EMKO ESM 30 Series User manual

ESM-7730 72x72 DIN Size Process Controller
ESM-7730 72 x 72 DIN Size
Universal Input PID Process Controller
- 4 4 digits process set value (SV)
display
(TC, RTD, mV Z, V Z, mA Z)
- Dual or multi point calibration for ZVoltage / Current input
- Adaptation of PID coefficients to the system with Auto-tune and
Self-tune
- Manual/Automatic mode selection for control output
- Bumpless transfer
- Programmable heating, cooling and alarm functions for control
Output
digits process value (PV) and
- Universal process input
- Configurable ON/OFF, P, PI, PD and PID control forms
Instruction Manual. ENG ESM-7730 02 V07 07/14

ABOUT INSTRUCTION MANUAL
2
Instruction manual of ESM-7730 process controller consists of two main sections. Also,
there are other sections which includes order information and technical specifications of the
device. All titles and page numbers in instruction manual are in “CONTENTS” section. User can
reach to any title with section number.
Installation:
In this section, physical dimensions of the device, panel mounting, electrical wiring,
physical and electrical installation of the device to the system are explained.
Operation and Parameters:
In this section, user interface of the device, how to access to the parameters, description
of parameters are explained.
Also in these sections, there are warnings to prevent serious injury while doing the
physical and electrical mounting or using the device.
Explanation of the symbols which are used in these sections are given below.
This symbol is used to determine the dangerous situations as a result of an electric
shock. User must pay attention to these warnings definitely.
a
cThis symbol is used for safety warnings. User must pay attention to these
warnings.
This symbol is used to determine the important notes about functions and usage of
the device.
i

3
1.PREFACE............................................................................................................................................
1.1 GENERAL SPECIFICATIONS
1.2 ORDERING INFORMATION
1.3 WARRANTY
1.4 MAINTENANCE
2.INSTALLATION....................................................................................................................................
2.1 GENERAL DESCRIPTION
2.2 DIMENSIONS
2.3 PANEL CUT-OUT
2.4 ENVIRONMENTAL RATINGS
2.5 PANEL MOUNTING
2.6 INSTALLATION MOUNTING CLAMP
2.7 REMOVING FROM THE PANEL
3.ELECTRICAL WIRING........................................................................................................................
3.1 TERMINAL LAYOUT AND CONNECTION INSTRUCTION
3.2 ELECTRICAL WIRING DIAGRAM
3.3 VIEW OF THE LABELS
3.4 CONNECTION OF DEVICE SUPPLY VOLTAGE INPUT
3.5 PROCESS INPUT CONNECTION
3.5.1 TC (THERMOCOUPLE) CONNECTION
3.5.2 RTD CONNECTION
3.6 GALVANIC ISOLATION TEST VALUES OF ESM-7730 PROCESS CONTROLLER
5.DEFINITION OF FRONT PANEL AND ACCESSING TO THE MENUS..............................................
5.2 OBSERVATION OF SOFTWARE REVISION ON THE BOTTOM DISPLAY WHEN POWER
IS ON
5.3 ADJUSTMENT OF PROCESS AND ALARM SET VALUES
CHANGING AND SAVING PARAMETERS
6.2.1 SELECTION OF PID TUNE AND OPERATION FORM
6.2.2 FUNCTION SELECTION FOR TOP AND BOTTOM DISPLAY
6.2.3 PROCESS INPUT TYPE AND RELEVANT PARAMETERS WITH PROCESS INPUT
6.2.8 GENERAL PARAMETERS
6.2.9 TECHNICIAN PASSWORD
7.FAILURE MESSAGES IN ESM-7730 PROCESS CONTROLLERS...................................................
8.SPECIFICATIONS................................................................................................................................
9.OTHER INFORMATION.......................................................................................................................
3.5.3 CONNECTION OF SERIAL TRANSMITTERS WITH CURRENT OUTPUT (LOOP
POWERED) TO THE PROCESS INPUT
3.5.4 CONNECTION OF 3-WIRE TRANSMITTERS WITH CURRENT OUTPUT TO THE
PROCESS INPUT
3.5.5 CONNECTION OF TRANSMITTERS WITH VOLTAGE OUTPUT TO THE PROCESS
INPUT
4.OUTPUT CONNECTION FORMS IN ESM-7730 PROCESS CONTROLLERS..................................
4.1 PROCESS OUTPUT (SSR DRIVER OUTPUT) CONNECTION
4.2 ALARM OUTPUT -1 RELAY CONNECTION
4.3 PROCESS OUTPUT OR ALARM OUTPUT -2 RELAY CONNECTION
6.PARAMETERS.....................................................................................................................................
6.1 PROCESS / ALARM SET PARAMETERS
6.2 TECHNICIAN PARAMETERS
6.2.4 PID CONFIGURATION PARAMETERS
6.2.5 PROCESS OUTPUT CONFIGURATION PARAMETERS
6.2.6 ALARM OUTPUT - 1 CONFIGURATION PARAMETERS
6.2.7 ALARM OUTPUT - 2 CONFIGURATION PARAMETERS
5.1 FRONT PANEL DEFINITION
5.4 EASY ACCESS DIAGRAM FOR PROGRAM PARAMETERS
5.5 ACCESSING TO THE TECHNICIAN MENU
5.6
CONTENTS
Page 5
Page 41
Page 21
Page 13
Page 8
Page 23
Page 64
Page 65
Page 66

