 1 % of full scale
Sensor Break Protection : Upscale
Control Form : PID or ON / OFF
Relay Outputs : 5 A@250 V V at Resistive Load (Heating Output)
: 3 A@250 V V at Resistive Load ( Humidificating, Alarm
and Egg tray rotator Output
Optional SSR Driver Output : Maximum 30mA, Maximum 15V
Temperature Display : 8 mm Red 4 digit LED Display
Humidity Display : 8 mm Green 4 digit LED Display
o o
LED Displays : P (Green),%(Green),C (Red), F(Red), Alarm (Red),
Humidifier Output (Red), Egg tray rotator Output (Red)
Heating Output (Red),
Internal Buzzer : ³83dB
Upprovals : ,
B C D E FG HI /
/
UV W Z/
/0
Power Supply VoltageA
Temperature Sensor Input
BScale(°C/°F)
ESM-3722
(77x35 DIN Size)
4
-20°C/-4°F ; 80°C/176°F
115V ( %15) 50/60Hz - 1.5VAV ±
ProNem Mini PMI-P
PT 100, IEC751(ITS90)
1
PTC (Not-1)
2
5230V ( %15) 50/60Hz - 1.5VAV ±
810 - 30 V Z 1.5W
0°C/32°F ;100°C/212°F
0°C/32°F ;100°C/212°F
NTC (Not-1)
3
0°C/32°F ;100°C/212°F
324V ( %15) 50/60Hz - 1.5VAV ±
0
224V ( %15) 50/60Hz - 1.5VAW ±
0% - 100%
0% - 100%
0% - 100%
0/2..10Vdc Voltage Input
4
50/4..20mA Current Input
6
Humidity Sensor Input
CScale (%)
ProNem Mini PMI-P
0/2..10Vdc Voltage Input
4
50/4..20mA Current Input
6
01 Relay Output ( 3A@250 V V,at Resistive Load ,1 NO )
Humidifier Output
FG
1Relay Output ( 5 A@250 V V,at Resistive Load 1NC ,1 NO )
Heating Output
E
2SSR Drive Output ( Maximum 30mA,Maximum 15V )
01 Relay Output ( 3A@250 V V,at Resistive Load ,1 NO )
Egg Try Rotator Output
HI
1Relay Output ( 3A@250 V V,at Resistive Load ,1 NO )
Alarm Output
U
Temp.Sensor which is given with ESM-3722
V
0None
3NTC-M5L20.K1.5 (NTC Probe thermoplastic moulded with
1.5m cable for cooling application)
4NTC-M6L50.K1.5 (NTC Probe stainless steel housing with
1.5m cable for cooling application)
9
ProNem Mini PMI-P.PT
7
Customer
1PTC-M6L40.K1.5 (PTC Air Probe 1.5 m silicon cable)
2PTCS-M6L30.K1.5.1/8”(PTC Liquid Probe with 1.5 m silicon cable)
A
User defined
User defined
(Pt100 Temperature and Humidity
Sensor with 2.5 mt cable)

ESM-3722 77 x 35 DIN-Größe Brutregler
Bedienungsanleitung. DE ESM-3722 01 V06 03/19
- 4-stellige Temperaturanzeige
- 4-stellige Feuchtigkeitsanzeige
- Temperatursensoreingang
NTC, PTC, PT-100, 0/2..10 V, 0/4..20 mA oder ProNem Mini PMI-P
(Muss der Reihenfolge nach bestimmt werden.)
- Feuchtigkeitssensoreingang
0/2..10 V, 0/4..20 mA oder ProNem Mini PMI-P
(Muss der Reihenfolge nach bestimmt werden.)
- 4 Ausgang
Heizungsregler-Ausgang
Bruthorde-Wender-Ausgang
Befeuchtungsreglerausgang
Alarmsteuerungsausgang
- Relais oder SSR-Ausgänge
(Müssen der Reihenfolge nach bestimmt werden.)
- Wählbare Temperaturregelung (PID oder EIN/AUS)
- Autotune PID
- Sollwertgrenzen
- Manueller Start des Wenders über Bedienfeld
- Alarmparameter
- Einstellbarer interner Summer je nach Alarmsituationen
- Passwortschutz für Programmierbereich
- CE-Kennzeichnung gemäß Europäischen Normen
ESM-3722 77 x 35 DIN-Größe
Digitaler Brutregler
DEUTSCH

c
1.2. Allgemeine Spezifikationen
1. Einleitung
Die Brutregler der Serie ESM 3722 dienen zur Regelung des Brutprozesses. Dank PID
oder Ein-Aus Steuerungsform und manuellem Start des Bruthorde-Wenders ist das Gerät einfach
zu bedienen.
ESM-3722
Stromversorgungs-
eingang
Ausgang
Ausgang
Ausgang
2
Befeuchtung
Bruthorde-Wender-Ausgang
Alarm
1.1 Umgebungsbedingte Leistungsfähigkeit
230V ( %15)50/60HzV ±
Optionale
Versorgungsspannung
- 30 V Z
115 V (±%15)50/60 Hz
24 V (±%15)50/60 Hz
24 V (±%15)50/60 Hz
10
V
V
W
Standard
Ausgang Heizen
Betriebstemperatur : -20 bis 70 °C
Max. Luftfeuchtigkeit bei Betrieb : 90% Rh (nicht kondensierend)
Höhe : Bis zu 2000 m.
Verbotene Bedingungen:
Korrosive Atmosphäre
Explosionsfähige Atmosphäre
Heimbereich (Das Gerät ist nur für industrielle Anwendungen)
Temperatursensor-
eingang
Feuchtigkeitssensor-
eingang
0/2..10V, 0/4..20 mA oder
ProNem Mini PMI-P
PTC, NTC, PT-100
0/2..10V, 0/4..20 mA oder
ProNem Mini PMI-P

