Translation of the original instructions
CANopen®, DeviceNet® are registered trademarks of the respective trademark
owners in certain countries.
1 Further applicable documents
All available documents for the product èwww.festo.com/pk.
2 Safety
2.1 Safety instructions
– Do not connect or disconnect plug connector when powered.
– Before starting mounting work: Switch off power supply.
– Observe tightening torques.
2.2 Intended use
Connecting cable with connection technology M12x1, A-coded to EN61076-2-101
for CANopen and DeviceNet.
3 Configuration
3.1 Product design
1Socket (1x)
2Wire end (5x)
3Cable (1x)
Fig. 1
3.2 Pin allocation
Port1Pin Wire colour1) Function
1 – Screening
2 RD V+
3 BK V–
4 WH CAN_H
5 BU CAN_L
1) Colour code in accordance with IEC 60757:1983-01
Tab. 1 Pin allocation
4 Mounting
4.1 Mounting, field device side
1. Connect socket1 to the matching plug connector.
2. Tighten the screw-type lock of the socket1.
4.2 Mounting, controller side
1. Shorten and pre-assemble wire ends as needed.
2. Connect the wires in accordance with the pin allocation.
4.3 Installation
Mounting in energy chain
1. Lay the chain out lengthwise.
2. Place the cables in the chain, making sure they are not twisted.
3. Separate cables from each other using separators/drill holes.
4. Do not connect cables together.
Fig. 2
5. Maintain spaceX. X>10% of the cable diameterD.
If the chain is suspended vertically, increase the spaceX.
Fig. 3
6. Align chain in the operating position:
– Make sure that the radius is greater than the bending radius R of the
cables.
– Cables can move freely in the bending radiusKR of the energy chain.
ÄCables are not forced through the chain.
7. Mount chain (ècorresponding assembly instructions).
8. Fasten cables:
– At both ends of the chain in case of short energy chains (è Fig.4).
– Only at the driver end in the case of long, sliding energy chains (è Fig.5).
Fig. 4
Fig. 5
9. Do not bend cables all the way to the fastening point.
ÄMounting spaceA between the fastening point and bending movement is
observed.
NOTICE!
Damage to cables if the chain breaks.
• Replace cables after a chain break.
NOTICE!
Malfunction and material damage due to vertically suspended cables.
The cables stretch.
• Regularly check the length of the cables.
• Readjust the cables if required.
5 Technical data
NEBC-M12G5-ES-...-LE5-CO
Cable characteristic Suitable for energy chains
Cable composition [mm²] (2x0.34) + (2x0.25) + 0.34
Shielding Shielded
Cable diameter D [mm] 6.7
8081599
Connecting line
NEBC-M12G5-ES-...-LE5-CO
8081599
2017-11
[8081601]
Instructions| Assembly
Festo SE & Co. KG
Ruiter Straße 82
73734 Esslingen
Germany