4
Manufacturer Company Name : Emko Elektronik A.S..
Manufacturer Company Address: DOSAB, Karanfil Sokak, No:6, 16369 Bursa, Turkiye
The manufacturer hereby declares that the product conforms to the following
standards and conditions.
Product Name : Process Controller
Model Number : ESM-7730
Type Number : ESM-7730
Product Category : Electrical equipment for measurement, control and
laboratory use
Conforms to the following directives :
2006 / 95 / EC The Low Voltage Directive
2004 / 108 / EC The Electromagnetic Compatibility Directive
has been designed and manufactured to the following specifications :
EN 61000-6-4:2007 EMC Generic Emission Standard for the Industrial Environments
EN 61000-6-2:2005 EMC Generic Immunity Standard for the Industrial Environments
EN 61010-1:2001 Safety Requirements for electrical equipment for measurement, control
And laboratory use
When and Where Issued Authorized Signature
th
16 October 2009 Name : Serpil YAKIN
Bursa-TURKEY Position : Quality Manager
EU DECLARATION OF CONFORMITY

ESM series process controllers are designed for measuring and controlling temperature
and any process value.They can be used in many applications with their universal process input,
control outputs, selectable alarm functions.
Some application fields and an application which they are used are listed below:
5
Application Fields Application
Glass PID Process Control
Plastic
Petro-Chemistry
Textile
Automative
Machine production industries
1.Preface
1.1 General Specifications
Alarm Output-1
(Relay Output)
Process Input
Power Supply
Input
ESM-7730
Heating-Cooling
Function
ON/OFF, PID Operation
Auto-Tune, Self-Tune
Automatic/Manual
Operation
Process Output
(SSR Driver Output)
Process Output or
Alarm Output-2
(Relay Output)
Control Output
Alarm Output
Control Output
Standard
Universal Process Input
TC, RTD,
ZVoltage/Current
Universal Supply Input
100-240 V V, 50/60Hz
Low Voltage (optional)
Supply Input
24V V50/60Hz ,24V Z,12V Z
Standard
Standard
Standard