3
Eine Sichtprüfung dieses Produkts auf mögliche Transportschäden wird vor der Installation empfohlen. Es
liegt in Ihrer Verantwortung dafür zu sorgen, dass qualifizierte Maschinenbau- und Elektrotechniker dieses
Produkt installieren.
Bei Gefahr eines schweren Unfalls durch Ausfall oder Defekt dieser Einheit, schalten Sie das System aus und
trennen Sie die elektrische Verbindung des Geräts vom System.
Die Einheit wird normalerweise ohne Stromschalter oder Sicherung geliefert. Verwenden Sie Netzschalter
und Sicherung nach Bedarf.
Stellen Sie sicher, dass Sie die Nennversorgungsspannung verwenden, um die Einheit vor Schäden zu
schützen und einen Ausfall zu verhindern.
Lassen Sie den Strom abgeschaltet, bis die gesamte Verkabelung abgeschlossen ist, damit Stromschläge
und Probleme mit dem Gerät verhindert werden können.
Versuchen Sie niemals die Einheit zu zerlegen, zu verändern oder zu reparieren.
Die Manipulierung des Geräts kann zu Fehlfunktion, Stromschlag oder Brand führen.
Verwenden Sie die Einheit nicht in brennbaren oder explosionsgefährdeten gashaltigen Atmosphären.
Beim Einsetzen des Geräts in die Öffnung der Metallplatte während der mechanischen Installation, können
Metallgrate Verletzungen an den Händen verursachen. Seien Sie vorsichtig.
Die Montage des Produkts in einem System muss mit dessen Befestigungsklammern erfolgen. Führen Sie die
Montage des Geräts nicht mit ungeeigneten Befestigungsklammern durch. Achten Sie darauf, dass das Gerät
während der Montage nicht herunterfällt.
Es liegt in Ihrer Verantwortung, wenn das Gerät auf eine nicht in dieser Bedienungsanleitung
vorgeschriebenen Art und Weise benutzt wird.
EMKO Elektronik garantiert, dass das gelieferte Gerät keinerlei Material- oder Verarbeitungsmängel
aufweist. Diese Garantie beschränkt sich auf einen Zeitraum von zwei Jahren. Die Garantiezeitbeginnt mit
dem Lieferdatum. Diese Garantie ist gültig, wenn die im Garantieschein und in der Bedienungsanleitung
festgelegten Pflichten und Verantwortlichkeiten vollständig durch den Kunden erfüllt werden.
Reparaturen dürfen nur von geschultem Fachpersonal durchgeführt werden. Trennen Sie das Gerät
von der Stromversorgung, bevor Sie Innenteile manipulieren. Reinigen Sie das Gehäuse nicht mit
Kohlenwasserstoff-Lösemitteln (Benzin, Trichloräthylen usw.). Die Verwendung dieser Lösemittelkann
die mechanische Zuverlässigkeit des Geräts beeinträchtigen. Verwenden Sie ein mit Ethylalkohol oder
Wasser angefeuchtetes Tuch, um das externe Kunststoffgehäuse zu reinigen.
1.3 Installation
1.4 Garantie
1.5 Wartung
1.6 Herstellerfirma
Herstellerangaben:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY
Telefon : +90 224 261 1900
Fax : +90 224 261 1912
Reparatur und Wartungsservice:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA /TURKEY
Telefon : +90 224 261 1900
Fax : +90 224 261 1912
Table of contents
Languages:
Other EMKO Controllers manuals

EMKO
EMKO ESM-1510 User manual

EMKO
EMKO ESM-7311-H User manual

EMKO
EMKO EAOM-36 Series User manual

EMKO
EMKO ESM-3711-CL User manual

EMKO
EMKO ESM-3712-CN User manual

EMKO
EMKO ESM-9430 User manual

EMKO
EMKO ESM-3712-H User manual

EMKO
EMKO ESM-3711-CN User manual

EMKO
EMKO EAOM-6 User manual

EMKO
EMKO EDA-3700 User manual

EMKO
EMKO EAOM-9F ND User manual

EMKO
EMKO EZM-4950 User manual

EMKO
EMKO DT-9910 User manual

EMKO
EMKO EPC-1 User manual

EMKO
EMKO Trans-midiAUTO.MPU.232... User manual

EMKO
EMKO EAOM-210 FLJ User manual

EMKO
EMKO PID QUADRO EPLC9600 User manual

EMKO
EMKO ESM-4410 User manual

EMKO
EMKO EAOM-9F ND User manual

EMKO
EMKO EAOM-72F User manual