6
ESM-7730 (72x72 DIN Size)
Supply Voltage
A
A
20
1
0
Configurable (Table-1) Table-1
None
BC D E FG HI /
/
U V W Z/
/
Input Type
Output-1
Serial Communication
Scale
BC
E
HI
D
All order information of ESM-7730 are
given on the table at left. User may form
appropriate device configuration from
information and codes that at the table and
convert it to the ordering codes.
Firstly, supply voltage then other
specifications must be determined. Please
fill the order code blanks according to your
needs.
Please contact us, if your needs are
out of the standards.
1.2 Ordering Information
1
01
Output-2
FG
Output-3
02
100-240V V(-15%;+10%) 50/60Hz
24 V V(-15%;+10%) 50/60Hz 24V Z(-15%;+10%)
1
2
Customer (Maximum 240V V(-15%;+10%))50/60Hz
9
01 02
VÞVac,
ZÞVdc
ÞVdc or Vac can be
applied
W
c
Table-1
21
39
41
40
42
43
44
45
22
23
25
27
28
29
31
33
35
37
24
26
30
32
34
36
38
L ,Fe Const DIN43710
PT 100 , IEC751(ITS90)
0...50 mV Z
PT 100 , IEC751(ITS90)
0...5 V Z
0...10 V Z
0...20 mA Z
4...20 mA Z
L ,Fe Const DIN43710
J ,Fe CuNi IEC584.1(ITS90)
K ,NiCr Ni IEC584.1(ITS90)
R ,Pt13%Rh Pt IEC584.1(ITS90)
S ,Pt10%Rh Pt IEC584.1(ITS90)
T ,Cu CuNi IEC584.1(ITS90)
B ,Pt30%Rh Pt6%Rh IEC584.1(ITS90)
E ,NiCr CuNi IEC584.1(ITS90)
N ,Nicrosil Nisil IEC584.1(ITS90)
C , (ITS90)
T ,Cu CuNi IEC584.1(ITS90)
B ,Pt30%Rh Pt6%Rh IEC584.1(ITS90)
E ,NiCr CuNi IEC584.1(ITS90)
N ,Nicrosil Nisil IEC584.1(ITS90)
C , (ITS90)
J ,Fe CuNi IEC584.1(ITS90)
K ,NiCr Ni IEC584.1(ITS90)
-100°C,850°C
-200°C,650°C
-1999,9999
-199.9°C,650.0°C
-100.0°C,850.0°C
-200°C,900°C
-200°C,1300°C
0°C,1700°C
0°C,1700°C
-200°C,400°C
44°C,1800°C
-150°C,700°C
-200°C,1300°C
0°C,2300°C
-199.9°C,900.0°C
-199.9°C,999.9°C
-199.9°C,400.0°C
44.0°C,999.9°C
-150.0°C,700.0°C
-199.9°C,999.9°C
0.0°C,999.9°C
-148°F ,1562°F
-328°F,1202°F
-199.9°F,999.9°F
-148.0°F,999.9°F
-328°F,1652°F
-328°F,2372°F
32°F,3092°F
32°F,3092°F
-328°F,752°F
111°F,3272°F
-238°F,1292°F
-328°F,2372°F
32°F,3261°F
-199.9°F,999.9°F
-199.9°F,999.9°F
-199.9°F,752.0°F
111.0°F,999.9°F
-199.9°F,999.9°F
-199.9°F,999.9°F
32.0°F,999.9°F
Input Type(TC)
Input Type(RTD)
Input Type( ZVoltage and Current)
Scale(°C)
Scale(°C)
Scale
Scale(°F)
Scale(°F)
BC
BC
BC
-1999,9999
-1999,9999
-1999,9999
-1999,9999
0
Relay Output (5A@250 VVat resistive load)
Relay Output (5A@250 VVat resistive load)
SSR Driver Output ( Maximum 17mA, 25V Z)

7
1.3 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and responsibilities which are determined in
warranty document and instruction manual performs by the customer completely.
1.4 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device
before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.

8
In package ,
- One piece unit
- Two pieces mounting clamps
- One piece instruction manual
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified
mechanical and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power
off the system and separate the electrical connection of the device from the system.
The unit is normally supplied without a power switch or a fuse. Use power switch and fuse
as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to
prevent failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble
with the unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may
results in malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During the equipment is putted in hole on the metal panel while mechanical installation
some metal burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s fixing clamps. Do not do the
montage of the device with inappropriate fixing clamp. Be sure that device will not fall
while doing the montage.
It is your responsibility if this equipment is used in a manner not specified in this
instruction manual.
Before beginning installation of this product, please read the instruction
manual and warnings below carefully.
2.Installation
c

9
Terminal protection cover
Product Label
Mounting Clamp
Front Panel
IP65 protection
NEMA 4X
Maximum 15mm / 0.59 inch
Panel surface
(maximum thickness 15mm / 0.59 inch)
72mm / 2.83 inch
72mm / 2.83 inch
2.1 General Description
2.2 Dimensions
76mm / 2.99 inch
11.5 ± 1 mm /0.45 inch
°C
°F
VV
PO
AO1
AO2
A
AT PSET ASET1 ASET2
M
SET
Process Controller
ESM-7730
PAT A/M

10
2.3 Panel Cut-Out
97 mm / 3.82 inch (min)
97 mm / 3.82 inch (min)
69mm / 2.72 inch
69mm / 2.72 inch

c
11
2
3
11-Before mounting the device in your
panel, make sure that the cut-out is of the
right size.
2-Check front panel gasket position
3-Insert the device through the cut-out. If
the mounting clamps are on the unit, put out
them before inserting the unit to the panel.
2.5 Panel Mounting
Operating Temperature : 0 to 50 °C
Max. Operating Humidity : 90% Rh (non-condensing)
Altitude : Up to 2000m.
Operating Conditions
Forbidden Conditions:
Corrosive atmosphere
Explosive atmosphere
Home applications (The unit is only for industrial applications)
2.4 Environmental Ratings
c
During installation into a metal panel, care should be taken to avoid injury from
metal burrs which might be present. The equipment can loosen from vibration
and become dislodged if installation parts are not properly tightened. These
precautions for the safety of the person who does the panel mounting.

Before starting to remove the unit from panel, power off the unit and the related
system.
Montage of the unit to a system must be done with it’s own fixing clamps. Do not
do the montage of the device with inappropriate fixing clamps. Be sure that
device will not fall while doing the montage.
c
c
12
12
1
2
3
2.6 Installation Mounting Clamp
2.7 Removing from the Panel
1-Loosen the screws.
2-Pull mounting clamps from top
and bottom fixing sockets.
3-Pull the unit through the front
side of the panel
The unit is designed for panel
mounting.
1-Insert the unit in the panel cut-out
from the front side.
2- Insert the mounting clamps to the
holes that located top and bottom
sides of device and screw up the fixing
screws until the unit completely
immobile within the panel

13
1
10
2
11
3
12
4
13
5
14
6
15
7
16
8
17
9
18
0,5Nm aa
6 mm / 0.236 inch
Wire Size:
18AWG / 1 mm²
Solid /Stranded
18 screws terminal
M3
Empty terminals
Torque 0.5 Nm
Screw driver
You must ensure that the device is correctly configured for your application.
Incorrect configuration could result in damage to the process being controlled,
and/or personal injury. It is your responsibility, as the installer, to ensure that
the configuration is correct.
Parameters of the device has factory default values. These parameters must be
set according to the system’s needs.
Only qualified personnel and technicians should work on this equipment. This
equipment contains internal circuits with voltage dangerous to human life.
There is severe danger for human life in the case of unauthorized intervention.
Be sure to use the rated power supply voltage to protect the unit against
damage and to prevent failure.
Keep the power off until all of the wiring is completed so that electric shock and
trouble with the unit can be prevented.
3.Electrical Wiring
c
c
c
c
3.1 Terminal Layout and Connection Instructions

14
Sensor or Transmitter
Supply Input
24 V Z
Max 50mA
TC
Pt-100
0 to 50mV Z
0 to 10V Z
0 to 20mA Z
Universal
Process Input
(TC, RTD, ZVoltage/Current)
Standard Process Output
SSR Driver Output
Process Output
or
Alarm Output-2
Relay
Alarm Output-1
Relay
1
10
2
11
3
12
4
13
5
14
6
15
CAT II
P/N : ESM-7730
Y
c
78 9
16 17 18
a
Process Out
Max. 17mA, 25V Z
Process measurement input is in CAT II class.
ii
Supply Voltage Input
100-240V V(-15%;+10%) 50/60Hz - 6VA
24 V V(-15%;+10%) 50/60Hz - 6VA
24V Z(-15%;+10%) - 6W
12V Z(-15%;+10%) - 6W
(It must be determined in order)
ALARM OUT-1
5A@250VV
NO CNC
(ALARM OUT-2)
PROCESS OUT
5A@250VV
NO CNC
3.2 Electrical Wiring Diagram
Electrical wiring of the device must be the same as ‘Electrical Wiring Diagram’
below to prevent damage to the process being controlled and personnel injury.
c

15
3.3 View of the Labels
4Z
2V
0 to 20mAZ0 T 50 IP65/IP20

3.4 Connection of Device Supply Voltage Input
16
c
c
c
100 - 240 V V
(-15%;+10%) 50/60 Hz 24V V(-15%;+10%) 50/60Hz
11
NL
12
otN e-1
Y
11
L
12
Y
c
or 24V Z(-15%;+10%)
c
aa
External
Fuse
(1 A VT)
External
Fuse
(24V V: 1 A VT)
(24V Z: 1 A ZT)
Note-2
N
Fuse
Fuse
Note-3
Note-3
Universal Supply
Voltage Connection Low Voltage 24 VW
Supply Voltage Input
Supply Voltage
Power
Supply
Switch
Power
Supply
Switch
ot 1N e-
Supply Voltage
Note-1 :There is an internal 33R W fusible flameproof resistor in 100-240 VV50/60Hz supply
voltage input
There is an internal 4R7 W fusible flameproof resistor in 24VV50/60Hz , 24VZsupply voltage
input
Note-2 : “L” is ( + ) ,” N” is ( - ) for 24V Z supply voltage
Note-3 : External fuse is recommended.
Make sure that the power supply voltage is the same indicated on the
instrument.
Switch on the power supply only after that all the electrical connections have
been completed.
Supply voltage range must be determined in order. While installing the unit,
supply voltage range must be controlled and appropriate supply voltage must
be applied to the unit. Controlling prevents damages in unit and system and
possible accidents as a result of incorrect supply voltage.
There is no power supply switch on the device. So a power supply switch must
be added to the supply voltage input. In accordance with the safety regulations,
the power supply switch shall bring the identification of the relevant
instrument.Power supply switch shall be easily accessible by the user.
Power switch must be two poled for seperating phase and neutral. On/Off
condition of power switch is very important in electrical connection. On/Off
condition of power switch must be signed for preventing the wrong connection.
If an external fuse is used, it must be on phase connection in Vsupply input.
If an external fuse is used, it must be on (+) line connection in Zsupply input.
The instrument is protected with an internal fuse (Please refer to Note1 for
information). In case of failure it is suggested to return the instrument to the
manufacturer for repair.

17
3.5.1 TC (Thermocouple) Connection
3.5 Process Input Connection
3.5.2 RTD Connection
Note 1 : In 3-wire system, use always cables of the same diameter (min 1mm²) Always use
wires of the same gauge and type whether a 2-wire or 3-wire system.
Note 2 : Install a jumper between terminals 2 and 3 when using a 2-wire RTD.
Note 3 : If the distance is longer than 10 meters, use 3-wire system
3-wire Pt-100 connection
(with line compensation)
(Max. Line impedance is 10 W)
2-wire Pt-100 connection
(without line compensation)
1 12 23 3
Pt-100
Note 1 Note 2
Pt-100
123
TC Connect the wires with the polarity as shown in the
figure at left.
Always use compensation wire corresponding to the thermocouple used. If
present, the shield must be connected to a proper ground.
ii
Input resistance is greater than 10M W
ii
Input resistance is greater than 10M W
ii
Always use compensation wire corresponding to the thermocouple
used. If present, the shield must be connected to a proper ground.

3.5.3 Connection of Serial Transmitters With Current Output (Loop Powered) to the
Process Input
18
3.5.4 Connection of 3-wire Transmitters with Current Output to the Process Input
Transmitter connection by using supply
voltage on the device
Transmitter connection by using external supply
voltage source.
Transmitter Transmitter
External
Supply
Voltage
PV PV
1 1
3 3
4 4
Transmitter connection by using supply
voltage on the device
Transmitter connection by using external supply
voltage source.
Transmitter Transmitter
External
Supply
Voltage
mA Z
PV PV
1 1
3 3
4 4
24 V Z
Max. 50mA
Note 1
Note 1
Note 1 : External power supply must be selected according to supply voltage range and
required current for transmitter.
Note-1 : External power supply must be selected according to supply voltage range and
required current for transmitter.
Input resistance is 2R7 W.
ii
Input resistance is 2R7 W.
ii
mA Z
24 V Z
Max. 50mA
mA Z
24 V Z
Max. 50mA
mA Z
24 V Z
Max. 50mA

19
3.5.5 Connection of Transmitters with Voltage Output to the Process Input
Transmitter connection by using supply
voltage on the device
Transmitter connection by using external supply
voltage source.
Transmitter Transmitter
External
Power
Supply
Note-1
mV, V Z
PV PV
1 1
2 2
4 4
Note-1 : External power supply must be selected according to supply voltage range and
required current for transmitter.
24 V Z
Max. 50mA
24 V Z
Max. 50mA
mV, V Z
Input resistance is greater than 10M W for 0...50mV Z
Input resistance is 43K W for 0...10V Z
ii

20
3.6 Galvanic Isolation Test Values of ESM-7730 Process Controller
Supply Voltage
Input
17
18 Ground 1
Process Output
(SSR Driver Output)
Process Output or
Alarm Output-2
Relay
Analog
Inputs
Alarm Output-1
Relay
2
3
2000VV(For ESM-7730.1..... )
500V V( For ESM-7730.2..... )
2000V V
2000V V
2000V V
2000V V
2000V V
2000V V
24V ZVoltage
Output
2000V V
8
9
8
9
10
12
2
3
44
10
12
11 11
13
15
13
15
14 14
This manual suits for next models
2
Table of contents
Other EMKO Controllers manuals

EMKO
EMKO EAOM-36 Series User manual

EMKO
EMKO EAOM-9F ND User manual

EMKO
EMKO EZM-4950 User manual

EMKO
EMKO ESM-4410 User manual

EMKO
EMKO EAOM-72F User manual

EMKO
EMKO PID QUADRO EPLC9600 User manual

EMKO
EMKO EAOM-9F ND User manual

EMKO
EMKO esm-4450 User manual

EMKO
EMKO EAOM-210 FLJ User manual

EMKO
EMKO ESM-4930 User manual
Popular Controllers manuals by other brands

IMG STAGE LINE
IMG STAGE LINE RGBL-100T instruction manual

smart home
smart home RemoteLinc 2 INSTEON 2444A2 quick start guide

digitalview
digitalview SVX-1920 instructions

Tolomatic
Tolomatic IMA Series manual

Samwontech
Samwontech TEMI1000 Series Operation manual

K-Rain
K-Rain BL-KR V1.0 Instructions for use